AS/NZS 3000:2018

Table C9

Loading of points per final subcircuit

The circuit loading tool reads from Table C9 the current each point counts for, by circuit-breaker rating. Points are socket‑outlets, lighting and fixed loads on a final subcircuit. The same rows give the cable sizes the table pairs with each rating, and the largest range each pair allows.

Verified: read against the printed standard, pages 483–485. Checked 27 Sept 2026.

Units: Rating A A, Lighting A A, Socket 10 non domestic A A, Socket 10 domestic A A, Socket 15 A A, Socket 20 A A, Cable mm², Range max W W, Socket min cable mm 2 mm²

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

9 rows

Table C9, Loading of points per final subcircuit
Rating ALighting ASocket 10 non domestic ASocket 10 domestic ASocket 15 ASocket 20 APairs cable (mm²)Pairs range max W
60.5————1—
80.5————1—
81.5—
100.5————1—
101.5—
102.5—
130.521——1—
131.5—
132.5—
160.52115—1—
161.55000
162.55000
1645000
200.52112201.55000
202.58000
2048000
20610000
250.52110182.58000
25410000
25610000
320.5218162.510000
32410000
32613000
321013000
400.52181610>13000