AmpSize

Updated

AU editions, 2025 and 2017

AS/NZS 3008.1.1 has two editions AmpSize can read for Australia. What the Edition select offers, what a link with no edition holds, and what a new job changes.

An Australian calculation, such as Cable size set to AU, reads its cable tables from AS/NZS 3008.1.1. It gives the current-carrying and volt drop values. Two editions of that part exist: 2025 and the superseded 2017 edition. New Zealand's part, AS/NZS 3008.1.2, has one edition, so its calculations carry no edition choice.

An Edition select appears on an AU form only, right after the Standard select. A new AU calculation starts on 2025. Choosing 2017 reproduces an older design on the superseded tables.

Both editions read the same reference conditions: 40 °C air and 25 °C soil. The 2025 tables renumber, and some current ratings move; d.c. ratings now extend to 1500 V.

A saved calculation or a shared link with no edition recorded reads 2017, forever. This keeps an old link's answer stable even after the default edition moves. A New Zealand link never carries an edition key at all.

See the guide below for four circuits run on both editions. It compares the size, table and clause each one now cites.