Simplified cable selector

Read the Appendix C device rating and voltage drop tables.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Try a job 6

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Cable size
2.5 mm²
Phases
Single phase, 230 V
Installation condition
Unenclosed in air
Design current
20 A
Route length
25 m
Voltage drop limit
5 %

Maximum device rating

25A

Voltage drop
3.91%
Ampere metres
500
Size for the drop limit
2.5mm²

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Maximum device rating InResult25A

    AS/NZS 3000:2018 Tables C6 and C7

  2. Ampere metres500

    AS/NZS 3000:2018 Table C8

  3. Ampere metres per percent for this size128

    AS/NZS 3000:2018 Table C8

  4. Voltage drop3.91%

    AS/NZS 3000:2018 Table C8

  5. Ampere metres per percent needed for the limit100

    AS/NZS 3000:2018 Table C8

  6. Smallest size for the voltage drop limit2.5mm²

    AS/NZS 3000:2018 Table C8

About this calculator

How this is calculated

The tool reads the simplified tables of AS/NZS 3000 Appendix C. They cover copper cable from 1 mm² to 25 mm². They give the largest device rating and the voltage drop in one pass.

  1. Maximum device rating. The tool reads the rating for your size, phases and installation condition from Tables C6 and C7.
  2. Ampere metres. It multiplies the load current by the one-way length.
  3. Ampere metres per percent. It reads the value for your size from Table C8.
  4. Voltage drop. It divides the ampere metres by that value. The result is the drop in percent.
  5. Size for the limit. It divides the ampere metres by your limit. It then picks the smallest size from Table C8 that meets the figure.
StepTable or clauseWhat it decides
Device ratingAS/NZS 3000 Tables C6 and C7The largest device for the size and condition
Drop and sizeAS/NZS 3000 Table C8The drop for the run and the size for your limit

Worked example

  • 2.5 mm² on one phase over 25 m at 20 A. The cable is in unenclosed air. The maximum device rating is 25 A. The run is 500 ampere metres. The drop is 3.91 %, inside the 5 % limit. The size for the limit is 2.5 mm².

Limits

The tables assume one circuit on its own. Where circuits are grouped, use the cable size calculator. The tool does not apply correction factors. It does not read AS/NZS 3008.1 tables. It stops at 25 mm².

See also: Cable size for a 32 A single-phase run of 25 m, AS/NZS 3000 Clause 3.6.2 voltage drop limit and Voltage drop basics.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the simplified selector do?

The tool reads AS/NZS 3000:2018 Tables C6 and C7 for the largest protective device a cable from 1 to 25 square millimetres may carry. It then reads Table C8 for the voltage drop over the run and the smallest size that meets the limit.

When should I use the full cable size tool instead?

Use the cable size tool when circuits are grouped, when the ambient temperature is not 30 degrees, when the cable is not PVC two-core or four-core and earth, or when the size is above 25 square millimetres. Appendix C assumes one circuit on its own.

How is the voltage drop worked out?

Multiply the design current by the route length to get ampere metres. Divide that by the ampere metres per percent for the size in Table C8. The answer is the drop as a percent of 230 volts single phase or 400 volts three phase.

Which installation condition should I pick?

Match the way the cable sits. A cable clipped in free air reads as unenclosed. A cable in a conduit, a duct or a wall cavity reads as enclosed in air. A buried run reads as enclosed in ground. Insulation around the cable reads as partly or completely surrounded. Note 3 to Table C6 gives the full mapping.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 26 Sept 2026.