通信电缆选型
选择通信电缆并检查线路长度。
Reads AS/NZS 3000:2018 and Industrial communications sources 2019-2024. Tables checked 26 Sept 2026.
尝试一个工程 8
每项工作都会预填示例数值。请替换为您自己的数值。
- Add an instrument loopA cable for the signal over a 150 m route.
- Select a comms cableA PROFINET cable for a 60 m run through a drag chain.
- Check an RS-485 runWhether 400 m at 115.2 kbps is in the limit.
- Check a long Modbus trunkWhether 1200 m at 9.6 kbps is in the limit.
- Check an Ethernet run past 90 mWhether a 110 m Ethernet run is in the limit.
- Pick a 24 V field supply cableA cable for a 24 V d.c. supply over 80 m.
- Pick a screened cable beside a driveA screened signal cable for a noisy area.
- Pick an outdoor Ethernet cableAn Ethernet cable for an outdoor run.
输入
使用默认输入值的示例计算。
- 接口
- RS-485
- 环境
- 固定安装
- 敷设长度
- 100 m
- 护套材料
- PVC
- 电缆带屏蔽层
- 是
- 传输速率
- 187.5 kbps
- 母线电缆系列
- 标准型、加强型、FRNC、食品级、地埋或船用
敷设长度
限值内
- 长度限值
- 1,000m
- 电缆结构
- 1 pair or more, 2 cores, larger than 0.34 mm2, required screen
- 屏蔽层
- 必需
- 屏蔽检查
- 通过
- 每端的终端连接
- 120Ω
- 每线单位负载
- 32
- 环境检查
- 通过
- 类别检查
- 不适用
- 备注
- A PROFIBUS DP segment at 187.5 kbps on standard bus cable may run 1000 m, from a cable maker network manual. The held table falls from 1000 m at 9.6 kbps to 100 m from 3 Mbps up. TIA-485 itself sets no maximum line length, and a separate report gives a nominal 1.2 km on 24 AWG cable.
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 接口RS-485
Industrial communications sources 2019-2024
- 回路长度100m
- 长度限值1,000m
Industrial communications sources 2019-2024
- 长度校核通过
- 结构1 pair or more, 2 cores, larger than 0.34 mm2, required screen
Industrial communications sources 2019-2024
- 需要屏蔽required
Industrial communications sources 2019-2024
- 屏蔽检查通过
- 环境固定安装
Industrial communications sources 2019-2024
- 环境检查通过
- 类别检查不适用
- 传输速率187.5 kbps
- 印刷速度行187.5 kbps
Industrial communications sources 2019-2024
- 母线电缆系列标准总线电缆
Industrial communications sources 2019-2024
- 两端端接120Ω
Industrial communications sources 2019-2024
- 每线单位负荷32
Industrial communications sources 2019-2024
- 每段总线接入点数32
Industrial communications sources 2019-2024
关于此计算器
How this is calculated
The tool picks the cable construction for a control or data link. It checks your run length against the limit for the interface. No AmpSize figure here comes from a printed Standard. The figures come from maker data and course notes, which the tool labels as secondary sources.
- Interface. You pick 24 V d.c., 4–20 mA, RS-485, Ethernet or PROFINET. For RS-485 you also pick the data rate and the bus cable family.
- Length limit. The tool reads the longest run for that interface. For RS-485 the limit falls as the data rate rises.
- Length check. It compares your run with the limit. It reports the run as inside or over the limit.
- Construction. It gives the pairs, the cores and the smallest core size. It says whether a screen is required, and checks the screen you enter.
- Environment. It checks the sheath and the bend radius for a fixed or a flexing installation. For Ethernet it checks the category.
- Termination. For RS-485 it gives the termination at each end and the unit loads per line.
| Step | Source | What it decides |
|---|---|---|
| Length limit | Industrial communications sources 2019 to 2024 | The longest run for the interface |
| Construction and screen | Industrial communications sources 2019 to 2024 | The cable build |
| Termination | Industrial communications sources 2019 to 2024 | The resistor at each end |
Worked example
- RS-485 at 187.5 kbps over 1200 m. The limit is 1,000 m, so the run is over the limit. The screen and environment checks pass. Add a repeater or shorten the run.
Limits
- The figures are secondary source and maker data. They are not a Standard. Confirm each one with the device maker.
- The tool does not size power conductors. Use the DC cable size calculator for a 24 V supply.
- The tool does not check segregation from power cables. Use the segregation checker.
- The termination value suits typical cable. Match it to the cable you use.
- The 32 unit loads on an RS-485 line are not a device count.
See also: Control panels and PLC wiring, 24 V DC instrument loop voltage drop and Loop power.
问题
结果仅供设计参考。请依据现行标准核对。
通信电缆选型工具有什么作用?
为 24 V 直流、4–20 mA、RS-485、以太网或 PROFINET 链路指明电缆结构,并说明线路长度是否在该接口的限值之内。它还会根据环境检查护套、屏蔽层和弯曲半径。
RS-485 段的最大长度是多少?
工具依据电缆制造商手册报告 PROFIBUS DP 段长度:标准总线电缆在 187.5 kbps 及以下为 1000 m,500 kbps 时为 400 m,1.5 Mbps 时为 200 m,3 Mbps 及以上为 100 m。柔性和扭转电缆的线路应更短。
RS-485 的 32 个上限指的是什么?
以单位负载计,而非按设备数量计。一个单位负载在 12 V 共模应力下耗电 1 mA。输入电阻超过 12 kΩ 的接收器仅相当于一个单位负载的一部分,因此一条线路可接入超过 32 个接收器。
RS-485 需要什么终端匹配?
终端电阻等于线路的特性阻抗。所用的源按两端各 120 ohm 工作,因此应与所用电缆匹配。足够短、可按集总参数处理的线路无需终端电阻。
24 V 直流和 4–20 mA 适用什么长度限制?
两者均无公布的长度。24 V 直流线路受电压降限制,因此请在 24 V 下使用 AmpSize 电压降工具。4–20 mA 回路受回路负载和变送器供电电压限制。
背景
本工具读取的条款和表格
- AS/NZS 3000:2018 Table 3.3Nominal minimum cross-sectional area of conductors
- Industrial communications sources, interface limitsLength, screen and construction limits for five industrial interfaces
表格最后核对于 26 Sept 2026。