Skip to content
AmpSize

AS/NZS 3000:2018

Table 3.6

Underground wiring systems minimum depth of cover

The underground cable tool reads the minimum depth of cover for the category and the location.

Verified: read against the printed standard, pages 197. Checked 26 Sept 2026.

Units: Cat A mm, Cat B mm, Cat C mm

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

4 rows

Table 3.6, Underground wiring systems minimum depth of cover
LocationCoveringCat A (mm)Cat B (mm)Cat C (mm)
within-buildingconcrete-75000
within-buildingnone50050050
elsewhereconcrete-7530030050
elsewherenone50050050

Tools that read it (1)

Guides and learn pages that cite it (1)