What size cable for a lighting circuit in NZ?

电缆截面计算器

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

导体规格

1.5mm²

降容后的容量
16A
电压降
4.3%
接地导体
1.5mm²
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Cable Size tool: conductor size 1.5 mm²; voltage drop checked.

A lighting circuit on a 10 A breaker in New Zealand takes 1.5 mm² copper cable on a typical route. For 30 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 16 A of derated capacity and a voltage drop of 4.3 %.

The case

The circuit is single‑phase at 230 V. The design current is the full 10 A of the curve C breaker. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 1.5 mm² earth, and the earth fault loop impedance is 1.34 Ω.

Voltage drop is the check closest to its limit. A longer run reaches the limit before the cable runs out of capacity.

What changes the answer

A 16 A lighting circuit on the same route takes 2.5 mm² with a drop of 3.76 %.

See also: How far can 1.5 mm² run on a 10 A circuit? and Voltage drop basics.