What size cable for power points in Australia?

电缆截面计算器

+2 references

Worked to AS/NZS 3008.1.1:2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

导体规格

2.5mm²

降容后的容量
20A
电压降
3.92%
接地导体
2.5mm²
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Cable Size tool: conductor size 2.5 mm².

A power point circuit on a 20 A breaker in Australia takes 2.5 mm² copper cable on a typical route. The tool reads AS/NZS 3008.1.1:2025 at its 40 °C air reference. For 25 m of multicore PVC cable enclosed in air, it gives 20 A of derated capacity and a voltage drop of 3.92 %.

The case

The circuit is single‑phase at 230 V, with a design current of 20 A on a curve C breaker. No other circuit shares the route. The voltage drop limit is 5 %. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.8 Ω.

The capacity equals the breaker rating here, so the cable has no spare margin. Any derating moves the size up.

What changes the answer

Grouping changes it. With three circuits bunched together, the tool selects 6 mm² with 23.1 A of capacity.

The same circuit in New Zealand reads AS/NZS 3008.1.2:2017 at its own reference temperature. There the cable has 23 A of capacity.

See also: What size cable for power points in NZ? and AS/NZS 3008.1.1:2025 overview.

使用这些输入试用

环境温度
40 °C
芯线
多芯
装置曲线
C 型曲线
检查保护装置
是
版本
AS/NZS 3008.1.1:2025
成组回路
1
绝缘
PVC 75 °C
标准
AU · AS/NZS 3008.1.1
敷设长度
25 m
设计电流
20 A
材料
铜
敷设方式
Enclosed in air
功率因数
1
相
单相
保护装置额定值
20 A
电压降限值
5 %
电压
230 V
外部阻抗 Ze
0.35 Ω