建筑面积需量计算器
根据建筑面积和用途估算商业需量。
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Estimate demand for a shop by floor areaThe demand of a 600 m² shop with airconditioning, from Table C3.
- Estimate demand for a warehouseA 3000 m² warehouse with ventilation and 40 kVA of special equipment.
- Estimate demand for a basement carparkA 4000 m² basement carpark with EV charging on a quarter of it.
- Estimate demand for an office floorAn 800 m² office with reverse cycle air, at the top of the range.
输入
使用默认输入值的示例计算。
- 相
- 三相
- 相电压
- 230 V
- 表中数值
- 印刷平均值
- 面积
- 2 行
- 特殊设备
- 0 kVA
每相最大需量
217.39A
- 总需求量
- 150kVA
- Offices · Light and power
- 75kVA
- Offices · Airconditioning, zonal reheat
- 75kVA
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 数值取自 Table C3打印平均值
AS/NZS 3000:2018 Table C3
- Offices · Light and power,能源需求50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Light and power,1500 m²75kVA
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat,能源需求50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat,1500 m²75kVA
AS/NZS 3000:2018 Table C3
- 总需量150kVA
AS/NZS 3000:2018 App C Para C2.4.3
- 每相电流,kVA ÷ (3 × 相电压)结果217.39A
AS/NZS 3000:2018 App C Para C2.4.3
关于此计算器
How this is calculated
The tool estimates the maximum demand of a commercial or light-industrial building from its floor area. It uses the energy demand method in AS/NZS 3000:2018 App C Para C2.4.3. It reads the VA per square metre from Table C3.
- Pick the figure. For each area, choose an occupancy and a use. The tool takes the printed average, or the low or high end of the printed range (Table C3). You can type your own figure instead.
- Work out each area. The tool multiplies the area by the VA per square metre and divides by 1000. The result is kVA.
- Add EV charging. The NOTE to Table C3 puts EV charging on top of all other energy demands. The tool adds the carpark EV rows to the total.
- Add special equipment. Table C3 prints no figure for it. You enter its kVA from the load details, and the tool adds it.
- Total demand. The tool adds every area and the special equipment (Para C2.4.3).
- Current. On one phase, the tool divides the kVA by the phase voltage. On three phases, it divides by 3 times the phase voltage. That gives the current in each phase.
| Step | Table or clause | What it decides |
|---|---|---|
| Figure per area | Table C3 | The VA per square metre for each use |
| EV charging | NOTE to Table C3 | The charging load added on top |
| Total demand | App C Para C2.4.3 | The sum of the areas and special equipment |
| Current | App C Para C2.4.3 | The demand in amps on each phase |
Worked example
- Small retail and office building with basement EV charging. Shops of 600 m² at 70 VA/m² for light and power and 30 VA/m² for air conditioning. Offices of 400 m² at 50 and 25 VA/m². A basement carpark of 300 m² at 15 VA/m², plus its EV charging at 20 VA/m². The total demand is 100.5 kVA. The current is 145.65 A per phase at 230 V.
- The Paragraph C2.4.3.2 case. 1500 m² of office at 50 + 50 VA/m². The total demand is 150 kVA. The current is 217.39 A per phase.
Limits
- Table C3 is for commercial and light-industrial buildings. It is not for homes. Use Table C1 for a home.
- The figures depend on the climate, the hours of use, energy management and how evenly the load spreads.
- The per phase figure assumes an even spread over three phases. Check the heaviest phase where the load is uneven.
- The tool uses the phase voltage. On a 230/400 V supply, enter 230.
- Special equipment has no printed figure. You must know its kVA. The tool does not guess it.
- An own figure outside the printed range gives a warning. Check it before you rely on it.
- To work from a list of loads, use the Table C2 method in the Maximum Demand tool.
See also: The energy demand method and Table C3, Shop and office maximum demand by floor area and the Maximum Demand tool.
问题
结果仅供设计参考。请依据现行标准核对。
何时使用 Table C3 而非 Table C2?
Table C3 适用于设计初期的商业或轻工业建筑,此时已知建筑面积及用途,但尚不知负荷。Table C2 需要负荷组。负荷确定后,请依据 Table C2 核对需量。
应从范围中取哪个数值?
工具默认采用标准中给出的平均值。标准指出,这些数值取决于气候、运行时长、能源管理以及负荷分布的均匀程度。炎热气候或运行时间长时取较高值,也可输入您自己的数值。
本工具如何将 kVA 换算为安培?
本工具用总 VA 除以相电压。三相时除以三倍相电压,因此 230 V 下 150 kVA 得出每相 217.39 A。这与 Paragraph C2.4.3.2 中的示例一致。
停车场的数值中是否已计入电动汽车充电?
否。Table C3 将电动汽车充电单列为露天及地下停车场的一行,其注规定该负荷另计于所有其他需量之外。请在停车场面积旁增加电动汽车充电区域的面积。
仓库或车间的专用设备如何处理?
Table C3 未给出专用设备的数值。请根据负荷详情计算,并以 kVA 输入。本工具将其计入总量。
本工具读取的条款和表格
- AS/NZS 3000:2018 App C Para C2.4.3Energy demand method for commercial installations
- AS/NZS 3000:2018 Table C3Maximum demand, energy demand method for non‑domestic installations
表格最后核对于 1 Oct 2026。
相关工具
这是否有用?
有问题,或数值看起来有误?联系我们。