跳至内容
AmpSize

This page is not in 简体中文 yet, so you are reading the English.

· 阅读约 1 分钟

Maximum Zs for a 16 A curve C breaker

接地故障回路阻抗计算器

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 27 Sept 2026.

允许的最大 Zs

1.92Ω

接地故障回路阻抗
0.89Ω
Zs 下的最大长度
86.94m
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Loop Impedance tool: earth fault loop impedance 0.89 Ω; checked.

A 16 A curve C circuit breaker allows a maximum earth fault loop impedance of 1.92 Ω at 230 V. The tool reads it from AS/NZS 3000:2018 Table 8.1. A measured or calculated Zs at or below that value disconnects a fault in time.

The case

The circuit is 30 m of 2.5 mm² copper PVC cable with a 2.5 mm² earth, on a supply with Ze of 0.35 Ω. R1 + R2 is 0.54 Ω, so Zs is 0.89 Ω, well inside the limit. The longest run that still meets the limit is 86.94 m.

What changes the answer

The curve sets the limit. A 16 A curve B breaker trips at a lower multiple of its rating, so it allows 3.59 Ω, and the same cable can run 180.01 m.

A higher Ze shortens every run. Measure Ze at the board before you rely on a calculated Zs.

See also: AS/NZS 3000 Table 8.1 maximum Zs explained and Earth fault loop impedance and disconnection time.

使用这些输入试用

有源导体规格
2.5 mm²
装置曲线
C 型曲线
接地导体规格
2.5 mm²
绝缘
PVC 75 °C
标准
NZ · AS/NZS 3008.1.2
敷设长度
30 m
材料
铜
保护装置额定值
16 A
电压
230 V
外部阻抗 Ze
0.35 Ω
使用这些输入打开计算器

下一步

其背后的概念

更多示例

AmpSize 是设计辅助工具。请对照现行标准核实结果。

这是否有用?

有问题,或数值看起来有误?联系我们。