AS/NZS 3002:2021
Section 2 and Section 3
Shows, carnivals and events, supply, RCD, wiring and enclosure figures
The show and carnival tool reads the RCD figures and exceptions for installation wiring and for event wiring. It also reads the underground peg trigger and depth, and the aerial height, for installation wiring. It reads two of the three IP ratings: the HRC fuse base and the connection facility enclosure. AmpSize leaves out the aerial span table of Cl 2.7.5.4.3.
Verified: read against the printed standard, pages 10, 11, 12, 13, 15, 16, 17, 19, 20, 21 (PDF = page + 8). Checked 1 Oct 2026.
Units: Max rated ma mA, Max final subcircuit A A, Min depth M m, Min height M m, Peg trigger mm mm, Concrete max above mm mm, Concrete min thickness mm mm, Concrete min width mm mm, Concrete min overlap each side mm mm
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
23 rows
| Kind | Method | Clause | Page | Jurisdiction | Max rated ma (mA) | Max final subcircuit A | Applies to | All live conductors | Number | Peg trigger mm | Min depth M (m) | Concrete max above mm | Concrete min thickness mm | Concrete min width mm | Concrete min overlap each side mm | Min height M (m) | Ip |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| supply | normal | 2.2.2 | 10 | ||||||||||||||
| supply | alternative | 2.2.3 | 11 | ||||||||||||||
| supply | standalone | 2.2.4 | 11 | ||||||||||||||
| supply | supplementary | 2.2.5 | 11 | ||||||||||||||
| supply | connection-facility | 3.2.1 | 20 | ||||||||||||||
| supply | generating-system | 3.2.2 | 21 | ||||||||||||||
| rcd | 2.5.1 | 12 | nz | 30 | 32 | socket-outlets, lighting, raised-risk-equipment | yes | ||||||||||
| rcd | 2.5.1 | 12 | au | 30 | 32 | socket-outlets, lighting, raised-risk-equipment | yes | ||||||||||
| rcd | 3.2.1.2 | 20 | nz | 30 | — | — | yes | ||||||||||
| rcd | 3.2.1.2 | 20 | au | 30 | — | — | yes | ||||||||||
| exception | 2.5.1 | 12 | nz | 1 | |||||||||||||
| exception | 2.5.1 | 12 | nz | 2 | |||||||||||||
| exception | 2.5.1 | 12 | nz | 3 | |||||||||||||
| exception | 2.5.1 | 13 | nz | 4 | |||||||||||||
| exception | 3.2.1.2 | 20 | au | 1 | |||||||||||||
| exception | 3.2.1.2 | 20 | au | 2 | |||||||||||||
| exception | 3.2.1.2 | 21 | nz | 1 | |||||||||||||
| exception | 3.2.1.2 | 21 | nz | 2 | |||||||||||||
| underground | 2.7.4 | 15 | 400 | 1 | 75 | 100 | 150 | 40 | |||||||||
| aerial | 2.7.5.4.1 | 16 | 6 | ||||||||||||||
| ip | 2.4.2.1 | 11 | IP2X | ||||||||||||||
| ip | 2.7.3.2 | 15 | IP23 | ||||||||||||||
| ip | 2.7.6.2 | 19 | IP23 |