Domestic 份指南
选定分支干线截面,核对长线路的电压降,并计算住宅的最大需量。
- 阅读约 5 分钟Builder's pole: supply, RCDs and cord lengthsA builder's pole for a house build, worked to AS/NZS 3012:2019. The supply it may take, the 30 mA RCDs, the Table 1 cord lengths and the test intervals.

- 阅读约 4 分钟Car-park floodlight: obtrusive light at a boundaryTwo 10 000 lm floodlights 10 m from a neighbour's window in zone A2, checked against AS/NZS 4282 for lux at the window, candela and the upward light ratio.

- 阅读约 3 分钟Homeowner shed supply voltage drop over 60 mA 20 A single-phase supply running 60 m to a shed on 6 mm² copper, with the drop, the percentage and the maximum length the AmpSize voltage drop engine returns.

- 阅读约 5 分钟Arc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.

- 阅读约 5 分钟Ohm's law on a 3 kW water heater elementWork the current and working resistance of a 3 kW, 230 V water heater element with Ohm's law, why a cold meter reading is lower, then a 9 kW three-phase bank.

- 阅读约 3 分钟Lighting circuit loop impedance, B curve 10 AA 60 m shop lighting circuit on 1.5 mm² cable with a B curve 10 A device, showing Zs, the maximum Zs, the fault current and the longest run that passes.

- 阅读约 5 分钟RCD tripping with no fault: add up the leakageAn RCD on a home office and kitchen trips with no fault found. Add up the standing leakage, check it against a third of 30 mA, and split it over two RCDs.

- 阅读约 3 分钟Voltage drop single phase vs three phaseThe same 6 mm² cable at 32 A over 50 m, worked on a three phase supply and on a single phase supply, with both drops, both percents and both run limits.

- 阅读约 5 分钟What size generator for a dairy shedSize a standby set for a dairy shed from its load list. The vacuum pump's start sets the size, then staggered steps, a drive and a soft starter shrink it.

- 阅读约 3 分钟Fixed heating maximum demand with Table C1Adding 7.5 kW of fixed heating to a house under Table C1 group D, the demand each group contributes, and the 80 A line that reg 59 draws.

- 阅读约 2 分钟A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.

- 阅读约 3 分钟A test sheet for a house boardA test sheet for a six-circuit New Zealand house board, with the tests in the AS/NZS 3017 order and the limit for each reading, then the Australian sheet.

- 阅读约 3 分钟Hot water cylinder cable size for a 3 kW elementA 16 A hot water circuit run 20 metres through wall insulation at 35 degrees, sized to 2.5 mm² with 17.86 A of derated capacity and 2.27 percent voltage drop.

- 阅读约 2 分钟IP ratings for an outdoor point and a hosed shedWhich IP code an outdoor power point, a milking shed light and a hosed switchboard need, and why an IP67 light can fail where IP65 passes.

- 阅读约 3 分钟Reading the wiring in an older houseA 1970s New Zealand house with yellow actives, a green earth and a black neutral. What each colour can be, what may stay, and how to sleeve new terminations.

- 阅读约 4 分钟Consumer mains fault withstand for 16 mm² copperA domestic 6 kA fault cleared in 10 milliseconds against 16 mm² copper PVC mains, giving a 5.41 mm² minimum size and a 17.76 kA adiabatic withstand.

- 阅读约 3 分钟Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at -5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.

- 阅读约 1 分钟How far can 1.5 mm² run on a 10 A circuit?1.5 mm² copper on a 10 A curve C circuit can run 34.85 m before it reaches the 5 % voltage drop limit. The fault loop alone would allow 82 m.

- 阅读约 1 分钟How far can 4 mm² run on a 25 A circuit?4 mm² copper on a 25 A curve C circuit can run 41 m at full load before it reaches the 5 % voltage drop limit. At 20 A of load it can run 51.25 m.

- 阅读约 1 分钟How many amps can 1.5 mm² cable carry?1.5 mm² copper multicore PVC cable carries 16 A enclosed in air at 30 °C in NZ, so it takes a 16 A breaker. Clipped direct, it carries 17 A.

- 阅读约 1 分钟How many amps can 10 mm² cable carry?10 mm² copper multicore PVC cable carries 50 A enclosed in air at 30 °C in NZ, so a 50 A breaker protects it. Clipped direct, it carries 58 A.

- 阅读约 1 分钟How many amps can 16 mm² cable carry?16 mm² copper multicore PVC cable carries 66 A enclosed in air at 30 °C in NZ, so it takes a 63 A breaker. Grouped with two circuits, it carries 46.2 A.

- 阅读约 1 分钟How many amps can 2.5 mm² cable carry?2.5 mm² copper multicore PVC cable carries 23 A enclosed in air at 30 °C in NZ, so a 20 A breaker protects it. Grouped with two circuits, it carries 16.1 A.

- 阅读约 1 分钟How many amps can 2.5 mm² carry in Australia?2.5 mm² copper multicore PVC cable carries 20 A enclosed in air at 40 °C on AS/NZS 3008.1.1:2025, exactly a 20 A breaker. Clipped direct, it carries 22 A.

- 阅读约 1 分钟How many amps can 6 mm² cable carry?6 mm² copper multicore PVC cable carries 38 A enclosed in air at 30 °C in NZ, so it takes a 32 A breaker. At 40 °C it carries 33.44 A.

- 阅读约 1 分钟How many 2.5 mm² cables fit in 20 mm conduit?Six single-core 2.5 mm² cables fit in 20 mm conduit at 34.56 % fill, inside the 40 % limit of AS/NZS 3000 Appendix C. A seventh takes it to 40.32 %.

- 阅读约 1 分钟How many lights on a 10 A circuit?In a home, AS/NZS 3000 Table C9 fills a 10 A circuit at 20 lighting points. A 21st point takes the sum over the circuit-breaker rating.

- 阅读约 1 分钟How many power points on a 20 A circuit?In a home, AS/NZS 3000 Table C9 fills a 20 A circuit at 20 single 10 A socket-outlets. A non-domestic installation counts each one at twice that.

- 阅读约 1 分钟Maximum Zs for a 16 A curve C breakerAS/NZS 3000 Table 8.1 allows a maximum Zs of 1.92 Ω for a 16 A curve C breaker at 230 V. A 30 m run of 2.5 mm² cable reads 0.89 Ω.

- 阅读约 1 分钟Minimum cable size for a lighting circuitAS/NZS 3000 Table 3.3 sets a minimum of 1 mm² copper for circuits other than socket-outlets, lighting included. The load and the run often need more.

- 阅读约 1 分钟Minimum cable size for power pointsAS/NZS 3000 Table 3.3 sets a minimum of 2.5 mm² copper for a socket-outlet circuit. An exception can allow less, under conditions you must meet first.

- 阅读约 1 分钟Voltage drop on 2.5 mm² over 30 m20 A on 2.5 mm² copper over 30 m drops 10.81 V, which is 4.7 % at 230 V and close to the 5 % limit. The run can reach 31.91 m.

- 阅读约 1 分钟What size cable for a 22 kW EV charger?A 22 kW three-phase EV charger on a 32 A circuit takes 6 mm² copper over 20 m, with 38 A of derated capacity and a 1.04 % drop. At 60 m it takes 10 mm².

- 阅读约 1 分钟What size cable for a 25 A circuit?A 25 A single-phase circuit takes 4 mm² copper on a typical NZ route, with 29 A of derated capacity. 2.5 mm² stops at 23 A, short of the breaker.

- 阅读约 1 分钟What size cable for a lighting circuit in NZ?A 10 A lighting circuit in New Zealand takes 1.5 mm² copper over 30 m, with 16 A of derated capacity and a 4.3 % drop. A 16 A circuit takes 2.5 mm².

- 阅读约 1 分钟What size cable for power points in Australia?A 20 A power point circuit in Australia takes 2.5 mm² copper on AS/NZS 3008.1.1:2025, rated 20 A enclosed in air at 40 °C. Grouping pushes it to 6 mm².

- 阅读约 1 分钟What size cable for power points in NZ?A 20 A power point circuit in New Zealand takes 2.5 mm² copper enclosed in air, with 23 A of derated capacity. Ceiling insulation moves it to 4 mm².

- 阅读约 3 分钟Where can a home battery go? Garage wallsA garage wall that backs onto a bedroom, with a hot water cylinder nearby. See which AS/NZS 5139 location rules fail for a home battery, then fix each one.

- 阅读约 5 分钟Kitchen power points and the cooktop zonePlace power points and switches near a cooktop, an outdoor gas bottle and a gas vent. Check each distance to AS/NZS 3000 and hand the sink to the wet area tool.

- 阅读约 3 分钟Max cable length for a 20 A C curve subcircuitA 20 A curve C socket circuit on 2.5 mm² runs 40 m. See the Zs the engine returns, the Table 8.1 limit and the maximum length before the circuit fails.

- 阅读约 4 分钟Downlights in an insulated ceilingRe-insulate a NZ ceiling with downlights in it. Check which may be covered, which only abutted, which must come out, and the clearances and roof space sign.

- 阅读约 5 分钟12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.

- 阅读约 3 分钟Shed earthing on a 16 mm² submainEarth a NZ shed 30 m from the house on a 16 mm² submain. Compare an earth with the submain and a separate MEN with its own rod, and when each is allowed.

- 阅读约 4 分钟Solar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.

- 阅读约 5 分钟Three circuits in a hot ceiling: correction factorThree 32 A circuits in conduit across a 40 °C and a 50 °C ceiling space, worked with the NZ 2017 tables and again with AS/NZS 3008.1.1:2025.

- 阅读约 5 分钟What size breaker for 4 mm² cable4 mm² copper enclosed in air takes a 25 A breaker, and 32 A fails at an Iz of 29 A. Grouping, a hot ceiling, insulation and a long run lower it.

- 阅读约 4 分钟RCD arrangement for a house boardCheck a New Zealand house board of eight circuits on two RCDs. See what fails with a fourth circuit on one RCD or both lights on one, and the AU change.

- 阅读约 4 分钟Total voltage drop: mains, submain and finalAdd the voltage drop of the consumer mains, a shed submain and a final subcircuit against the 5 % limit, and fix a long submain before the shed circuits fail.

- 阅读约 5 分钟Wire a bathroom: zones, IP ratings and the RCDA New Zealand bathroom with a 1.6 m bath and an open shower, worked through the AS/NZS 3000 Section 6 zones, the IP each item needs, the RCD and bonding.

- 阅读约 4 分钟Cable size for a 20 A heat pump circuit in summerA 20 A heat pump circuit over 18 m in a 40 °C roof space needs 4 mm², with a derated capacity of 22.88 A and a voltage drop of 1.59 percent.

- 阅读约 4 分钟AS/NZS 3000 Appendix C: conduit space factorWhat the conduit space factor in AS/NZS 3000 Appendix C governs, which tool reads it, and a worked 50 mm conduit that reaches 52.95 % fill against a 40 % limit.

- 阅读约 3 分钟EV charger cable size for a 7 kW 32 A circuitA 7 kW EV charger on a 32 A dedicated circuit over 30 m needs 6 mm², with 38 A derated capacity, 2.85 percent voltage drop and 0.73 Ω loop impedance.

- 阅读约 3 分钟AS/NZS 3000 Tables C1 and C2: demand groupsWhat the demand group letters govern, when to use Table C1 or Table C2, and a commercial assessment that returns 276.26 A total and 92.09 A per phase.

- 阅读约 4 分钟AS/NZS 3008.1.1 vs 3008.1.2: AU and NZ conditionsThe AU part of AS/NZS 3008.1 rates cable at 40 °C air and the NZ part at 30 °C. One 32 A circuit needs 6 mm² in Australia and 4 mm² in New Zealand.

- 阅读约 4 分钟AS/NZS 3008.1.2 Tables 4 to 21: current ratingsWhat the current rating tables govern, which table AmpSize reads today, and a 40 A circuit that lands on 10 mm² with a derated capacity of 50 A.

- 阅读约 4 分钟AS/NZS 3008 Table 13 (now 3.18): multicore ratingsWhat AS/NZS 3008 Table 13 gives, why the 2025 AU part calls it Table 3.18, how to read its columns into the calculator, and what moved for buried cable.

- 阅读约 3 分钟AS/NZS 3008 Table 22 (now 3.33): bunched groupingAS/NZS 3008 Table 22 is the grouping table for bunched circuits, not a temperature table. The 2025 AU part calls it Table 3.33. Read it in the calculator.

- 阅读约 3 分钟AS/NZS 3008 Table 27 (now 3.44, 3.45): temperatureAS/NZS 3008 Table 27 corrects a cable rating for the air or soil temperature. The 2025 AU part splits it into Tables 3.44 and 3.45 and re-derives the factors.

- 阅读约 4 分钟AWG and the NEC for NZ and AU electriciansAWG sizes and the NEC set against AS/NZS 3000 and 3008.1. A gauge converts to mm², but its rating does not, and the NEC 3 % drop figure is only a note.

- 阅读约 3 分钟Conduit fill: 4 x 6 mm² singles in 25 mmFour 6 mm² single-core cables in 25 mm conduit, with the fill percent, the space factor and the smallest conduit the tool recommends for the bundle.

- 阅读约 3 分钟AS/NZS 3000 Table 8.1: max Zs by curve and ratingTable 8.1 max Zs for a 16 A device, by curve. B allows 3.59 Ω, C allows 1.92 Ω and D allows 1.15 Ω. See why, with a 30 m circuit at 0.89 Ω.

- 阅读约 5 分钟AS/NZS 3008.1.1:2025: what changed from 2017The 2025 AU part adds d.c. ratings to 1500 V, renumbers every table and moves some ratings. Four circuits, each run on both editions, show what moves.

- 阅读约 3 分钟Voltage rise for a 5 kW solar inverter cableA 5 kW single-phase inverter 40 m from the switchboard on 10 mm² copper, with the rise in volts, the percent and the maximum length the tool returns.

- 阅读约 3 分钟AS/NZS 3000 Clause 3.6.2: voltage drop limitWhat Clause 3.6.2 governs, how the 5 percent budget splits across mains and subcircuits, and a 25 A run over 35 m that returns 2.6 percent from the engine.

- 阅读约 4 分钟Cable size for a 32 A single‑phase 25 m runWork through a 32 A single-phase circuit over 25 metres in New Zealand. See every derating factor, the check that sets the size, and the result the tool gives.

- 阅读约 4 分钟Domestic maximum demand with Table C1Assess the maximum demand of a New Zealand house from Table C1, group by group, with a worked example that lands on 52.61 A on a single-phase supply.

- 阅读约 4 分钟Earth fault loop impedance and maximum ZsWhat earth fault loop impedance measures, how the maximum Zs check works, and a 32 A circuit on 6 mm² over 25 m that lands on 0.67 ohms against a 0.96 limit.

- 阅读约 3 分钟Voltage drop with the mV/A·m methodHow the millivolt per amp metre method works, with a 32 A run over 25 metres on 6 mm² copper and the exact drop, percent and maximum length the tool returns.

本指南使用的计算器
- 现场软线长度计算器施工现场上电缆或软线可以敷设的最长长度。
- 干扰光检查器依据 AS/NZS 4282,检查边界窗处的室外照明干扰光。
- 电压降计算器计算电缆线路的电压降并检查限值。
- 蓄电池电弧闪络与等级蓄电池 DVC、危险等级、电弧闪络能量及个人防护装备等级。
- 欧姆定律与功率V、I、R 和 P 中任意两项可求出其余两项。
- 接地故障回路阻抗计算器对照最大 Zs 检查接地故障回路阻抗。
- RCD 持续漏电流预算一个 RCD 可承受多少持续漏电流。
- 根据负荷清单进行发电机选型根据负荷清单(含电动机启动)为发电机选型。
- 最大需量计算器估算家用或非家用负荷的最大需量。
- 配电箱回路一览表制作配电箱回路一览表及其所需标签。
- 配电箱测试记录表打印配电箱测试单,并列出每项测试的限值。
- 电缆截面计算器求出通过各项检查的最小电缆截面。
- IP 防护等级表与解读解读 IP 代码,并求出某位置的最低 IP 要求。
- 电线颜色指南查找固定布线及软线(新旧均包括)的导线颜色。
- 电缆短路耐受计算器检查导体能否承受故障电流。
- 光伏组串计算器光伏组件每串数量、组串电流及隔离开关。
- 最大回路长度计算器电压降和故障回路所允许的最长线路。
- 现有回路检查检查已安装回路:电缆、保护装置、电压降和 Zs。
- 线管填充率计算器检查电缆束能否放入线管。
- 回路负荷计算器统计终端分支回路可承载的点位数。
- 最小导体截面查询查阅回路允许的最小导体截面。
- 蓄电池位置检查器依据 AS/NZS 5139,检查家用储能电池可以安装在哪里。
- 插座位置检查灶台、煤气瓶、通风口或水槽附近的插座。
- 筒灯净距检查IC、CA90 或 Non‑IC:绝缘材料可以接触灯具吗?
- 附属建筑接地棚屋接地:可与分支干线共用接地,或采用独立的 MEN。
- 太阳能储能电池计算器为光伏晚间负荷选型家用储能电池。
- 修正系数计算器读取每个修正系数,以及电缆所需的额定值。
- RCD 配置检查检查每个 RCD 的回路数及照明分配。
- 总电压降计算器将进线、分支干线和终端分支回路的压降相加,并对照 5 %。
- 潮湿区域分区检查器求出近水区域的 Section 6 分区、IP 及 RCD。
- 英制电缆截面换算器求出旧式英制电缆的保护装置额定值。
- 电压升高计算器计算分布式发电或光伏的电压升高。