总电压降计算器
将进线、分支干线和终端分支回路的压降相加,并对照 5 %。
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check the total voltage drop to a shedThe mains, the shed submain and a final subcircuit added against 5 %.
- Find the drop left for a new circuitWhat 25 m of mains and a 40 m submain leave for a final subcircuit.
- Add a three phase submain to a finalThree phase mains and submain with a single phase final, added by percent.
- Use the 7 % substation limitA factory fed from its own transformer, checked against 7 %.
输入
使用默认输入值的示例计算。
- 供电点
- 电网供电(5 % 限值)
- 标准
- NZ · AS/NZS 3008.1.2
- 功率因数
- 0.9
- 敷设路径中自供电点起的各段
- 3 行
总电压降
4.25%
- 电压降限值
- 5%
- 干线和分干线
- 1.98%
- 留给末端分路
- 3.02%
- 留在使用点
- 0.75%
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 第 1 部分用户主电源
- 第 1 部分 mV/A·m2.6mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- 第 1 部分电压降2.6V
- 第 1 部分电压降,占 230 V 的百分比1.13%
AS/NZS 3000:2018 App C Para C4.1
- 第 1 部分后的累计总计1.13%
AS/NZS 3000:2018 App C Para C4.1
- 第 2 部分分干线
- 第 2 部分 mV/A·m4.09mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- 第 2 部分电压降1.96V
- 第 2 部分电压降,占 230 V 的百分比0.85%
AS/NZS 3000:2018 App C Para C4.1
- 第 2 部分后的累计总计1.98%
AS/NZS 3000:2018 App C Para C4.1
- 第 3 部分末端分路
- 第 3 部分 mV/A·m16.31mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- 第 3 部分电压降5.22V
- 第 3 部分电压降,占 230 V 的百分比2.27%
AS/NZS 3000:2018 App C Para C4.1
- 第 3 部分后的累计总计4.25%
AS/NZS 3000:2018 App C Para C4.1
- 电压降限值5%
AS/NZS 3000:2018 Cl 3.6.2
- 总电压降结果4.25%
AS/NZS 3000:2018 Cl 3.6.2
- 干线和分干线1.98%
- 留给末端分路3.02%
AS/NZS 3000:2018 Cl 3.6.2
- 留在使用点0.75%
关于此计算器
How this is calculated
AS/NZS 3000 limits the voltage drop from the point of supply to any point in the installation. It is one limit for the whole run, not one per circuit. So the drop in the consumer mains, every submain and the final subcircuit must add up to no more than the limit. This tool adds them.
You enter each part of the run in order from the point of supply: the consumer mains, up to three submains and the final subcircuit. For each part you give the phases, the current, the route length and the cable. The tool works each part with the same calculation as the voltage drop tool. It reads the cable's resistance and reactance from AS/NZS 3008.1, finds the mV/A·m at the power factor, and gives the drop in volts.
Each drop is then taken as a percent of that part's own circuit voltage: 230 V for single phase and 400 V for three phase. Appendix C of AS/NZS 3000 adds the percents directly, so a three‑phase submain adds to a single‑phase final subcircuit with no conversion. The running total is the drop at the end of each part.
The limit is 5 % of the nominal voltage. Where the point of supply is the low voltage terminals of a substation on the premises, which supplies only this installation, it is 7 %. The clause sets no split between the parts. The tool shows what the mains and submains take, and what that leaves for a final subcircuit from the last board.
| Step | Table or clause | What it decides |
|---|---|---|
| Resistance and reactance of each part | AS/NZS 3008.1 Tables 34 and 35 | The impedance of the cable |
| Drop of each part | AS/NZS 3008.1 Cl 4.5 | The mV/A·m and the drop in volts |
| Percent of each part | AS/NZS 3000 App C Para C4.1 | The drop as a percent of its circuit voltage, added part by part |
| The limit | AS/NZS 3000 Cl 3.6.2 | The most the total may be from the point of supply |
| A substation on the premises | AS/NZS 3000 Cl 3.6.2 Exception 3 | The higher limit where it applies |
| A load spread along a final subcircuit | AS/NZS 3000 Cl 3.6.2 Exception 1 | The current you may use for that part |
Worked examples
- A house: mains, a garage submain and a socket‑outlet circuit. The total voltage drop is 4.25 %. The mains and submain take 1.98 %, which leaves 3.02 % for a final subcircuit.
- A shed 30 m from the house. The total voltage drop is 4.83 %, inside the 5 % limit but close to it. The upstream parts take 3.13 %, which leaves 1.87 % for a final subcircuit.
- A factory on its own substation. The total voltage drop is 6.27 % against the 7 % limit. The mains and submain take 4.38 %, which leaves 2.62 % for a final subcircuit.
- A farm workshop 60 m from the house. The total voltage drop is 10.82 %, so the run fails. The mains and submain take 8.55 % on their own, which leaves −3.55 % for a final subcircuit. A larger submain is the fix.
Limits
The tool works a.c. runs at 230 V and 400 V nominal. It does not check extra-low voltage circuits, which Cl 3.6.2 leaves out, or a stand-alone system, which Exception 4 judges on the utilisation voltage. Single‑core parts use the highest reactance the table gives for the formation. Use the voltage drop tool for one run with a known formation or an unbalanced neutral.
Motor starting and other short transient drops are not part of the limit. Check those against the equipment.
See also: Voltage drop, The 5 % voltage drop limit from supply to load and Total voltage drop: mains, submain and final.
问题
结果仅供设计参考。请依据现行标准核对。
5 % 的电压降是针对每个回路还是整个装置?
整个装置。AS/NZS 3000 Cl 3.6.2 限制从供电点到任一点的电压降。用户进线、分支干线及终端分支回路共用一个 5%,因此本工具将其相加。
进线与终端分支回路之间是否按 2 % 和 3 % 分配?
AS/NZS 3000 中并无此规定。Cl 3.6.2 只规定一个限值,未作拆分。设计人员常会作分配规划,但该条款仅要求总量不超过限值。工具显示进线和分支干线所占用量及剩余量。
如何在单相终端分支回路上增加三相分支干线?
按百分比计算。每一部分按其所在回路电压的百分比计算:三相为 400 V,单相为 230 V。AS/NZS 3000 的 Appendix C 直接将这些百分比相加。
限值何时为 7 %?
当供电点是同一场地内仅为本装置供电的变电站低压端子时。选择“自有变电站”,工具采用 7 %。
每个部分应使用哪个电流?
每个部分的最大需量、所接负荷或保护装置额定值,以您已知者为准。负荷沿线路分布的终端分支回路,可取保护装置额定值的一半。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 3000:2018 App C Para C4.1Adding voltage drop by percent
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit from the point of supply, and how the parts of an installation add
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
表格最后核对于 1 Oct 2026。