حاسبة تصحيح معامل القدرة
حدّد قدرة المكثف بوحدة kvar اللازمة لرفع معامل القدرة.
Reads AS/NZS 3000:2018.
جرّب مشروعاً 10
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Correct a factory power factorThe kvar and bank steps to lift a 250 kW load from 0.78 to 0.95.
- Free supply capacity with power factor correctionThe kVA a 400 kVA site gets back when its power factor rises to 0.98.
- Correct a motor boardThe kvar to lift a 75 kW motor load from 0.82 to 0.95.
- Choose the capacitor stepsThe bank in 25 kvar steps for a 300 kVA load.
- Check a bank for resonanceThe bank against the fault level and 20 % harmonic load.
- Correct a single‑phase loadThe kvar for a 15 kW single‑phase load at 0.7.
- Size a capacitor at a motorThe largest capacitor a pump motor can take, and its new line current.
- Correct a small motor at the motorWhy a small motor capacitor stops short of the target power factor.
- Cut the line current of a large motorThe current a capacitor at a large motor takes off its cable and starter.
- Check a motor capacitor for self-excitationThe no-load limit on a capacitor at a small conveyor motor.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- صحيح
- حمل أو لوحة
- الأطوار
- ثلاثي الأطوار
- الجهد
- 400 V
- وحدة الحمل
- kW
- الحمل
- 100
- معامل القدرة الحالي
- 0.75
- معامل القدرة المستهدف
- 0.95
- مرحلة بنك المكثفات
- 25 kvar
- التشوه التوافقي للتيار (THDi)
- 0 %
- مستوى العطل عند البنك
- 0 MVA
التصحيح مطلوب
55.32kvar
- المجموعة المركبة
- 3 × 25kvar
- معامل القدرة مع المجموعة
- 0.991
- التيار قبل
- 192.45A
- التيار بعد
- 145.59A
- السعة المحررة
- 32.47kVA
- موصلات المجموعة، على الأقل
- 146.14A
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- القدرة الفعلية100kW
- القدرة المتفاعلة عند معامل القدرة الحالي88.19kvar
- القدرة المتفاعلة عند معامل القدرة المستهدف32.87kvar
- التصحيح مطلوبالنتيجة55.32kvar
- خطوات المجموعة
3 × 25 kvar
- معامل القدرة مع بنك المكثفات0.99
- التيار قبل192.45A
- التيار بعد145.59A
- السعة المحررة32.47kVA
- التيار المقنن للمجموعة108.25A
- أدنى سعة لموصلات بنك المكثفات، 135 %146.14A
AS/NZS 3000:2018 Cl 4.15.2.3
حول هذه الحاسبة
How this is calculated
The tool finds the capacitor bank that lifts a load to a target power factor. It then gives the current before and after.
- Real power. You enter kW, or kVA with a power factor. The tool finds the real power.
- Reactive power. It finds the reactive power at the present power factor. It does the same at the target.
- Correction required. The difference is the kvar the bank must supply.
- Bank steps. It rounds up to whole steps of the size you enter. It then recalculates the power factor with that bank.
- Currents. It finds the current before and after. The difference is the capacity the bank releases.
- Bank conductors. It sizes the bank conductors at 135 % of the bank rated current. This follows AS/NZS 3000 Cl 4.15.2.3.
AS/NZS 3000 Cl 4.15.2.2 covers switching, and Cl 4.15.3.1 covers discharge.
Worked example
- 100 kW three‑phase load at 400 V, 0.75 to 0.95, 25 kvar steps. The correction required is 55.32 kvar. The bank is 3 × 25 kvar. The power factor with the bank is 0.991. Current falls from 192.45 A to 145.59 A. The released capacity is 32.47 kVA. The bank conductors need at least 146.14 A.
One motor
Set Correct to one motor to size a capacitor fitted at a motor and switched with it. The capacitor must not supply more than the motor's own magnetising kvar. If it does, the motor, still turning after it is switched off, can excite itself from the capacitor and raise its voltage. The tool takes the no-load current as all magnetising and keeps the capacitor to 90 % of the no-load kvar, a rule of practice. It fits the smaller of that and the kvar to reach the target at full load, then gives the line current with it from the motor tool's full load current.
- A 30 kW motor at 0.85 with 17 A no-load current can take 10.6 kvar at most. The 9.7 kvar to reach 0.95 fits, and the line current falls from 56.6 A to 50.64 A.
- An 11 kW motor at 0.8 with 7.5 A no-load current can take 4.68 kvar at most, which lifts it to 0.939 and cuts the line current to 18.79 A. Correct the rest at the board.
- A 55 kW motor at 0.75 with 30 A no-load current can take 18.71 kvar at most, which lifts it to 0.867 and cuts the line current to 101.78 A.
Limits
The tool does not assess harmonics unless you enter the THDi. Switch each step with a device rated for capacitors. The tool does not model resonance with the supply.
See also: Power factor and reactive power, Power factor correction for a 250 kW factory and Three phase power.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ما أكبر مكثف يمكنني تركيبه عند المحرك؟
لا يزيد عن نحو 90 % من kvar عند الحمل الفارغ للمحرك، وهي قاعدة عملية. والأكبر منها قد يجعل المحرك يثير نفسه بعد إيقافه. اضبط الأداة على محرك واحد وأدخل تيار الحمل الفارغ.
كيف يُحسب kvar؟
تحسب الأداة القدرة غير الفعالة عند معامل القدرة الحالي وعند الهدف، كلتيهما من القدرة الفعالة. والفرق هو kvar الذي يجب أن تزوده مجموعة المكثفات. ثم تقرّب إلى أعلى إلى خطوات كاملة للمجموعة.
لماذا ينخفض التيار بعد التصحيح؟
تبقى القدرة الفعالة كما هي، لكن مجموعة المكثفات تزوّد القدرة غير الفعالة في الموقع. لذلك تحمل التغذية قدرة ظاهرية أقل. ينخفض التيار بنسبته، وkVA الذي يحرّره هو السعة المحرّرة.
متى أحتاج إلى بنك مُزاح التردد؟
تسحب المشغّلات والمقوّمات ومشغّلات LED تيارات توافقية. ويمكن للمكثفات العادية أن تدخل في رنين مع التغذية وتضخّمها. كقاعدة عامة، فوق نحو 10 % من THDi، ركّب مجموعة مكثفات مُعدّلة التردد مع مفاعلات على التوالي. وفوق 20 %، احصل على دراسة توافقيات.
ماذا تعني رتبة الرنين؟
تشكّل مجموعة المكثفات والتغذية دائرة مضبوطة. رتبة الرنين هي الجذر التربيعي لمستوى العطل مقسوماً على kvar لمجموعة المكثفات. عند الاقتراب من التوافقية الخامسة أو السابعة أو الحادية عشرة أو الثالثة عشرة، تحذّرك الأداة.
أمثلة محلولة
الخلفية
البنود والجداول التي تقرأها هذه الأداة
أدوات ذات صلة
هل كان هذا مفيداً؟
سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.