The question
A maximum demand calculation ends in amps. A network connection application asks for kVA. The estimator holds 250 A per phase at 400 V. The network company wants one number in kVA before the design goes out for pricing.
The inputs
- Phases: 3
- Voltage: 400 V
- Current: 250 A
- Power factor: 0.9
The 250 A comes from the maximum demand step. The 0.9 is an assumed power factor for a mixed commercial load. Use the measured figure where one exists, and state the assumption on the application where one does not.
The clause
AS/NZS 3000:2018 Cl 2.2.2 sets how maximum demand is established for an installation. The Electricity (Safety) Regulations 2010 reg 28 covers the connection of an installation to works. The network company sets its own application form and its own required content.
The steps
The tool multiplies the line voltage by the line current, then by the square root of three.
- Apparent power: 173.21 kVA
It applies the power factor for the real power. It takes the remaining leg of the power triangle for the reactive power.
- Real power: 155.88 kW
- Reactive power: 75.5 kvar
The result
The application figure is 173.21 kVA. That is the number the network company uses to check the transformer, the fuse and the low voltage main.
The 155.88 kW figure is the one the client recognises, because it matches equipment nameplates and energy bills. The two are not interchangeable on an application. A form filled with 155.88 kW where it asks for kVA understates the demand. The connection can come back undersized.
The 75.5 kvar figure rarely appears on the form. It still matters, because a network company that applies a power factor requirement judges the connection on it.
Where the estimate goes wrong
The power factor is a guess. A connection with large motor load sits below 0.9 and needs more kVA for the same kW. A connection that is mostly lighting, heating and corrected drives sits above it.
Diversity is already in the 250 A. Do not apply a second diversity factor to the kVA. The maximum demand step has applied it once.
Future load is not in the figure. A tenancy fitout, an EV charger bank or a heat pump upgrade lands after the connection is fixed. Ask the client for the ten-year view. Apply the allowance before the application goes in, not after the transformer is set.
Starting current is separate. The kVA figure describes steady load. A large direct-on-line motor draws a short surge far above it. The network company may ask for that figure on its own.
Before the form goes in
Collect four items with the kVA figure.
The phase count and the voltage. 173.21 kVA at 400 V three‑phase is a different connection from the same kVA at 230 V single‑phase.
The assumed power factor. State the 0.9 on the form so the network company can see the basis.
The method behind the 250 A. AS/NZS 3000:2018 Cl 2.2.2 allows more than one method, and the network company may ask which one produced the demand.
The largest single motor or load step. That figure drives flicker and starting checks, and it sits outside the steady kVA.
This page is a design aid. Verify every value against the current edition of the standard.