What size cable for a 22 kW EV charger?

电缆截面计算器

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

导体规格

6mm²

降容后的容量
38A
电压降
1.04%
接地导体
2.5mm²
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Cable Size tool: conductor size 6 mm².

A 22 kW three‑phase EV charger on a 32 A circuit takes 6 mm² copper cable on a typical route. For 20 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 38 A of derated capacity and a voltage drop of 1.04 %.

The case

At 400 V and unity power factor, a 22 kW charger draws 31.75 A in each phase. The circuit is sized for the full 32 A of its curve C breaker. Ze is 0.35 Ω and the voltage drop limit is 5 %. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.61 Ω.

What changes the answer

Length moves it. Over 60 m, the earth fault loop impedance sets the size, and the tool selects 10 mm² with a drop of 1.85 %.

The charger's circuit also needs its RCD and the spare capacity of the supply checked. The EV charger tool covers both.

See also: Three‑phase EV charger current and EV charger cable size for a 7 kW circuit.