Segregation and separation checker

Check what may share an enclosure and the separation.

AS/NZS 3000

Reads AS/NZS 3000:2018 and HELUKABEL and LAPP catalogues 2024. Tables checked 27 Sept 2026.

Try a job 6

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

First circuit
Low voltage
Second circuit
Extra-low voltage
Both circuits are in the same electrical installation
Yes
Both circuits serve the same occupancy
Yes
Wiring system
Common enclosure
Arrangement for mixed voltage
None
The circuits start or end at this switchboard
No
Nearby non-electrical service
None
Data network cable on the same route
None

May share this wiring system

No

Clause
AS/NZS 3000:2018 Cl 3.9.8.3
Reason
LV and ELV cables may share a wiring system only under one of three listed arrangements.

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. CircuitsLow voltage with extra-low voltage

    AS/NZS 3000:2018 Cl 3.9.8.3

  2. Wiring systemCommon enclosure

    AS/NZS 3000:2018 Cl 3.9.8.2.1

  3. PermittedResultNo

    AS/NZS 3000:2018 Cl 3.9.8.3

  4. Arrangement in forceNone

    AS/NZS 3000:2018 Cl 3.9.8.3

About this calculator

How this is calculated

The tool checks whether two kinds of circuit may share a wiring system. It reads AS/NZS 3000:2018 Cl 3.9.8. It also gives the separation to keep from other circuits.

  1. Circuits. You pick the two circuit types, such as low voltage and extra-low voltage. The tool reads the rule for that pair from Cl 3.9.8.3.
  2. Wiring system. You pick the enclosure, such as a common enclosure or separate ones. The tool reads Cl 3.9.8.2.1 for the sharing of one system.
  3. Arrangement. You pick the arrangement in force. The tool checks it against the arrangements the clause permits.
  4. Result. The tool gives Yes or No, with the clause and the reason. It adds the separation to keep from a service or from data circuits nearby.
StepTable or clauseWhat it decides
Circuit pairAS/NZS 3000:2018 Cl 3.9.8.3Whether the pair may share
Wiring systemCl 3.9.8.2.1The enclosure the pair shares
ArrangementCl 3.9.8.3Which permitted arrangement applies

Worked example

  • Low voltage and extra-low voltage in one enclosure. The circuits sit in the same installation and occupancy, with no special arrangement. The tool answers No. They may share a wiring system only under one of three listed arrangements. The clause is Cl 3.9.8.3.

Limits

The tool reads the rules of Cl 3.9.8. It does not read the rules of a cable maker or a data standard. For telecommunications cable, check the cable own rules.

It does not size the separation by calculation. It states the rule. It does not cover induced noise or electromagnetic interference. Check the installation against the full clause before you rely on a Yes.

See also: Control panels and PLC wiring, the comms cable selector and the loop power tool.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the segregation tool do?

The tool reports whether two circuits may share a pipe, conduit, cable, enclosure or tray. It gives the clause, the arrangement needed for mixed voltage, and the minimum separation distance. It also reports the separation from gas, water and telecommunications services.

Which clause does the result come from?

AS/NZS 3000:2018 Clause 3.9.8. Clause 3.9.8.2.1 covers a common pipe or cable, Clause 3.9.8.2.2 covers segregation in a common enclosure, Clause 3.9.8.3 covers voltage levels, and Clause 3.9.8.4 covers gas, water and telecommunications services.

What is the minimum distance for segregation?

Clause 3.9.8.2.2 gives 50 mm when distance alone segregates the circuits in a common enclosure. The other two methods are cables with their own sheaths and a fire-resisting barrier. The rule does not apply at a switchboard where the circuits start or end.

Can low voltage cables share a wiring system with extra-low voltage cables?

Only under one of three Clause 3.9.8.3 arrangements. In the first, the low voltage cables give protection equal to double insulation. In the second, every cable and each core in it has insulation rated for the highest voltage in the run. In the third, fixed continuous barriers give the low voltage cables their own compartment. High voltage never shares.

Does the tool give telecommunications separation distances?

Yes, the ones Clause 3.9.8.4(c) shows in Figures 3.8 and 3.9. On a surface, or in a wall, floor or ceiling, keep 50 mm or fit a barrier. In a shared trench in New Zealand, keep 50 mm between the conduits. AS/CA S009 and the NZ TCF Premises Wiring Guidelines hold the other cases. AmpSize holds neither document.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?