电压升高计算器
新西兰和澳大利亚太阳能及分布式发电电压升高计算器,对照 AS/NZS 4777.1 限值进行检查。
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 4777.1:2016. Tables checked 27 Sept 2026.
尝试一个工程 6
每项工作都会预填示例数值。请替换为您自己的数值。
- Check solar voltage riseThe voltage rise on a 45 m cable from a 5 kW inverter.
- Check rise on a three‑phase inverterThe rise on a 10 kW three‑phase inverter cable of 30 m.
- Check rise on a long rural runThe rise on 5 kW over 80 m.
- Check rise against a 2 % limitThe rise on a 3 kW inverter in Australia against 2 %.
- Check rise on a battery inverterThe rise on a 5 kW battery inverter over 15 m.
- Check rise on a 30 kW arrayThe rise on a 30 kW commercial inverter over 40 m.
输入
使用默认输入值的示例计算。
- 相
- 单相
- 电压
- 230 V
- 逆变器输出
- 5 kW
- 功率因数
- 1
- 敷设长度
- 30 m
- 标准
- NZ · AS/NZS 3008.1.2
- 电缆
- 10 mm² 铜 PVC 75 °C
- 电压升高限值
- 2 %
电压升高
1.26%
- 逆变器电流
- 21.74A
- 电压升高
- 2.91V
- 限值下的最大长度
- 47.44m
- 电压升高限值
- 2%
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 逆变器输出电流21.74A
- 电阻2.23Ω/km
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- mV/A·m4.46mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- 电压升高2.91V
- 电压升高百分比结果1.26%
- 最大长度47.44m
关于此计算器
How this is calculated
The tool works out the voltage rise on the cable between an inverter and its point of supply. It uses the cable data of AS/NZS 3008.1.2:2017. The Australian choice reads AS/NZS 3008.1.1:2025 and the superseded 2017 edition.
- Inverter current. The tool divides the inverter power by the voltage and the power factor. On three phases, it also divides by the square root of three.
- Resistance and reactance. It reads the conductor resistance from Tables 34 and 35. It reads the reactance from Table 30. It uses the value for your size, material and insulation.
- Millivolts per ampere metre. It combines both values with the power factor. This is the method of Cl 4.5.
- Voltage rise. It multiplies the millivolts per ampere metre by the current and the run length. It gives the result in volts and as a percentage of the supply voltage.
- Maximum length. It finds the run length at which the rise equals your limit.
The limit is an input. AS/NZS 3000:2018 Cl 3.6.2 Note 3 refers the rise limit to AS/NZS 4777.1. Check the current edition for the value that applies to your site.
Worked example
- 5 kW inverter on 30 m of 10 mm² copper. The supply is single‑phase at 230 V with a power factor of 1. The inverter current is 21.74 A. The voltage rise is 2.91 V, or 1.26 %. That is within a limit of 2 %. The longest run at that limit is 47.44 m.
Limits
The limit of 2 % is a default you can change. It is not a value read from a standard. The tool does not check the inverter voltage settings or the rules of the network operator.
The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation. The tool does not size the cable for current. Use the cable size calculator for that.
See also: Solar inverter voltage rise at 5 kW, Voltage rise on a long rural PV run and the PV string tool.
问题
结果仅供设计参考。请依据现行标准核对。
电压升高计算器有什么作用?
工具依据逆变器额定值、电压及功率因数计算逆变器输出电流。然后计算沿电缆至供电点的电压升高,以伏特和百分比表示。它还报告仍满足限值的最长线路。
工具采用的电压升高限值是多少?
工具默认采用 2%,您可以更改。AS/NZS 3000:2018 Clause 3.6.2 注 3 将电压升高引用至 AS/NZS 4777.1。AmpSize 未收录 AS/NZS 4777.1。请阅读现行版本的 AS/NZS 4777.1,以获取适用于贵场地的限值。
哪些输入最重要?
逆变器额定值和线路长度直接按比例影响升高。导体截面和材料决定电阻。功率因数限定在 0.8 至 1 之间,默认为 1,即逆变器的常见情形。并联电缆分担阻抗。
还应检查什么?
本工具仅涵盖逆变器电缆上的升高。它不涵盖供电网络、保护或防孤岛。请使用电缆截面工具核对同一电缆的载流量。输入值保存在页面地址中,因此链接可重现该计算。
计算示例
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
- Voltage rise for a 5 kW solar inverter cableA 5 kW single‑phase inverter 40 m from the switchboard on 10 mm² copper, with the rise in volts, the percent and the maximum length the tool returns.
背景
- Voltage drop basicsOhm's law on a cable, the mV/A·m shortcut, the percent limit and the maximum length, worked on a 25 A run over 35 m of 4 mm² copper.
- PV and inverter basicsHow a grid-connected PV system connects to an installation, why voltage rise sets the inverter cable, and which standards the AmpSize tools cannot quote.
本工具读取的条款和表格
- AS/NZS 3008.1.2:2017 Cl 4.5Voltage drop method
- AS/NZS 4777.1:2016 Cl 3.3Inverter connection voltage rise
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
表格最后核对于 27 Sept 2026。