Every guide on this site is one calculation, run end to end, with the table behind each number. The index below groups them by calculator and tags each one with the trade it was written for.
The shape of a worked example
Take the shortest case on the site. A single‑phase circuit carries 20 A at 230 V over 15 m. The cable is multicore copper with PVC insulation, enclosed in air at 30 °C. One circuit shares the route. The device is a 20 A C curve and Ze is 0.35 Ω.
Selection follows AS/NZS 3000:2018 Cl 3.4, with ratings from AS/NZS 3008.1.2:2017 Tables 4-21. The total derating factor is 1, so the required tabulated current stays at 20 A. The answer is 2.5 mm². The derated capacity is 23 A and the drop is 2.13 %. Zs is 0.62 Ω on a 2.5 mm² earth conductor.
Every guide below follows that order: the circuit, the clause, the steps, the result.
Index by calculator
Arc flash
- Arc flash incident energy at a 400 V switchboard — industrial
- Arc flash boundary at a motor control centre — automation
- Arc flash label inputs for a commercial main switchboard — commercial
Battery
- Off-grid battery bank autonomy at 48 V — solar
- Battery backup for a PLC panel at 24 V DC — instrumentation
- Battery bank for three days autonomy in winter — solar
Cable size
- Cable size for a 32 A single‑phase 25 m run — domestic
- AS/NZS 3008 2025 changes: what moved from 2017 — commercial
- Cable size for a 20 A heat pump circuit in summer — domestic
- EV charger cable size for a 7 kW 32 A circuit — domestic
- Submain cable size for 3‑phase 100 A over 60 m — commercial
- Hot water cylinder circuit cable size for 3 kW — domestic
Conduit fill
- Conduit fill for 4 x 6 mm² singles in 25 mm conduit — domestic
- Conduit fill for a 4 x 35 mm² submain in 50 mm conduit — commercial
- Conduit fill for six PV string cables in 32 mm conduit — solar
Fault rating
- Prospective fault current at a main switchboard — commercial
- Consumer mains fault withstand for 16 mm² copper — domestic
- Switchboard fault rating: conductor withstand at 25 kA — automation
Full load current
- Full load current for a 22 kW three‑phase EV charger — solar
- Commercial kitchen kW to amps full load current — commercial
- Chiller kVA rating to full load current for an estimate — estimator
Generator
- Generator sizing for a 150 kVA holiday park backup — commercial
- Generator full load current: 200 kVA to amps — estimator
- Generator fault current from subtransient reactance — engineer
IDMT protection
- IDMT curve grading for a 100 A feeder — automation
- Dairy shed switchboard IDMT grading before shutdown — industrial
- IDMT grading between a commercial main switch and submain — commercial
Loop impedance
- Earth fault loop impedance and maximum Zs — domestic
- Loop impedance maximum length for a 20 A final subcircuit — domestic
- Shop lighting circuit loop impedance on a B curve 10 A — commercial
Maximum demand
- Domestic maximum demand with Table C1 — domestic
- Commercial maximum demand with Table C2 for a tender — estimator
- Office fitout maximum demand per phase with Table C2 — estimator
- Winter heating maximum demand with Table C1 group D — domestic
- Block of units maximum demand with Table C1 three‑phase — estimator
Motor
- Motor full load current and DOL start for 11 kW 400 V — industrial
- Motor starting current for a 55 kW DOL start — industrial
- Dairy shed vacuum pump motor: 15 kW full load current — industrial
Three‑phase power
- Three‑phase power: kVA to amps at 400 V — apprentice
- Plant metering: current and power factor to kW — instrumentation
- Supply application kVA from maximum demand — estimator
Transformer
- Transformer secondary fault current for 500 kVA — engineer
- Transformer full load current for 1000 kVA at 11 kV — industrial
- Commercial building transformer kVA to amps — commercial
Voltage drop
- Voltage drop with the mV/A·m method — domestic
- Voltage drop on a 24 V DC instrument loop — instrumentation
- Submain voltage drop estimate for a 160 A tender — estimator
- Voltage drop single‑phase vs three‑phase worked example — apprentice
- Homeowner shed supply voltage drop over 60 m — homeowner
Voltage rise
- Voltage rise for a 5 kW solar inverter cable — solar
- Voltage rise for a 10 kW three‑phase inverter — solar
- Voltage rise on a long rural PV run of 80 m — solar
The tag after each link names the trade the example was written for. The method still applies across trades: a 400 V motor feeder and a 230 V heat pump circuit take the same five checks.
To compare AmpSize with other cable size calculators, read the cable size calculators compared table.
This page is a design aid. Verify every value against the current edition of the standard.
See also: Current-carrying capacity and derating, Maximum demand and diversity and IB ≤ IN ≤ IZ: the overload rule on a 32 A circuit.