跳至内容
AmpSize

测试结果检查器

对照 Section 8 限值,检查实测测试结果。

Reads Electricity (Safety) Regulations 2010, AS/NZS 3000:2018 and AS/NZS 3017:2022. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

保护装置
B 型断路器
保护装置额定值
20 A
切断时间
0.4 s
相线
2.5 mm²
绝缘测试情形
500 V 下的普通回路
检查绝缘电阻
是
实测绝缘电阻
50 MΩ
检查接地连续性
是
末端分路接地导体的实测电阻
0.3 Ω
检查回路阻抗
是
实测 Zs
1.2 Ω
检查 RCD 跳闸时间
否
极性已确认
是

验证

通过

绝缘电阻
合格。测得 50 MΩ,最小值 1 MΩ
Earth continuity, subcircuit earth conductor
合格。测得 0.3 Ω,最大值 0.9 Ω
接地故障回路阻抗
合格。测得 1.2 Ω,最大值 2.9 Ω

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 绝缘电阻限值1MΩ

    AS/NZS 3000:2018 Cl 8.3.6

  2. 测试电压500V

    AS/NZS 3000:2018 Cl 8.3.6

  3. 接地连续性限值,subcircuit earth conductor0.9Ω

    AS/NZS 3000:2018 Table 8.2

  4. 最大接地故障回路阻抗2.9Ω

    AS/NZS 3000:2018 Table 8.1

  5. 额定电流 80% 时的最大 Rphe1.8Ω

    AS/NZS 3000:2018 Table 8.2

  6. 额定电流 80% 时的最大 Re0.9Ω

    AS/NZS 3000:2018 Table 8.2

  7. 绝缘电阻限值,AS/NZS 3017:20221MΩ

    AS/NZS 3017:2022 Cl 4.5.4

  8. 总接地及等电位连接限值,AS/NZS 3017:20220.5Ω

    AS/NZS 3017:2022 Cl 4.4.4

  9. 极性及回路接线已确认

    AS/NZS 3017:2022 Cl 4.6.4

  10. 检查已通过3 of 3

关于此计算器

How this is calculated

The tool compares your measured test values with the limits for the circuit. Tick the tests you did. The tool checks only those.

  1. Insulation resistance. The tool reads the minimum and the test voltage from AS/NZS 3000 Cl 8.3.6. It also reads the AS/NZS 3017:2022 figure from Cl 4.5.4.
  2. Earth continuity. It reads the limit for the earth conductor size from Table 8.2. It also reads the limit at 80 % of the rated current. AS/NZS 3017:2022 Cl 4.4.4 gives the main earth and bonding limit.
  3. Loop impedance. It reads the maximum Zs for the device and disconnection time from Table 8.1.
  4. RCD trip time. It compares your measured time with the limit for the rated residual current.
  5. Polarity. You confirm polarity and connections. The tool does not measure them. It points at AS/NZS 3017:2022 Cl 4.6.4.
  6. Verdict. The result passes only when every test you ticked passes.

Worked example

Limits

The tool does not take your readings. It does not correct a loop reading for temperature. A pass here is not a certificate. A competent person signs the verification. Use the loop impedance calculator to predict Zs before the test.

See also: Testing to Section 8, Earth fault loop impedance and maximum Zs and Table 8.1 maximum Zs explained.

问题

结果仅供设计参考。请依据现行标准核对。

测试结果工具有什么作用?

工具将您在现场测得的数值与 AS/NZS 3000 Section 8 的验收限值进行比较。它检查绝缘电阻、接地连续性、回路阻抗和 RCD 动作时间。每项检查均报告合格或不合格。总体结论为合格、不合格或未验证。

最小绝缘电阻是多少?

Clause 8.3.6.3 规定,直流 500 V 时为 1 MΩ。带护套的加热元件为 0.01 MΩ,RCD 功能接地连接为 0.05 MΩ。若存在浪涌保护或电子设备,测试电压可降至 250 V。

它采用哪个回路阻抗限值?

工具依据 AS/NZS 3000:2018 Table 8.1,按保护装置类型、额定值和切断时间,列出表中的最大 Zs。工具还会报告 Table 8.2 中在额定电流 80% 时的最大 Rphe 和 Re,适用于无负荷测试。

为何工具显示“未验证”?

您所要求的测试无法进行。Table 8.1 中没有与该保护装置额定值对应的行,或未选择任何测试。对于未进行的检查,本工具不会报告通过。请更改额定值,或使用回路阻抗工具。

AS/NZS 3017:2022 适用于哪些情况?

AS/NZS 3017:2022 给出各项检验测试的方法。其绝缘和总接地限值与 Section 8 一致,因此本工具两者均予引用。其回路阻抗表格保留一位小数,因此本工具的 Zs 采用 Table 8.1。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 26 Sept 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。