Table 7

Enclosure size correction factor coefficients

The arc flash tool reads the enclosure size correction for VCB, VCBB and HCB. VOA and HOA take no correction.

Verified: read against the printed standard, pages 28-30 (PDF 29-31). Checked 1 Oct 2026.

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the IEEE 1584-2018 page

3 rows

Table 7, Enclosure size correction factor coefficients
ConfigABTypicalShallow
VCB420-0.000302, 0.03441, 0.43250.002222, -0.02556, 0.6222
VCBB1024-0.000298, 0.032, 0.479-0.002778, 0.1194, -0.2778
HCB1022-0.000192, 0.01935, 0.6899-0.000556, 0.03722, 0.4778