Skip to content
AmpSize

RCD standing leakage budget

How much standing leakage one RCD can carry.

Reads AS/NZS 3000:2018 and AS/NZS 3760:2022. Tables checked 1 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Country
New Zealand
Rated residual current
30 mA
Protects socket-outlets
Yes
What the RCD supplies
3 rows

Standing leakage

7.3mA

Leakage on this RCD
Within the one-third budget
Budget, one-third of the rating
10mA
Share of the rated residual current
24.3%
RCDs to keep each within the budget
1

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Heat pump: 1 × 3.5 mA measured3.5mA
  2. Computers: 3 × 1 mA measured3mA
  3. Fridge: 1 × 0.8 mA measured0.8mA
  4. Standing leakageResult7.3mA
  5. Budget, one-third of the rating10mA

    AS/NZS 3000:2018 Cl 2.6.2.1 Note 1

  6. The RCD may operate above15mA

    AS/NZS 3000:2018 Cl 2.6.2.1 Note 1

  7. Share of the rated residual current24.3%
  8. Leakage on this RCDWithin the one-third budget

    AS/NZS 3000:2018 Cl 2.6.2.1 Note 1

  9. RCDs to keep each within the budget1

    AS/NZS 3000:2018 Cl 2.6.2.1

About this calculator

How this is calculated

Every item on a circuit leaks a little current to earth in normal use, through its insulation and through the filters on its supply. An RCD cannot tell that current from a fault. On one RCD the leakage of everything it supplies adds up, and enough of it trips the RCD with nothing wrong. AS/NZS 3000 asks for circuits to be split so the leakage expected in normal use is unlikely to trip the device. This tool adds up the leakage on one RCD and checks it.

You list what the RCD supplies. For each item you type a measured or maker's leakage, or you take the in-service test limit for its class from AS/NZS 3760: the most a Class I or Class II item may leak and still pass its test. The class limit is a worst case. Most items leak much less, so a measured figure gives a truer total.

The total is checked against two points of the clause's first note. The leakage should not pass one-third of the RCD's rated residual current, and an RCD may operate at any residual current above half of it. Past one-third the tool warns that unwanted trips are likely, past half that the RCD may trip, and at the rating it fails, because the RCD is made to trip there. It then places the items, largest first, on the fewest RCDs that keep each within the one-third budget, without splitting an item.

StepTable or clauseWhat it decides
Leakage of a Class I or Class II itemAS/NZS 3760 Table 2.1The worst-case leakage of an item with no measured figure
The duty to split circuitsAS/NZS 3000 Cl 2.6.2.1That normal leakage must not trip the RCD
The budget and the point it may tripAS/NZS 3000 Cl 2.6.2.1 Note 1One-third and one-half of the rated residual current
Socket-outlets on one RCDAS/NZS 3000 Cl 2.6.2.1 Note 2A reminder that plugged-in items add leakage
A 10 mA RCD in New ZealandAS/NZS 3000 Cl 2.6.3.3.2 Note 3Fewer socket-outlets on one 10 mA RCD

Worked examples

Limits

The tool adds standing leakage, the current that flows all the time. It does not model the short surges as filters charge at switch-on, leakage from a frequency drive at its switching frequency, or a fault. Type F and Type B RCDs, and where each is needed, are for the RCD selection tool.

The class limits are the most an item may leak and still pass. A measurement with a leakage clamp on the circuit gives the real figure.

See also: RCD selection, RCD arrangement and Test and tag.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

Why does an RCD trip with nothing faulty?

Every connected item leaks a little current to earth in normal use. On one RCD the leakage adds up. An RCD may operate at any residual current above half its rating, so 15 mA of normal leakage can trip a 30 mA RCD.

How much leakage can one 30 mA RCD carry?

AS/NZS 3000 Cl 2.6.2.1 Note 1 says the leakage should not pass one-third of the rated residual current: 10 mA for a 30 mA RCD. The tool adds the items and checks the total against that.

Where do the leakage figures come from?

Type a measured or maker's figure for each item. Where you have none, the tool can use the AS/NZS 3760 in-service limit for the item's class: 5 mA for Class I and 1 mA for Class II. Those are the most a passing item may leak, so they are a worst case.

How many RCDs do I need?

The tool places the items largest first on the first RCD with room under the one-third budget. An item is not split between RCDs. The count is the fewest that keep each RCD within the budget.

What items leak the most?

Items with filters on their supply, such as computers, drives, heat pumps and LED drivers, and heating elements as they age. Measure them where you can: the leakage of one model differs from another.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 1 Oct 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.