Construction site supply calculator
Supply, RCD and test rules for a construction site.
Reads AS/NZS 3012:2019. Tables checked 1 Oct 2026.
Try a job 6
Each job fills in example values. Replace them with your values.
- Supply a building site from a generatorThe RCD protection for tools on a construction site generator.
- Supply a site from the house boardThe rules when the permanent switchboard feeds the site.
- Supply site wiring from an inverterThe rules for an RCD-protected inverter supply.
- Supply a welder from a generating setThe rule for an arc welder built into a generating set.
- Use hire equipment on a siteThe inspection and RCD rules for hired equipment.
- Supply a site in AustraliaThe same pole against the Australian rules.
Inputs
Worked example with the default inputs. The live calculator replaces it when the page loads.
- Country
- New Zealand
- Supply source
- An electricity distributor's main
- Circuit
- A final sub-circuit that starts at the construction switchboard
- Exception that applies
- None
- What you are verifying
- Portable gear you carry to the job: tools and appliances, leads, cord extension sets, generators and inverters
- The RCD is a portable RCD
- Yes
- This is hire equipment
- No
- An arc welder is incorporated into the generating set
- No
RCD-based additional protection
Required, 30 mA
- Supply clause
- AS/NZS 3012:2019 Cl 2.1.1(a)
- Protection clause
- AS/NZS 3012:2019 Cl 2.4.6.1
- Inspection and test interval
- 3months
- RCD push-button test
- Connect the portable RCD to the supply socket, then press its test button before you connect equipment. Do this again every day while it is in use
- RCD operating time test
- 3months
This result is a design aid. Verify it against the current standard.
Calculation steps
- Supply arrangementAn electricity distributor's main
AS/NZS 3012:2019 Cl 2.1.1(a)
- Additional protection requiredYes
AS/NZS 3012:2019 Cl 2.4.6.1
- Maximum rated residual current30mA
AS/NZS 3012:2019 Cl 2.4.6.1
- Inspection and test interval3months
AS/NZS 3012:2019 Table 6
- RCD push-button testConnect the portable RCD to the supply socket, then press its test button before you connect equipment. Do this again every day while it is in use
AS/NZS 3012:2019 Table 6
- RCD operating time test3months
AS/NZS 3012:2019 Table 6
- Socket-outlets on a switchboard10A
AS/NZS 3012:2019 Cl 2.3.4
- Isolating switch marking height6mm
AS/NZS 3012:2019 Cl 2.4.4
About this calculator
How this is calculated
The tool gives the supply arrangement and the RCD protection for a construction or demolition site. It reads AS/NZS 3012:2019.
- Supply arrangement. You pick the source, such as a distributor main. The tool finds the supply clause, here Cl 2.1.1(a).
- Additional protection. It reads Cl 2.4.6.1 for the circuit type and the exceptions. It says whether RCD protection is required.
- Residual current. It gives the maximum rated residual current for that circuit.
- Test intervals. It reads Table 6 for the inspection and test interval of the equipment.
- RCD tests. Table 6 also gives the push-button test and the operating time test.
- Switchboard points. It points at Cl 2.3.4 for socket-outlets and Cl 2.4.4 for the isolating switch marking.
Worked example
- Final subcircuit from a distributor main, portable equipment. RCD protection is required at 30 mA. The inspection and test interval is 3 months. The operating time test is also 3 months. The push-button test is daily while the RCD is in use.
Limits
The RCD must trip on every active conductor and the neutral. Where a board feeds two or more lighting circuits, spread them across the RCDs. New Zealand sites also complete a Record of Assessment in the Appendix G form. The tool does not size cable. It does not check the cord length.
The tool gives one supply arrangement at a time. Pick the arrangement that matches the board in front of you. Then read the clause the tool names. Test the RCD on the site, as the intervals say. Record the results with the date.
See also: Construction site supplies to AS/NZS 3012, Builder's pole, RCDs and cord lengths and Site cord length.
Questions
Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.
What does the construction site supply tool do?
The tool reports the supply arrangements allowed on a site under construction or demolition, the RCD protection for the circuit, and the inspection and test intervals for the equipment. It works to AS/NZS 3012:2019.
What RCD does a construction site need?
Clause 2.4.6.1 protects every final sub-circuit run from the construction switchboard with an RCD of at most 30 mA, tripping on every active conductor and the neutral. Three exceptions apply: mechanical operation at risk, SELV or PELV supply, and a safety isolating transformer.
How often are site RCDs tested?
Plug in a portable RCD, or start the generator or inverter that carries one, then press its test button before you connect equipment. Do this every day it is in use. Press a fixed RCD's test button monthly. Do the operating-time test every 3 months on a portable RCD, every 12 months on a fixed one.
Which supplies are allowed on a site?
Clause 2.1.1 allows an electricity distributor's main, an existing switchboard of the permanent installation, a low voltage generating set complying with and installed to AS/NZS 3010, or an inverter to AS/NZS 4763. That is AS/NZS 3012:2019; the 2010 edition also named AS 2790 for the generator. Isolated winding types supply only a separated circuit.
Does the tool cover insulation resistance for welders?
Yes, but only for arc welders built into generating sets, which is the scope Clause 3.5.4 gives Table 7 of AS/NZS 3012:2019. Other equipment follows AS/NZS 3760 instead; AmpSize's Test and Tag tool covers those checks.
Clauses and tables this tool reads
- AS/NZS 3012:2019 Cl 2.4.6.1Additional protection for a site under construction or demolition
- AS/NZS 3012:2019 Cl 3.4Verification of RCDs on site
- AS/NZS 3012:2019 Cl 2.1.1, 2.1.2, 2.4.6Permitted supply arrangements for a site under construction or demolition
- AS/NZS 3012:2019 Cl 2.4.6 and Table 6RCD protection and periodic verification intervals for a site under construction or demolition
- AS/NZS 3012:2019 Table 7Minimum insulation resistance for arc welders incorporated into generating sets
Every clause and table, with how each was verified
Tables last checked on 1 Oct 2026.
Related tools
- Show and carnival wiring checkerShow wiring RCD checks, plus site wiring depth and height.AS/NZS 3002Electricity (Safety) Regulations 2010
- Wet area zones checkerFind the Section 6 zone, IP and RCD near water.AS/NZS 3000
- Site cord length calculatorThe longest a cord or cable may run on a construction site.AS/NZS 3012