现场软线长度计算器

施工现场上电缆或软线可以敷设的最长长度。

Reads AS/NZS 3012:2019. Tables checked 1 Oct 2026.

输入

使用默认输入值的示例计算。

额定电流
10 A
导体截面积
2.5 mm²
电缆
单相,三芯
用途
一般用途,如锯、磨光机和电钻
从插座至设备的总长度
40 m
PSOA 供电引线
0 m
插座之前固定布线已使用的电压降
0 %
两个或以上的电源延长组件连接在一起
否
软线以盘绕或卷盘方式使用
否

最大长度

60m

已核对长度
40m
PSOA 供电引线
0m
限值内
是
线长所依据的电压降
5%
上游已使用的电压降
0%
设备处的总电压降
5%
参考
AS/NZS 3012:2019 Table 1

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 已录入长度40m

    AS/NZS 3012:2019 Table 1

  2. PSOA 供电引线0m

    AS/NZS 3012:2019 Cl 2.6.10(b)

  3. 长度按 Table 1 校核40m

    AS/NZS 3012:2019 Table 1

  4. 额定电流10A

    AS/NZS 3012:2019 Table 1

  5. 导体截面积2.5mm²

    AS/NZS 3012:2019 Table 1

  6. 长度所依据的电压降5%

    AS/NZS 3012:2019 Table 1

  7. 上游已使用的电压降0%

    AS/NZS 3012:2019 Table 1

  8. 该长度所隐含的总压降5%

    AS/NZS 3012:2019 Table 1

  9. 最大长度60m

    AS/NZS 3012:2019 Table 1

  10. 一般用途,单相结果60m

    AS/NZS 3012:2019 Table 1

  11. 一般用途,三相120m

    AS/NZS 3012:2019 Table 1

  12. 特定用途,单相35m

    AS/NZS 3012:2019 Table 1

  13. 特定用途,三相70m

    AS/NZS 3012:2019 Table 1

关于此计算器

How this is calculated

The tool checks a cord or flexible cable on a construction site. It uses the length limit in AS/NZS 3012:2019 Table 1. The limit depends on the rated current, the conductor area, the use and the phases.

  1. Length entered. You enter the length of the cord run. You can add the length of the PSOA supply lead, under Cl 2.6.10(b).
  2. Length checked. The tool adds the two. It checks that total against Table 1.
  3. Rated current and area. It reads the Table 1 row for your rated current and conductor area.
  4. Use and phases. It picks the column: general or specific use, single or three phase.
  5. Maximum length. It gives the Table 1 length. The inside-the-limit answer passes when the length checked is at or under it.
  6. Total drop. The Table 1 length is based on a 5 % drop. The tool adds the drop already used upstream and gives the total at the equipment.
StepTable or clauseWhat it decides
PSOA leadAS/NZS 3012 Cl 2.6.10(b)The length counted with the cord
Maximum lengthTable 1The limit for the rating, area and use
Total dropTable 1The drop at the equipment, with the upstream drop

Worked example

A 10 A single‑phase cord of 1.5 mm², 50 m long, for general use. The maximum length is 35 m. The 50 m run fails. A 2.5 mm² cord at 40 m passes, with a maximum of 60 m.

Limits

  • The 5 % drop is in addition to the drop the fixed installation already used. Enter the real upstream drop.
  • A zero upstream drop is the default. Treat it as optimistic.
  • The figures suit ordinary site power tools.
  • The smallest flexible cord conductor is 1 mm². Every cord carries its own earth conductor.
  • Cord extension sets use heavy duty sheathed cable (Cl 2.6.3).
  • Do not use double adaptors or piggyback plug adaptors (Cl 2.6.6).

See also: Construction site supplies, AS/NZS 3012, Builder's pole house build supply, RCDs and cord lengths and the site supply tool.

问题

结果仅供设计参考。请依据现行标准核对。

施工现场的延长线最长可以拉多长?

AS/NZS 3012:2019 Table 1 给出各额定电流及导体截面的限值。额定 10 A、2.5 mm² 的单相通用软线限长 60 m。同样截面的三相四芯电缆可达 120 m。

一般用途与特定用途有什么区别?

通用用途适用于锯、角磨机和电钻等日常现场工具。其长度允许在额定电流下压降 5 %。专用用途适用于电动机启动失败会危及人身安全的设备。其长度允许压降 3 %,因此长度较短。

表中的电压降是否包括固定布线?

否。表中的百分比叠加于固定布线在插座之前已产生的压降之上。请输入该数值,工具将显示设备处的总压降。每项结果均注明此点。

两根延长线可以接在一起使用吗?

是的,前提是整条线路都在 Table 1 的一个限值内。输入每组连接软线的总长度,工具将核对该总和。PSOA 供电线也计入其中,因此工具会将其相加。AS/NZS 3012 建议只用一组软线,并规定不得使用盘绕或卷在线盘上的软线。

允许的最小软线导体是多少?

Cl 2.6.2 规定软线每根芯线的最小截面为 1.0 mm²。软线还需要在带电导体旁设置一根接地导体。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 1 Oct 2026。