PV string calculator
Modules per string, string current and isolator for PV.
Reads AS/NZS 5033:2021 and AS/NZS 4777.2:2020. Tables checked 2 Oct 2026.
Try a job 8
Each job fills in example values. Replace them with your values.
- Size solar strings for a 600 V inverterThe modules per string for 49.5 V modules on a 600 V inverter at −5 °C.
- Check string fuses on three parallel stringsWhether three parallel strings of 13.9 A modules call for string fuses, and their rating.
- Size strings for a 1000 V inverterThe modules per string for a commercial inverter.
- Size strings for a cold inland siteThe modules per string at a record low of −8 °C, on a 600 V inverter.
- Check a string on a hot roofWhether the hot voltage stays above the tracker's minimum.
- Check two strings need no fuseWhether two strings in parallel need string fuses.
- Check the array current at the inverterThe array's short-circuit current against the inverter input.
- Size strings for a house trackerThe modules per string for a 450 V window.
Inputs
A worked example with the default inputs.
- Module Voc
- 49.5 V
- Module Vmp
- 41.5 V
- Module Isc
- 13.9 A
- Voc temperature coefficient
- −0.27 %/K
- Vmp temperature coefficient
- −0.35 %/K
- Module maximum series fuse
- 25 A
- Cold voltage correction
- Maker’s coefficient, Cl 4.2.1.2(a)
- Record low temperature
- −5 °C
- Record high temperature
- 35 °C
- Cell rise above ambient
- 35 K
- Installation
- Domestic, 1000 V limit
- Modules per string
- 10
- Strings in parallel
- 2
- KI, bifacial factor
- 1
- Backfeed current from the inverter
- 0 A
- String fuse rating
- 0 A
- Inverter maximum d.c. voltage
- 600 V
- MPPT minimum voltage
- 150 V
- MPPT maximum voltage
- 550 V
- Inverter Isc PV
- 0 A
Modules per string
5 to 11
- String maximum voltage
- 535.1V
- String Vmp at the hottest cell
- 349.6V
- Maximum string current
- 17.38A
- Array current to the inverter
- 34.75A
- d.c. isolator, at least
- 34.75 A at 535.1 V
- String fuses
- Not called for
This result is a design aid. Verify it against the current standard.
Calculation steps
- Voc correction, 1 + coefficient × (Tmin − 25 °C)×1.08
AS/NZS 5033:2021 Cl 4.2.1.2
- Module maximum voltage at the coldest cell53.51V
AS/NZS 5033:2021 Cl 4.2.1.2
- Limit for a domestic installation1,000V
AS/NZS 5033:2021 Cl 3.1
- Most modules per string11
AS/NZS 5033:2021 Cl 4.2.1.3.1
- Hottest cell, record high plus the rise70°C
- Module Vmp at the hottest cell34.96V
- Fewest modules per string for the MPPT minimum5
- String maximum voltage535.1V
AS/NZS 5033:2021 Cl 4.2.1.3.1
- String Vmp at the hottest cell349.6V
- String Vmp at the coldest cell458.6V
- Maximum string current, 1.25 × KI × Isc17.38A
AS/NZS 5033:2021 Cl 3.3.3.1
- Fault current from the other strings, (SA − 1) × ISTRING MAX17.38A
AS/NZS 5033:2021 Cl 3.3.3.2
- String fuse window, above 1.2 × ISTRING MAX and at most the module rating20.85 to 25A
AS/NZS 5033:2021 Table 3.1
- String cable current17.38A
AS/NZS 5033:2021 Table 4.2
- Array cable current to the inverter34.75A
AS/NZS 5033:2021 Table 4.2
- d.c. isolator current rating, at least34.75A
AS/NZS 5033:2021 Table 4.3
- d.c. isolator voltage rating, at least535.1V
AS/NZS 5033:2021 Table 4.3
- Smallest conductor4mm²
AS/NZS 5033:2021 Cl 4.4.2.3
- Cable temperature near the modules, record high plus 40 K75°C
AS/NZS 5033:2021 Cl 4.4.2.2
About this calculator
How this is calculated
The tool sizes a PV string. It finds how many modules fit in a string, the string current, the fuses and the d.c. isolator. It reads AS/NZS 5033:2021. It reads the inverter limits from the plate you enter.
- Cold voltage. The tool corrects the module Voc for the coldest cell (Cl 4.2.1.2). The factor is 1 + coefficient × (Tmin − 25 °C). Tmin is the record low.
- Most modules. It divides the voltage limit by the corrected Voc. The limit is the lower of the inverter maximum and the domestic limit in Cl 3.1 (Cl 4.2.1.3.1).
- Fewest modules. It finds the hot cell as the record high plus the cell rise you enter. It then finds the fewest modules that keep Vmp above the MPPT minimum.
- String current. It works 1.25 × KI × Isc (Cl 3.3.3.1). It adds the fault current from the other strings (Cl 3.3.3.2).
- Fuses. A fuse window sits above 1.2 times the string current and at most the module rating (Table 3.1).
- Cable and isolator. It gives the cable currents (Table 4.2), the isolator ratings (Table 4.3) and the smallest conductor (Cl 4.4.2.3).
| Step | Table or clause | What it decides |
|---|---|---|
| Cold voltage | Cl 4.2.1.2 | The module voltage at the coldest cell |
| String length | Cl 4.2.1.3.1 | The most modules in a string |
| String current | Cl 3.3.3.1 and Cl 3.3.3.2 | The current for cable and fuse |
| Fuse window | Table 3.1 | The fuse range |
| Isolator | Table 4.3 | The current and voltage ratings |
Worked example
- 10 modules of 49.5 V Voc, 2 strings, 600 V inverter. The tool gives 5 to 11 modules per string. The string maximum voltage is 535.1 V. The string current is 17.38 A and the array current is 34.75 A. No string fuses are called for.
Limits
- The tool derives the AS/NZS 5033 figures from the text until the Standard is checked. It says so in a warning.
- AS/NZS 5033 sets no cell rise. The tool uses the rise you enter.
- The inverter limits are the ones on its plate. Read them from the data sheet.
- The tool does not size the cable. Use the DC cable size calculator at these currents and at the hot cable temperature.
- Above 120 V, hold the voltage drop from the furthest module to the inverter to 5 % of Vmp.
See also: PV string voltage and temperature, Solar string sizing for a 600 V inverter and PV and inverter basics.
Questions
The result is a design aid. Verify against the current standard.
How does the tool find the most modules per string?
It corrects the module Voc to the record low temperature, by the maker’s coefficient or by AS/NZS 5033 Table 4.1. It divides the lower of the inverter maximum and the 1000 V or 1500 V limit by that voltage, and rounds down.
How does the tool find the fewest modules per string?
It works the module Vmp at the hottest cell: the record high plus the cell rise you enter. It divides the MPPT minimum by that voltage and rounds up. AS/NZS 5033 sets no cell rise, so the 35 K default is AmpSize’s assumption.
When does a string take a fuse?
Where strings run in parallel, the others can feed a fault in one string. The tool adds that current to the backfeed and compares it with the module’s maximum series fuse. Where it is higher, the fuse sits above 1.2 times the maximum string current and at or under the module rating.
Are the AS/NZS 5033 figures verified?
Yes. Table 4.1 and the voltage, current and cable limits were read against the printed pages of AS/NZS 5033:2021. Check each figure against the current standard before you rely on it.
Worked examples
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
Background
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
Clauses and tables this tool reads
- AS/NZS 5033:2021 Cl 3.1Maximum voltage of PV d.c. circuits
- AS/NZS 5033:2021 Cl 3.3.3.1Maximum string current
- AS/NZS 5033:2021 Cl 3.3.3.2Fault current from parallel strings
- AS/NZS 5033:2021 Cl 3.3.4.1When strings take overcurrent protection
- AS/NZS 5033:2021 Cl 4.2.1.2PV module maximum voltage
- AS/NZS 5033:2021 Cl 4.2.1.3.1String voltage limit
- AS/NZS 5033:2021 Cl 4.4.2.2PV cable temperature
- AS/NZS 5033:2021 Cl 4.4.2.3Smallest PV conductor
Every clause and table, with how each was verified
Tables last checked on 2 Oct 2026.
Related tools
- DC cable size calculatorSize a d.c. cable up to 1500 V for current and voltage drop.AS/NZS 3008.1.1
- PV isolator and earthing calculatorRate the PV array cables, d.c. isolator and earthing.AS/NZS 5033AS/NZS 3000
- Power factor correction calculatorFind the capacitor kvar to lift a power factor.AS/NZS 3000
Was this useful?
A question, or a value that looks wrong? Contact us.