跳至内容
AmpSize

配电箱测试记录表

打印配电箱测试单,并列出每项测试的限值。

Reads Electricity (Safety) Regulations 2010, AS/NZS 3000:2018 and AS/NZS 3017:2022. Tables checked 1 Oct 2026.

输入

使用默认输入值的示例计算。

国家
新西兰
配电箱名称
未说明
末端分路
6 行

图纸上的回路

6

顺序中的测试
7
主接地和等电位连接,至多
0.5Ω
没有 Table 8.1 对应行的回路
0
测试顺序
De-energized, earth continuity, insulation, polarity, phase sequence, Zs, RCD

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 测试 1验证已停电

    AS/NZS 3017:2022 Cl 4.3

  2. 测试 2接地连续性

    AS/NZS 3017:2022 Cl 4.4

  3. 测试 3绝缘电阻

    AS/NZS 3017:2022 Cl 4.5

  4. 测试 4极性及正确的回路连接

    AS/NZS 3017:2022 Cl 4.6

  5. 测试 4多相插座的相序

    AS/NZS 3017:2022 Cl 4.7

  6. 测试 5接地故障回路阻抗

    AS/NZS 3017:2022 Cl 4.8

  7. 测试 6RCD 动作

    AS/NZS 3017:2022 Cl 4.9

  8. 测试 7重做未通过的测试,以及可能受其影响的前序测试

    AS/NZS 3017:2022 Cl 4.2.2

  9. 回路 1 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  10. 回路 1 接地连续性 Re,不超过1Ω

    AS/NZS 3000:2018 Table 8.2

  11. 回路 1 接地故障回路阻抗,不超过3.1Ω

    AS/NZS 3000:2018 Table 8.1

  12. 回路 1 Rphe,不超过2Ω

    AS/NZS 3000:2018 Table 8.2

  13. 回路 1 RCD 在 30 mA 下的动作时间,不超过300ms

    Electricity (Safety) Regulations 2010 reg 24

  14. 回路 2 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  15. 回路 2 接地连续性 Re,不超过0.5Ω

    AS/NZS 3000:2018 Table 8.2

  16. 回路 2 接地故障回路阻抗,不超过1.5Ω

    AS/NZS 3000:2018 Table 8.1

  17. 回路 2 Rphe,不超过1Ω

    AS/NZS 3000:2018 Table 8.2

  18. 回路 2 RCD 在 30 mA 下的动作时间,不超过300ms

    Electricity (Safety) Regulations 2010 reg 24

  19. 回路 3 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  20. 回路 3 接地连续性 Re,不超过0.5Ω

    AS/NZS 3000:2018 Table 8.2

  21. 回路 3 接地故障回路阻抗,不超过1.5Ω

    AS/NZS 3000:2018 Table 8.1

  22. 回路 3 Rphe,不超过1Ω

    AS/NZS 3000:2018 Table 8.2

  23. 回路 3 RCD 在 30 mA 下的动作时间,不超过300ms

    Electricity (Safety) Regulations 2010 reg 24

  24. 回路 4 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  25. 回路 4 接地连续性 Re,不超过0.5Ω

    AS/NZS 3000:2018 Table 8.2

  26. 回路 4 接地故障回路阻抗,不超过1.5Ω

    AS/NZS 3000:2018 Table 8.1

  27. 回路 4 Rphe,不超过1Ω

    AS/NZS 3000:2018 Table 8.2

  28. 回路 4 RCD 在 30 mA 下的动作时间,不超过300ms

    Electricity (Safety) Regulations 2010 reg 24

  29. 回路 5 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  30. 回路 5 接地连续性 Re,不超过0.5Ω

    AS/NZS 3000:2018 Cl 8.3.5

  31. 回路 5 接地故障回路阻抗,不超过1Ω

    AS/NZS 3000:2018 Table 8.1

  32. 回路 6 绝缘电阻,不低于1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  33. 回路 6 接地连续性 Re,不超过0.5Ω

    AS/NZS 3000:2018 Table 8.2

  34. 回路 6 接地故障回路阻抗,不超过1.5Ω

    AS/NZS 3000:2018 Table 8.1

  35. 回路 6 Rphe,不超过1Ω

    AS/NZS 3000:2018 Table 8.2

  36. 主接地和等电位连接,至多0.5Ω

    AS/NZS 3000:2018 Cl 8.3.5

关于此计算器

How this is calculated

You list the final subcircuits of one board: what each supplies, its protective device and rating, its active conductor, single or three phase, and its RCD. The tool turns the list into the sheet you test from.

The tests follow the preferred order of the verification standard's sequence figure. First prove the circuit de-energized. Then test earth continuity, insulation resistance, and polarity with the correct connection of each circuit. A circuit with three‑phase socket‑outlets also takes the phase sequence test, so every outlet of a type turns a motor the same way. Then the earth fault-loop impedance, and last the operation of each RCD. If a test fails, fix the fault and repeat that test and any earlier one it may have upset.

Each circuit carries the limits its readings are judged against. They come from the wiring rules, through the same code the test results tool uses: the insulation resistance and its test voltage, the earth continuity Re and the Rphe from the subcircuit resistance table, and the earth fault-loop impedance from the loop impedance table, at a 0.4 s disconnection time. Where the resistance table has no row, Re falls back to the main earth figure, and the tool says so.

An RCD must operate at about its rated residual current and disconnect the circuit. In New Zealand the sheet also holds it to the regulations' trip time at that current. In Australia the sheet states no time, since the verification standard prints none.

StepTable or clauseWhat it decides
Order of testsAS/NZS 3017 Figure 4.1The sequence on the sheet
Repeat after a fixAS/NZS 3017 Cl 4.2.2Which tests to run again
Insulation resistanceCl 8.3.6The least resistance and the test voltage
Earth continuity and RpheTable 8.2The most each conductor may read
Earth fault-loop impedanceTable 8.1The most Zs may read
Phase sequenceAS/NZS 3017 Cl 4.7Which circuits take it
RCDAS/NZS 3017 Cl 4.9.4 and reg 24What the RCD must do, and the NZ trip time

Worked examples

  • A New Zealand house board. The sheet holds 6 circuits. The 10 A lighting circuit reads Zs at most 3.1 Ω, and each 30 mA RCD trips within 300 ms.
  • An Australian house board. The same 6 circuits, and each RCD must operate at about 30 mA; the sheet states no trip time.
  • A workshop board. The sheet holds 4 circuits. The three‑phase socket circuit takes the phase sequence test, and the D20 compressor reads Zs at most 0.9 Ω.

Limits

The sheet sets out the tests and the limits; it does not judge a reading. Put a reading into the test results tool to check it, or use it for a fuse circuit at a 5 s disconnection time. The sheet covers final subcircuits: test the main earthing conductor and the bonding against their own limit, shown on the sheet. It does not replace the visual inspection the standard asks for first.

See also: The order of verification tests, A test sheet for a house board and Test Results.

问题

结果仅供设计参考。请依据现行标准核对。

新装置应按什么顺序测试?

AS/NZS 3017 Figure 4.1 规定了优先顺序:先验证已停电,然后依次为接地连续性、绝缘电阻、极性及连接、接地故障回路阻抗,最后是 RCD。后续发现的故障可能影响先前的测试,因此修复后应重新进行这些测试。

合格限值来自哪里?

来自 AS/NZS 3000:绝缘电阻依据 Cl 8.3.6,接地连续性 Re 和 Rphe 依据 Table 8.2,接地故障回路阻抗依据 Table 8.1。这些与测试结果工具检查读数所用的限值相同。

RCD 需要多长的动作时间?

在新西兰,表格按 Electricity (Safety) Regulations 的限值,要求 30 mA RCD 在其额定剩余电流下动作。AS/NZS 3017 要求每个 RCD 在约其额定电流下动作并切断回路,且未规定时间,因此澳大利亚版表格不给出时间。

哪些回路需要相序测试?

带多相插座的回路,使同一类型的每个插座具有相同的相序(AS/NZS 3017 Cl 4.7)。请在该回路上勾选三相插座选项。

我可以打印这张表吗?

是的。PDF 会打印每个回路及其限值,并留出绝缘、Re、Zs、极性和 RCD 读数的空白栏,供现场填写。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 1 Oct 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。