AS/NZS 3000:2018
Cl 2.6.2.1
Standing leakage on an RCD
The RCD leakage budget tool reads the one-third budget and the 50 % point of Cl 2.6.2.1 Note 1, and the socket‑outlet notes for 30 mA and NZ 10 mA RCDs.
Verified: read against the printed standard, pages 120, 123–130 (PDF = page + 4). Checked 1 Oct 2026.
Units: Value fraction of the rated residual current
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
7 rows
| Kind | Value (fraction of the rated residual current) | Clause | Page |
|---|---|---|---|
| shall | — | 2.6.2.1 | 120 |
| should | — | 2.6.2.1 Note 1 | 120 |
| fraction | 0.333333 | 2.6.2.1 Note 1 | 120 |
| fraction | 0.5 | 2.6.2.1 Note 1 | 120 |
| should | 30 | 2.6.2.1 Note 2 | 120 |
| should | 10 | 2.6.3.3.2 Note 3 | 130 |
| should | — | 2.6.3.2.3.3 Exception 3(ii) | 125 |