منحنى فصل MCB وحد الكابل
ارسم نطاق فصل MCB مقابل الكابل الذي يحميه.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 2 Oct 2026.
جرّب مشروعاً 4
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a breaker clears a long circuitA long lighting run with little fault current against its breaker and cable.
- See a D curve on a motor circuitHow long a D curve breaker can take at a modest fault, against the cable.
- Check a small cable near the boardWhether a high fault current outruns a small cable before the breaker trips.
- Compare a B and C curve breakerThe instant trip current of a Type B breaker on a socket‑outlet circuit.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- نوع القاطع
- المنحنى C
- القيمة الاسمية
- 20 A
- تيار العطل عند الطرف البعيد
- 300 A
- تيار العطل عند اللوحة
- 0 A
- المعيار
- NZ · AS/NZS 3008.1.2
- مقاس الكابل
- 2.5 mm²
- المادة
- النحاس
- العزل
- PVC 75 °C
أقصى زمن فصل عند تيار العطل
0.1s
- تحمل الكابل لتيار العطل
- 0.86s
- فصل فوري، وفق Table 8.1
- 150A
- فصل فوري، النطاق المعتاد
- من 100 إلى 200A
- تيار التشغيل الاصطلاحي
- 29A
- أكبر Zs عند 0.4 s
- 1.53Ω
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- تيار التشغيل الاصطلاحي29A
AS/NZS 3000:2018 Cl 2.5.3.1
- متوسط تيار الفصل، النوع C150A
AS/NZS 3000:2018 Table 8.1
- الإطلاق اللحظي عند المتوسط، بحد أقصى0.1s
AS/NZS 3000:2018 Table 8.1
- أكبر Zs عند 0.4 s1.53Ω
AS/NZS 3000:2018 Table 8.1
- حد الفصل اللحظي النموذجي، الحافة الدنيا100A
- حد الفصل اللحظي النموذجي، الحافة العليا200A
- معامل k×111.00
AS/NZS 3008.1.2:2017 Table 52 p.121
- تحمل الكابل لتيار العطل0.86s
AS/NZS 3008.1.2:2017 Cl 5.3
- أقصى زمن فصل عند تيار العطلالنتيجة0.1s
حول هذه الحاسبة
How this is calculated
A miniature circuit-breaker does not trip at one exact time for a current. Two breakers of the same type and rating trip at different times, so a maker draws a band: the earliest and the latest each can trip. This tool draws that band for a Type B, C or D breaker, draws the cable's limit beside it, and reads the latest trip time at the fault current you enter.
Three figures come from AS/NZS 3000. A breaker operates within its conventional time at 1.45 times its rating. Table 8.1 takes it as tripping instantly, within 0.1 s, at its mean tripping current: 4 times the rating for Type B, 7.5 for Type C and 12.5 for Type D. The largest loop impedance for a 0.4 s disconnection follows from that current. The rest of the band, the edges of the instant region and the thermal part, is a typical band. AmpSize does not hold AS/NZS 60898, and the result says so.
The cable's line is its adiabatic limit: the time it can carry a fault current before its insulation is damaged, from the k factor of AS/NZS 3008.1, through the fault rating tool. The circuit passes when the breaker's latest time is no longer than the cable's time at that current. Check it at the far end, where the fault current is least and the trip slowest, and give the fault current at the board too: there the current is highest, the cable's time shortest, and the worse of the two ends decides.
| Step | Table or clause | What it decides |
|---|---|---|
| Conventional operating current | AS/NZS 3000 Cl 2.5.3.1 | Where the band starts |
| Instant trip at the mean current | AS/NZS 3000 Table 8.1 and Para B4.5 | The current that trips it instantly, and the largest Zs |
| Instant region and thermal edges | A typical band, not a standard | The earliest and latest trip at each current |
| The cable's limit | AS/NZS 3008.1 Table 52 and Cl 5.3 | The time the cable withstands the fault |
| The check | The latest trip against the cable's time | Whether the breaker clears the fault first |
Worked examples
- A C20 lighting circuit in 2.5 mm² with a 300 A fault trips in 0.1 s at the latest, well inside the cable's 0.86 s. The Table 8.1 instant trip current is 150 A.
- A B20 circuit in 2.5 mm² with a 150 A fault trips in 0.1 s against the cable's 3.42 s. The Table 8.1 instant trip current is 80 A.
- A D32 motor circuit in 6 mm² with a 500 A fault can take up to 1.6 s on the slow edge of the band, just inside the cable's 1.77 s. Table 8.1 counts it as instant above 400 A.
- A long B16 circuit in 1.5 mm² with only 60 A of fault current fails: the breaker can take 27.74 s, longer than the cable's 7.7 s, and 60 A is under the Table 8.1 instant trip current of 64 A.
- The same C20 circuit with 3000 A of fault at the board fails at the board: the band shows 0.1 s there, and the cable lasts 0.01 s at 3000 A, though it takes 0.86 s at the far end's 300 A. The maker's let-through energy decides it.
- A C32 circuit in 4 mm² close to the board, 2000 A of fault fails on the band: it shows 0.1 s, and the cable lasts 0.05 s. The maker's let-through energy decides it.
Limits
The band is typical, not a maker's curve. A real breaker clears a large fault in much less than 0.1 s, and limits the energy it lets through; the maker publishes that energy as I²t. Where the band fails a cable at a high current, compare the maker's I²t with k²S² before you change the cable.
gG fuses are not drawn yet. Their curves are in IEC 60269, which AmpSize does not hold.
See also: Loop impedance, Fault rating and IDMT protection.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ما الفرق بين قاطع MCB من المنحنى B والمنحنى C والمنحنى D؟
ما التيار الذي يجعله يفصل فوراً؟ يأخذ AS/NZS 3000 Table 8.1 المتوسط بقيمة 4 أضعاف القيمة الاسمية للنوع B، و7.5 للنوع C، و12.5 للنوع D. ويتحمّل النوع الأعلى تيارات بدء المحركات والمحوّلات دون أن يفصل.
لماذا يُرسم منحنى الفصل كنطاق؟
يفصل قاطعان من النوع والقيمة الاسمية نفسهما في أزمنة مختلفة. يرسم الصانع أبكر وأحدث زمن يمكن أن يفصل فيه كل منهما. تقرأ الأداة أحدث زمن، لذلك يظل الفحص صالحاً للقاطع الأبطأ.
كيف أعرف أن القاطع يحمي الكابل عند العطل؟
يستطيع الكابل تحمّل تيار العطل لزمن يحدده معامل k ومقاسه، (k × S ÷ I)². يجب أن يفصل قاطع الدائرة خلال ذلك الزمن. تقارن الأداة بين الاثنين عند تيار العطل الذي تدخله.
هل النطاق هو منحنى الصانع؟
لا. تأتي نقاط التشغيل من AS/NZS 3000، وحدود النطاق نموذجية للنوع. لا تحتفظ AmpSize بـ AS/NZS 60898. تحقّق من نتيجة قريبة على منحنى الشركة الصانعة.
ماذا لو كان زمن العطل أقل من 0.1 s؟
قرب اللوحة يكون تيار العطل مرتفعًا، ويصمد الكابل الصغير بضع ميلي ثوانٍ فقط. يفصل القاطع العطل الكبير أسرع من 0.1 s. قارن طاقة النفاذ للشركة الصانعة، I²t، مع k²S².
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 2.5.3.1Operating points of circuit-breakers and fuses
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 52Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.2:2017 Table 52, 53, 54, 55Short-circuit K values and temperature limits
- AS/NZS 3008.1.1:2017 Table 52Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.1:2017 Table 52, 53, 54, 55Short-circuit K values and temperature limits
- AS/NZS 3008.1.1:2025 Table 5.1Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.1:2025 Table 5.1, 5.2, 5.3, 5.4Short-circuit K values and temperature limits
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 2 Oct 2026.
أدوات ذات صلة
- حاسبة معاوقة حلقة عطل التأريضCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- تيار اندفاع المحوّل وقاطعهCheck a transformer’s switch-on inrush against its breaker.AS/NZS 3000
- حاسبة تحمّل الكابل لتيار العطلCheck that a conductor can withstand the fault current.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
هل كان هذا مفيداً؟
سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.