حاسبة مستوى العطل
تيار العطل المتوقع عند لوحة من مصدرها.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
جرّب مشروعاً 8
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Find the fault level at a sub‑boardThe fault current at a board 45 m from a 300 kVA transformer, against 6 kA breakers.
- Check breakers beside a 1000 kVA transformerWhether 25 kA breakers suit a main board 20 m from a 1000 kVA transformer.
- Find the fault level at a house boardThe fault current at the end of 20 m of 16 mm² mains.
- Find the fault level at a shedThe fault current 60 m down a 16 mm² submain.
- Find the fault level at an MCCThe fault current 30 m from a 500 kVA transformer.
- Check 6 kA breakers at a tenancy boardWhether 6 kA devices suit the fault level at the board.
- Find the fault level on parallel feedersThe fault current with two cables per phase.
- Find fault level from a 10 kA serviceThe fault current at a board in Australia.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- المصدر
- المحوّل
- تقنين المحوّل
- 500 kVA
- معاوقة المحوّل
- 4.5 %
- جهد الخط
- 400 V
- المعيار
- NZ · AS/NZS 3008.1.2
- طول الخط الفرعي الرئيسي
- 30 m
- حجم الموصل
- 35 mm²
- المادة
- النحاس
- العزل
- PVC 75 °C
- الأسلاك الداخلية
- متعدد القلوب
- الكابلات المتوازية
- 1
- سعة قطع قاطع الدائرة
- 15 kA
تيار العطل ثلاثي الطور عند اللوحة
10.01kA
- الحد الأقصى لتيار عطل الطور إلى الأرض
- 3.18kA
- تيار عطل الطور إلى الأرض، والكابل حيّ
- 2.63kA
- معاوقة المصدر لكل طور
- 14.4mΩ
- سعة القطع
- 15kA
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- معاوقة المحول لكل طور، U² ÷ S × Z%0.01Ω
- تيار العطل عند المصدر16.04kA
- مقاومة طور الفرعي الرئيسي عند درجة حرارة التشغيل0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- مقاومة طور الفرعي الرئيسي عند 20 °C0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- مفاعلة الطور للفرعي الرئيسي0Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- مقاس الموصل الوقائي10mm²
AS/NZS 3000:2018 Table 5.1
- مقاومة الموصل الوقائي عند 20 °C0.06Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- تيار العطل ثلاثي الأطوار عند اللوحة، U0 ÷ |Z|النتيجة10.01kA
- تيار عطل الطور إلى التأريض عند اللوحة، الأقصى3.18kA
- تيار عطل الطور إلى التأريض، الكابل عند درجة حرارة التشغيل2.63kA
- قدرة قطع القاطع15kA
حول هذه الحاسبة
How this is calculated
The tool finds the fault current at a board. The source is a transformer or a stated supply fault level. A submain then adds impedance. The tool compares the result with the breaking capacity of your device.
- Source impedance. For a transformer, the tool works Z = U² ÷ S × Z% per phase. It takes the source as all reactance. That gives the highest current for the size.
- Source current. It gives the fault current at the transformer terminals.
- Submain impedance. It reads the resistance and reactance of the submain for your size, length and material. The tables are Table 30 for reactance and Tables 34 and 35 for resistance. It scales the resistance to 20 °C for the maximum figure.
- Protective conductor. It reads the earth conductor size from Table 5.1 of AS/NZS 3000:2018. It adds that resistance to the earth loop.
- Fault currents. It gives the three‑phase current as U0 ÷ |Z|. It also gives the phase-earth current, maximum and with the cable hot.
- Breaking capacity. It compares the three‑phase current with the rating you enter.
| Step | Table or clause | What it decides |
|---|---|---|
| Submain reactance | AS/NZS 3008.1.2 Table 30 | The reactance of the submain |
| Submain resistance | AS/NZS 3008.1.2 Tables 34 and 35 | The resistance of the submain |
| Earth conductor | AS/NZS 3000 Table 5.1 | The size of the protective conductor |
Worked example
- 500 kVA transformer with a 30 m 35 mm² submain. The transformer has 4.5 % impedance. The three‑phase fault current at the board is 10.01 kA. The maximum phase-earth current is 3.18 kA. A 15 kA device passes.
Limits
- The tool works at nominal voltage. It does not apply the IEC 60909 voltage factors.
- It takes the network above the transformer as infinite. A real network lowers the current a little.
- It takes the phase-earth loop at the transformer as its phase impedance, as for a Dyn transformer.
- It does not add motor contribution. It does not grade devices. Use the IDMT tool for grading.
- The result is an estimate for sizing. Ask the network company for the supply fault level at the point of supply.
See also: Prospective fault current at a board, Fault level at a sub‑board on a 300 kVA transformer and Fault rating.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
كيف تحسب أداة مستوى العطل التيار؟
تجمع الأداة المعاوقات لكل طور. يعطي المحوّل U² ÷ S × Z%، وتعطي التغذية الجهد الطوري مقسوماً على مستوى العطل لديها. يضيف المغذّي الفرعي مقاومته ومفاعلته من جداول المعاوقة في AS/NZS 3008.1. والجهد الطوري مقسوماً على المجموع هو تيار عطل الأطوار الثلاثة عند اللوحة.
لماذا توجد قيمتان للطور إلى التأريض؟
تحتفظ الجداول بالمقاومة عند درجة حرارة تشغيل الموصل. الكابل البارد يعطي أعلى تيار، لذلك يحوّل الحد الأقصى المقاومة إلى 20 °C. والرقم الساخن هو الأدنى، ويُستخدم لفحوص زمن الفصل في أداة معاوقة الحلقة.
ما الذي تفترضه الأداة عن المصدر؟
تعامل الأداة المصدر على أنه مفاعلة بالكامل، والشبكة فوق المحوّل على أنها لانهائية. يعطي الاثنان أعلى تيار للقيم التي تدخلها. وتستخدم الجهد الاسمي دون معامل جهد IEC 60909. يحتاج مصدر التغذية إلى Ze عند المنبع للقيم طور-أرض.
ماذا أفعل بالنتيجة؟
قارنه بسعة القطع لقواطع الدائرة في اللوحة. ثم انقله إلى أداة تحمّل العطل، التي تتحقق من قدرة الكابلات على تحمّل العطل خلال زمن الفصل.
أمثلة محلولة
- Starting a loaded conveyorA 22 kW conveyor that needs 120 % torque to break away. Why star-delta and a soft starter will not start it, and what a drive or autotransformer does.
- Fault level at a sub‑board, 300 kVA transformerWork the prospective fault current at a sub‑board 45 m from a 300 kVA transformer, three‑phase and phase-earth, and check 6 kA and 10 kA breakers against it.
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 27 Sept 2026.
أدوات ذات صلة
- حاسبة تحمّل الكابل لتيار العطلCheck that a conductor can withstand the fault current.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000