Skip to content
AmpSize

Transformer size from the demand

Size a transformer from the demand, with growth and losses.

Try a job 4

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Maximum demand
220
Demand in
kVA
Power factor
0.9
Growth allowance
20 %
Most loading at the design load
100 %
Phases
Three phase
Primary voltage
11,000 V
Secondary voltage
400 V
Impedance
4.5 %
X/R ratio
4
No-load loss, of the rating
0.2 %
Load loss at full load, of the rating
1.1 %

Transformer size

300kVA

Design load with growth
264kVA
Loading today
73.3%
Loading with growth
88%
Voltage regulation with growth
2.59%
Losses with growth
3.16kW
Secondary full load current
433.01A
Secondary fault current
9,622.5A

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Design load with 20 % growth264kVA
  2. Smallest typical size at 100 % loading300 kVA
  3. Loading today73.3%
  4. Loading with growth88%
  5. Resistance, of the rating1.09%
  6. Reactance, of the rating4.37%
  7. Voltage regulation with growth2.59%
  8. Secondary voltage at the design load389.7V
  9. Losses with growth3.16kW
  10. Efficiency with growth98.69%
  11. Secondary full load current433.01A
  12. Secondary fault current9,622.5A

About this calculator

How this is calculated

A transformer is sized from the maximum demand it will carry, with room for the load to grow. Too small and it runs hot and drops too much voltage; too large and it costs more and wastes energy in its core every hour of the year. This tool finds the size and shows what it does at the load.

You enter the maximum demand, in kVA or in kW with a power factor, and a growth allowance. The design load is the demand plus that growth. The tool picks the smallest rating from a list of typical sizes that carries the design load within the loading limit you set. The list is common distribution and site ratings, not a standard's list.

At that size it works the loading today and with growth, then the voltage regulation: the drop through the transformer's own resistance and reactance at the design load and power factor. The impedance on the rating plate splits into the two by the X/R ratio. The losses are the core loss, which is there whenever the transformer is energised, plus the winding loss, which rises with the square of the loading. The full load and fault currents at the size come from the transformer tool.

The impedance, X/R ratio and losses are maker's data. The defaults are typical figures, and the result names them as assumptions.

StepTable or clauseWhat it decides
Design loadDemand plus the growth allowanceThe load the size must carry
SizeSmallest typical rating within the loading limitThe transformer rating
Resistance and reactanceImpedance split by the X/R ratioThe two parts of the drop
Voltage regulationLoading times the drop at the power factorThe voltage lost through the transformer
LossesCore loss plus winding loss times loading squaredThe heat and the running cost
CurrentsThe transformer toolThe full load and fault current at the size

Worked examples

Limits

The regulation is the drop through the transformer alone. The network upstream and the cables downstream add their own drop; the total voltage drop tool adds the cable parts. A tap changer or off-load taps can raise the secondary voltage to make up for it.

The tool does not cover transformers in parallel, harmonic loads, the temperature rise of the windings or the network company's own sizing rules for a supply transformer.

See also: Transformer, Maximum demand and Fault level at a board.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

How do I size a transformer?

Start from the maximum demand, add an allowance for growth, and pick the smallest standard rating that carries the result. Then check the voltage the transformer drops at that load and what it loses as heat.

How much growth should I allow for?

It depends on the site. 20 to 30 % is common where more load is likely. A transformer lasts decades, and changing it later costs more than one size up now.

What is transformer voltage regulation?

The drop in secondary voltage from no load to the load, as a percent. It comes from the transformer's resistance and reactance, and it is larger at a low power factor.

Why not just pick a much bigger transformer?

A larger unit costs more and its core loss runs all day, every day, even at light load. Sized close to the load, a transformer runs where its losses are lowest for the energy it delivers.

Where do the impedance and losses come from?

The impedance is on the rating plate. The losses and the X/R ratio are in the maker's test report. The tool's defaults are typical figures until you have the real ones.

Was this useful?

A question, or a value that looks wrong? Contact us.