AS/NZS 3002:2021

Section 2 and Section 3

Shows, carnivals and events, supply, RCD, wiring and enclosure figures

The show and carnival tool reads the RCD figures and exceptions for installation wiring and for event wiring. It also reads the underground peg trigger and depth, and the aerial height, for installation wiring. It reads two of the three IP ratings: the HRC fuse base and the connection facility enclosure. AmpSize leaves out the aerial span table of Cl 2.7.5.4.3.

Verified: read against the printed standard, pages 10, 11, 12, 13, 15, 16, 17, 19, 20, 21 (PDF = page + 8). Checked 1 Oct 2026.

Units: Max rated ma mA, Max final subcircuit A A, Min depth M m, Min height M m, Peg trigger mm mm, Concrete max above mm mm, Concrete min thickness mm mm, Concrete min width mm mm, Concrete min overlap each side mm mm

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3002:2021 page

23 rows

Section 2 and Section 3, Shows, carnivals and events, supply, RCD, wiring and enclosure figures
KindMethodClausePageJurisdictionMax rated ma (mA)Max final subcircuit AApplies toAll live conductorsNumberPeg trigger mmMin depth M (m)Concrete max above mmConcrete min thickness mmConcrete min width mmConcrete min overlap each side mmMin height M (m)Ip
supplynormal2.2.210
supplyalternative2.2.311
supplystandalone2.2.411
supplysupplementary2.2.511
supplyconnection-facility3.2.120
supplygenerating-system3.2.221
rcd2.5.112nz3032socket-outlets, lighting, raised-risk-equipmentyes
rcd2.5.112au3032socket-outlets, lighting, raised-risk-equipmentyes
rcd3.2.1.220nz30——yes
rcd3.2.1.220au30——yes
exception2.5.112nz1
exception2.5.112nz2
exception2.5.112nz3
exception2.5.113nz4
exception3.2.1.220au1
exception3.2.1.220au2
exception3.2.1.221nz1
exception3.2.1.221nz2
underground2.7.41540017510015040
aerial2.7.5.4.1166
ip2.4.2.111IP2X
ip2.7.3.215IP23
ip2.7.6.219IP23

Tools that read it (1)