Outbuilding earthing

Earth a shed: earth with the submain, or its own MEN.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Country
New Zealand
Outbuilding
Individual: one structure with its own board
Earthing arrangement
Earth run with the submain
Submain phases
Single phase
Submain active size
6 mm²
Conductor
Copper
Metal services between the buildings
No

Protective earthing conductor

2.5mm²

Allowed for this outbuilding
Earth with the submain, or a separate MEN

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. OutbuildingIndividual

    AS/NZS 3000:2018 Cl 1.4.88

  2. Earthing arrangementEarth run with the submain

    AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)

  3. Allowed hereYes

    AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)

  4. Protective earthing conductorResult2.5mm²

    AS/NZS 3000:2018 Table 5.1

About this calculator

How this is calculated

A shed, garage, sleep-out or workshop with its own board, fed by a submain, is an outbuilding. AS/NZS 3000 gives it two ways to be earthed. The tool asks which outbuilding it is and which way you plan, then checks the plan and gives the sizes.

An individual outbuilding is one structure, separated by land from the building whose board supplies it. It may take a protective earthing conductor run with the submain, connected at the main switchboard. Or it may be a separate MEN installation: the submain neutral becomes a PEN, the outbuilding board has its own MEN link, and an electrode is driven at the outbuilding. Combined outbuildings share a foundation, a metal roof or a metal frame. They take the earth with the submain only, so a separate MEN for them fails.

The sizes come from the same table as the earthing tool. With an earth in the submain, it is the protective earthing conductor for the submain's active size. With a separate MEN, the lead from the outbuilding board to its electrode is a main earthing conductor, sized from the submain. The PEN must be at least the neutral the submain needs and at least that earthing conductor, so the tool gives the larger. The electrode is one of the types the electrode table accepts, driven to the depth or laid to the length and cover for your country.

StepTable or clauseWhat it decides
Individual or combinedCl 1.4.88 and Cl 1.4.89Which arrangements the outbuilding may take
Earth with the submainCl 5.5.3.1(a)(i) and Cl 5.5.2.1Where the earth connects
Separate MENCl 5.5.3.1(a)(ii) and (c)The MEN link, the board and the main earthing conductor
Combined outbuildingCl 5.5.3.1(b)No separate MEN
Earthing conductor sizesTable 5.1The protective and main earthing conductors
PEN sizeCl 3.5.2(c)The least PEN of the submain
ElectrodeTable 5.2 and Cl 5.3.6.3The electrode, and its depth, length and cover

Worked examples

Limits

The tool does not size the submain itself; use the cable size or total voltage drop tools for that. It does not check the earth fault-loop impedance at the outbuilding, which the loop impedance tool does. It does not decide whether a structure is an outbuilding: that is the definition and your site. Bonding of water pipes and other services follows the earthing tool.

See also: Earthing an outbuilding: earth or its own MEN, Shed earthing on a 16 mm² submain and Earthing and bonding.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

Does a shed need its own earth stake?

Not always. AS/NZS 3000 Cl 5.5.3.1 lets an individual outbuilding take an earth run with the submain, with no electrode. It may instead be a separate MEN installation, and then it needs its own electrode and MEN link.

What is the difference between an individual and a combined outbuilding?

An individual outbuilding is one structure with its own board, separated by land from the building that supplies it. Combined outbuildings share a foundation, a metal roof or a metal frame. Combined outbuildings take an earth with the submain only.

What size is the PEN to a separate MEN shed?

At least the neutral the submain needs, which is the active size for a single-phase submain, and at least the earthing conductor from Table 5.1. The tool gives the larger.

How deep does the earth electrode go?

A driven rod goes at least 1.8 m in New Zealand and 1.2 m in Australia. A strip in a trench has at least 0.5 m cover and is at least 7.5 m long in New Zealand or 3 m in Australia.

Why do metal pipes between the buildings matter?

With a separate MEN, the submain neutral is also the earth. A metal water pipe or walkway between the buildings can carry part of the neutral current in parallel. The tool warns, and an earth with the submain avoids it.

Clauses and tables this tool reads