Worked examples index by tool and trade

Cable size calculator

+4 references

Worked to AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017 (NZ). Tables checked 27 Sept 2026.

The inside of an electrician's van, with cable reels, tool cases and test gear on shelves.

Every guide on this site is one calculation, run end to end, with the table behind each number. The index below groups them by calculator and tags each one with the trade it was written for.

The shape of a worked example

Take the shortest case on the site. A single‑phase circuit carries 20 A at 230 V over 15 m. The cable is multicore copper with PVC insulation, enclosed in air at 30 °C. One circuit shares the route. The device is a 20 A C curve and Ze is 0.35 Ω.

Selection follows AS/NZS 3000:2018 Cl 3.4, with ratings from AS/NZS 3008.1.2:2017 Tables 4-21. The total derating factor is 1, so the required tabulated current stays at 20 A. The answer is 2.5 mm². The derated capacity is 23 A and the drop is 2.13 %. Zs is 0.62 Ω on a 2.5 mm² earth conductor.

Every guide below follows that order: the circuit, the clause, the steps, the result.

Index by calculator

Arc flash

Battery

Cable size

Conduit fill

Fault rating

Full load current

Generator

IDMT protection

Loop impedance

Maximum demand

Motor

Three‑phase power

Transformer

Voltage drop

Voltage rise

The tag after each link names the trade the example was written for. The method still applies across trades: a 400 V motor feeder and a 230 V heat pump circuit take the same five checks.

To compare AmpSize with other cable size calculators, read the cable size calculators compared table.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Current-carrying capacity and derating, Maximum demand and diversity and IB ≤ IN ≤ IZ: the overload rule on a 32 A circuit.

Subukan gamit ang mga input na ito

Ambient na temperatura
30 °C
Mga core
Multicore
Curve ng device
Curve C
Suriin ang protective device
Oo
Naka-group na circuit
1
Insulation
PVC 75 °C
Haba ng run
15 m
Design current
20 A
Material
Tanso
Installation method
Enclosed in air
Power factor
0.9
Mga phase
Single phase
Device rating
20 A
Limit ng voltage drop
5 %
Voltage
230 V
External impedance Ze
0.35 Ω
Buksan ang calculator gamit ang mga input na ito

Ano ang susunod

Ang mga ideyang nasa likod nito

Higit pang worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.