Transformer inrush me tōna breaker
Tirohia te inrush whakahoki o tētahi transformer ki tōna breaker.
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Stop a transformer tripping its breakerWhy an isolation transformer trips a Type B breaker at switch-on, and what holds.
- Pick a breaker for a site transformerThe breaker and cable for a portable site transformer.
- Check a control transformer breakerWhether a small control transformer on an extra-low voltage secondary holds its breaker.
- Size the breaker for a step-down transformerThe smallest breaker of each type for a single‑phase step-down transformer.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Reiti
- 15 kVA
- Ngā wāhanga
- Wāhanga toru
- Voltage tuatahi
- 400 V
- Whakahiato tuarua
- 400 V
- Ngā ara iahiko i te taha tuarua
- Kotahi, kāore he whakamarumaru tōna ake
- Whakaruruhau, × au utanga katoa
- 12
- Ka roa te whakaruruhau
- 0.1 s
- Momo kaiwhakatere
- Kauwhata C
- Reiti
- 32 A
Te pirenga i te wā whakahiko
Ka pea ka tripi
- Iahiko inrush
- 259.8A
- Au utu katoa tuatahi
- 21.65A
- Te Type B iti rawa e pupuri ana
- 100 A
- Te Type C iti rawa e pupuri ana
- 63 A
- Te Type D iti rawa e pupuri ana
- 32 A
- Ngā kaiwhakahaere tuarua, iti rawa
- 21.7A
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Au kawe kī katoa tuatahi21.65A
- Au whakaurunga, 12 × te au utu katoa mō te 0.1 s259.8A
- Momo C 32 A, whānui wawe noa mai i160A
- Momo C 32 A, whānui wawe noa ki320A
- Te pirenga i te wā whakahikoHuaKa pea ka tripi
- Te Type B iti rawa e pupuri ana100 A
- Te Type C iti rawa e pupuri ana63 A
- Te Type D iti rawa e pupuri ana32 A
- Ngā kaiwhakahaere tuarua, iti rawa21.7A
AS/NZS 3000:2018 Cl 4.14.2.2
Mō tēnei tātaitai
How this is calculated
When a transformer is switched on, its core can draw a large current for a few cycles while the magnetic flux settles. This inrush can be ten or more times the full load current. It lasts about a tenth of a second, and it is often enough to trip the breaker on the primary. This tool checks whether it does, and finds a breaker that rides through it.
The tool takes the primary full load current from the transformer tool, then multiplies it by the inrush multiple you enter, for the time you enter. No standard on hand prints these two figures, so they are your assumptions. Take them from the maker's data sheet. The multiple is a peak, and the tool compares it with the breaker's band, which is given in RMS multiples of the rating, as if it were RMS: that errs towards a trip.
It then places that current on the trip band of the breaker, the same band the MCB trip curve tool draws. The breaker holds when the band's earliest trip is no sooner than the inrush lasts. It trips when the latest trip is sooner, and it may trip in between. For each type, B, C and D, the tool finds the smallest rating that carries the full load current and holds.
With one circuit on the secondary and no protection there, AS/NZS 3000 lets the secondary cable go without its own breaker if it carries the primary current scaled by the voltage ratio. The tool gives that current.
| Step | Table or clause | What it decides |
|---|---|---|
| Full load current | The transformer tool | The current the inrush multiplies |
| Inrush | The multiple and time you enter | The current and time the breaker sees |
| The breaker's band | AS/NZS 3000 Cl 2.5.3.1 and Table 8.1, and a typical band | Holds, may trip or trips |
| The secondary cable | AS/NZS 3000 Cl 4.14.2.2 Exception | The least capacity of an unprotected secondary cable |
| An extra-low voltage transformer | AS/NZS 3000 Cl 4.14.1 Exception 2 | Whether Cl 4.14 applies at all |
Worked examples
- A 15 kVA three‑phase isolation transformer on a C32 draws 259.8 A of inrush, inside the C32's typical instant band, so the breaker may trip at switch-on. A 32 A Type D holds.
- The same transformer on a D32 holds the 259.8 A and passes. The 32 A Type D is also the smallest D that carries the 21.65 A load.
- The same transformer on a B32 fails: the inrush is past the top of the typical instant band and the breaker trips. A 32 A Type D would hold.
- A 3 kVA 230/110 V site transformer on a C16 may trip on its 156.5 A inrush. A 16 A Type D holds, and the 110 V cable needs at least 27.3 A.
- A 10 kVA 400/230 V transformer, 10 × inrush, on a D32 holds and passes. A 32 A Type D is the smallest D that holds.
Limits
The inrush depends on where on the wave the transformer is switched and on the flux left in the core, so it differs from one switch-on to the next. The tool uses one figure for the peak and one for the time. A toroidal transformer can draw much more than a laminated one. A soft-start or inrush limiter changes the figures; enter what the maker gives.
The breaker's band is typical of its type, not a maker's curve. The tool does not check a fuse or a moulded-case breaker.
See also: MCB trip curve, Transformer and Cable size.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He aha te transformer e trip ai tōna breaker ina whakahohea?
Ka tango te core i tētahi iahiko magnetising nui mō ētahi huringa iti i te wā e noho ai tōna flux. Ka taea te inrush te 10 ōna iahiko uta katoa neke atu rānei. Mēnā ka tae ki te pae wawe o te breaker, ka taea e te breaker te trip.
He rahi pēhea te iahiko transformer inrush?
Ka whakawhirinaki ki te hoahoa me te wāhi o te ngaru i whakahohea ai. Ko te 10 ki te 12 ōna iahiko uta katoa mō te 0.1 s pea, he tuku tuatahi noa. Ka taea e te toroidal transformer te tango nui ake. Ko te data sheet a te kaihanga e hoatu ana i te tauāhua pono.
Ko tēhea kauwhata circuit-breaker e pai ana mō tētahi transformer?
I te nuinga o te wā, he Type D, ā, ko tōna pae wawe ka tīmata i te 10 ōna reiti. Me reiti nui ake te Type C mō taua inrush ōrite, ā, me nui atu anō te Type B. Ka kimihia e te taputapu te reiti iti rawa o ia momo e pūmau ana.
Me whai breaker motuhake te taura secondary?
Ka whakaaetia e AS/NZS 3000 Cl 4.14.2.2 kia kore he whakamaru i tētahi ara iahiko secondary kotahi, ina kawe tōna taura i te iahiko primary whakatauhia whakareia ki te rōnaki voltage primary ki te secondary. Ina nui ake ngā ara iahiko, whakamarutia ia tētahi.
Ko te pae circuit-breaker te kauwhata a te kaihanga?
Kāo. He pae arowhānui mō te momo, ko tērā anō e tārua ana e te taputapu MCB Trip Curve. Mēnā ko te putanga he May trip, arotakehia te kauwhata a te kaihanga, kōwhiria rānei te reiti e whai ake nei.
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 4.14.1Transformers outside Cl 4.14
- AS/NZS 3000:2018 Cl 4.14.2.2Transformer secondary circuits
- AS/NZS 3000:2018 Cl 2.5.3.1Operating points of circuit-breakers and fuses
- AS/NZS 3000:2018 Cl 4.14Transformer secondary circuits
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 2 Oct 2026.
Ngā taputapu hononga
- Tātaitai TransformerCalculate transformer full load current and impedance.Kāore he paerewa
- Trip curve MCB me te rohe tauraPlot an MCB trip band against the cable it protects.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1
- Te rahi transformer mai i te demandSize a transformer from the demand, with growth and losses.Kāore he paerewa