简易电缆选型

查阅附录 C 中的保护装置额定值和电压降表。

Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

电缆截面
2.5 mm²
相
单相,230 V
安装条件
空气中未封闭
设计电流
20 A
路径长度
25 m
电压降限值
5 %

最大装置额定值

25A

电压降
3.91%
安培米
500
按压降限值选择规格
2.5mm²

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 装置最大额定值 In结果25A

    AS/NZS 3000:2018 Tables C6 and C7

  2. 安培米500

    AS/NZS 3000:2018 Table C8

  3. 该规格每百分比的安培米数128

    AS/NZS 3000:2018 Table C8

  4. 电压降3.91%

    AS/NZS 3000:2018 Table C8

  5. 达到限值所需的每百分比安培米数100

    AS/NZS 3000:2018 Table C8

  6. 满足电压降限值的最小规格2.5mm²

    AS/NZS 3000:2018 Table C8

关于此计算器

How this is calculated

The tool reads the simplified tables of AS/NZS 3000 Appendix C. They cover copper cable from 1 mm² to 25 mm². They give the largest device rating and the voltage drop in one pass.

  1. Maximum device rating. The tool reads the rating for your size, phases and installation condition from Tables C6 and C7.
  2. Ampere metres. It multiplies the load current by the one-way length.
  3. Ampere metres per percent. It reads the value for your size from Table C8.
  4. Voltage drop. It divides the ampere metres by that value. The result is the drop in percent.
  5. Size for the limit. It divides the ampere metres by your limit. It then picks the smallest size from Table C8 that meets the figure.
StepTable or clauseWhat it decides
Device ratingAS/NZS 3000 Tables C6 and C7The largest device for the size and condition
Drop and sizeAS/NZS 3000 Table C8The drop for the run and the size for your limit

Worked example

  • 2.5 mm² on one phase over 25 m at 20 A. The cable is in unenclosed air. The maximum device rating is 25 A. The run is 500 ampere metres. The drop is 3.91 %, inside the 5 % limit. The size for the limit is 2.5 mm².

Limits

The tables assume one circuit on its own. Where circuits are grouped, use the cable size calculator. The tool does not apply correction factors. It does not read AS/NZS 3008.1 tables. It stops at 25 mm².

See also: Cable size for a 32 A single‑phase run of 25 m, AS/NZS 3000 Clause 3.6.2 voltage drop limit and Voltage drop basics.

问题

结果仅供设计参考。请依据现行标准核对。

简易选型工具有什么作用?

工具读取 AS/NZS 3000:2018 Tables C6 和 C7,以获得 1 至 25 mm² 电缆可承载的最大保护装置。随后读取 Table C8,获得线路的电压降以及满足限值的最小截面。

何时应改用完整的电缆截面工具?

当回路成组敷设、环境温度不为 30 °C、电缆并非 PVC 双芯或四芯带接地,或截面超过 25 mm² 时,请使用电缆截面工具。Appendix C 假定单独一个回路敷设。

电压降如何计算?

将设计电流乘以线路长度,得到安培米。再除以 Table C8 中该截面每百分比的安培米数。结果即为占单相 230 V 或三相 400 V 的压降百分比。

应选择哪种安装条件?

按电缆的敷设方式对应。在空气中明敷卡固的电缆视为非封闭。穿于线管、管道或墙腔中的电缆视为封闭于空气中。埋地敷设视为封闭于土壤中。电缆周围有隔热材料时,视为部分或完全被隔热材料包围。Table C6 的注 3 给出完整对应关系。

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 26 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。