Skip to content
AmpSize

Stationary battery by duty cycle

Size a stationary battery and charger to a duty cycle.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Nominal battery voltage
110 V
Cells in series
55
Lowest voltage the loads accept
96 V
Periods, one after another
3 rows
Rate factor
1
Temperature factor
1
Design margin
1.1
Ageing factor
1.25
Load on the charger while recharging
10 A
Recharge time
12 h
Recharge factor
1.1

Capacity by Ah

112.1Ah

Ampere-hours of the duty
81.5Ah
Charger current
17.5A
End voltage per cell
1.75V
Highest current in the duty
70A
Energy at the nominal voltage
12.33kWh

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Period 1: 70 A for 1 min1.17Ah
  2. Period 2: 10 A for 478 min79.67Ah
  3. Period 3: 40 A for 1 min0.67Ah
  4. Ampere-hours of the duty81.5Ah
  5. Duty length480 min
  6. Rate factor, from the maker's table1x
  7. Temperature factor1x
  8. Design margin1.1x
  9. Ageing factor1.25x
  10. Capacity by AhResult112.1Ah
  11. End voltage per cell

    96 V ÷ 55 cells = 1.745 V

  12. Charger current17.5A
  13. Energy at the nominal voltage12.33kWh

About this calculator

How this is calculated

A stationary battery carries a site's d.c. loads when the charger loses its supply: protection relays, breaker trip and close coils, emergency lights, radios, controls. Those loads change through the outage. The duty cycle lists them in order, as a current for a number of minutes.

The tool adds the ampere-hours of each period: the current times the minutes over sixty. That is the charge the duty takes out of the battery.

A battery gives less than its rated capacity when it discharges faster than its rated hours, or to a higher end voltage. So the tool multiplies the duty by a rate factor you read from the maker's table. It then applies a temperature factor for a cold battery room, a design margin for growth and unknowns, and an ageing factor so the battery still does the duty near the end of its life. The product is the capacity by ampere-hours. When a later period draws more than the one before it, that sum is too small, and the tool warns.

The end voltage per cell is the lowest voltage your loads accept, at the battery terminals, over the number of cells in series. Read the maker's capacity at that end voltage.

The charger must carry the standing load and put back what the duty took, with a margin for charge losses, in the recharge time you set. The tool adds the continuous load to the duty's ampere-hours times the recharge factor over the hours.

AmpSize does not hold IEEE 485 or any cell's capacity factors. With the maker's Kt on every period, the tool works the last section, each change in current times its Kt, and that figure governs. Every factor is an assumption you set, and the result says so.

StepTable or clauseWhat it decides
DutyΣ I × t ÷ sixtyThe ampere-hours the periods take out
CapacityDuty × rate × temperature × margin × ageingThe battery capacity by ampere-hours
SectionsΣ ΔI × Kt × temperature × margin × ageingThe capacity with the maker's Kt, which governs
End voltageLowest voltage ÷ cellsThe end voltage per cell to read the maker's table at
ChargerContinuous load + duty × recharge factor ÷ hoursThe charger current

Worked examples

Limits

Without Kt values, the tool adds ampere-hours. A battery's capacity falls at high rates, so a heavy load of a minute or two can need far more than its ampere-hours show. The rate factor carries that, and only the maker's table gives it.

It does not pick a cell, a chemistry or a float voltage, and it does not check ventilation or the battery room. Follow the maker's data for those.

See also: Battery, Fire alarm battery and DC cable size.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

How do you size a battery for a duty cycle?

List what the battery must carry, period by period: the current and the minutes. Add the ampere-hours. Multiply by a rate factor from the maker’s table, a temperature factor, a design margin and an ageing factor. When a later period draws more than the one before it, the sum is too small: use the maker’s Kt and the section method.

Why does a short heavy load need more than its ampere-hours?

A battery gives fewer ampere-hours at a high rate than at its rated rate. A one-minute trip load can need far more capacity than its share of the duty. The rate factor from the maker’s table at your end voltage allows for it.

What end voltage per cell should I use?

Divide the lowest voltage your loads accept, at the battery, by the number of cells. Read the maker’s capacity at that end voltage. A higher end voltage gives less capacity from the same cell.

How big should the charger be?

The charger carries the standing load and puts back the ampere-hours taken out, plus a little more, in the recharge time. The tool adds the continuous load to the duty’s ampere-hours times the recharge factor over the hours.

Does the tool follow IEEE 485?

AmpSize does not hold IEEE 485 or any cell’s Kt values. Enter the maker’s Kt on every period and the tool works the last section of the method. Without them, it adds ampere-hours, applies your factors and warns when a later period draws more.

Was this useful?

A question, or a value that looks wrong? Contact us.