AmpSize

Imperial cable size converter

Find the device rating for an old imperial cable.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Imperial cable size
7/.029
Installation method
Unenclosed
Insulation
V75

Maximum circuit-breaker rating

32A

Existing fuse or plug-in circuit-breaker
20A
Calculated area
2.98mm²
Nearest metric size
2.5mm²

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Wires in the conductor7
  2. Wire diameter, inches0.03
  3. Calculated conductor area2.98mm²
  4. Nearest metric size2.5mm²
  5. Maximum circuit-breaker rating32AAS/NZS 3000:2018 Table I1
  6. Maximum existing rewireable fuse or plug-in circuit-breaker rating20AAS/NZS 3000:2018 Table I1

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the imperial cable tool do?

The tool reads AS/NZS 3000:2018 Table I1. Pick the imperial size, the insulation and the installation method. AmpSize then reports the largest circuit-breaker the table prints for that conductor. It also reports the largest existing fuse or existing plug-in circuit-breaker. Appendix I gives the scope.

Can I fit a rewireable fuse to an old circuit?

No. AmpSize treats the second column of Table I1 as an existing device only. Clause 2.5.2 governs that point, and Note 2 under the table points at it. Use that rating where a rewireable fuse or a plug-in circuit-breaker is already in place on an alteration or a repair.

How is the metric equivalent worked out?

AmpSize calculates the conductor area from the wire count and the wire diameter, then reports the nearest standard metric size. That area is arithmetic, not a value read from the standard. AmpSize does not encode Table I2, the table for cables connected in parallel. Read it in the standard for that case.

Do the Table I1 ratings apply to every installation?

No. Note 1 under Table I1 sets the conditions the ratings hold under. Read it on the page. Then check the route, the grouping and the voltage drop before you rely on a value.

Worked examples

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 26 Sept 2026.