Voltage rise for a 5 kW solar inverter cable

حاسبة ارتفاع الجهد

+3 references

Worked to AS/NZS 3000:2018, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 4777.1:2016. Tables checked 27 Sept 2026.

Solar panels on the roof of a weatherboard house, with the inverter mounted on the wall below.

An inverter pushes current towards the point of supply. The cable between the inverter and the switchboard carries that current. The voltage at the inverter therefore sits above the voltage at the board. That difference is the voltage rise.

The inputs

A 5 kW single‑phase inverter in a detached garage.

  • Phases: 1, supply 230 V
  • Inverter output: 5 kW
  • Power factor: 1
  • Run length: 40 m
  • Conductor: 10 mm² copper, PVC, one cable
  • Rise limit: 2 %

The clause and the tables

Cl 3.6.2 Note 3 of AS/NZS 3000:2018 refers voltage rise to AS/NZS 4777.1. AmpSize does not hold AS/NZS 4777.1, so the 2 % limit is the tool's assumption and an input you can change. The tool works the rise at the rated current of the inverter. Check the current edition of AS/NZS 4777.1 for the limit and the clause that apply to the installation.

The impedance data is the same data the voltage drop tool uses. Reactance comes from Table 30 of AS/NZS 3008.1.2:2017 and a.c. resistance from Tables 34 and 35. Cl 4.5 sets how the two combine into one millivolt per amp metre figure.

The steps

The tool first converts the inverter rating into a current. 5 kW at 230 V and a power factor of 1 gives an output current of 21.74 A.

It then reads the conductor data. The resistance of 10 mm² copper is 2.23 Ω/km. Combined at a power factor of 1, the cable gives 4.46 mV/A·m.

A 21.74 A circuit over 40 m on 10 mm²Supply230 VDevice21.74 A40 m10 mm² CuLoad21.74 A
A 21.74 A circuit over 40 m on 10 mm²

4.46 mV multiplied by 21.74 A and by 40 m gives a rise of 3.88 V. Against 230 V that is 1.69 %.

The result

  • Voltage rise: 1.69 %
  • Inverter current: 21.74 A
  • Rise in volts: 3.88 V
  • Maximum length at the limit: 47.44 m

The result sits under the 2 % input, and the tool marks it a pass. It also raises a warning, because 1.69 % is close to the limit. The maximum length figure explains why. This cable reaches 47.44 m before the rise meets 2 %, and the run is already 40 m.

That leaves little margin for a route change. A deviation around a wall or a longer drop into the board adds route length. A later move of the inverter can take the run past 47.44 m.

The next size up answers that. On 16 mm² the same run gives a rise of 1.06 % and 2.43 V. The maximum length goes to 75.57 m.

Power factor changes the answer too. This example uses 1, which is the usual inverter case. An inverter set to absorb or supply reactive power draws more current for the same kilowatts.

At a power factor of 0.9 the same inverter draws 24.15 A. The rise becomes 1.72 % and the maximum length falls to 46.53 m.

The network voltage sits underneath

The rise adds to whatever the network already delivers at the point of supply. A site near the top of the supply range has less room for rise than this calculation shows. Measure the voltage at the board before committing to a long inverter run.

This page is a design aid. Verify every value against the current edition of the standard.

See also: AS/NZS 3000 Clause 3.6.2: voltage drop limit, Voltage drop with the mV/A·m method and Voltage drop basics.

جرّبه بهذه المدخلات

عزل كابل
PVC
مادة كابل
Cu
المسارات المتوازية لـ كابل
1
مقاس كابل
10 mm²
خرج العاكس
5 kW
طول المسار
40 m
حد ارتفاع الجهد
2 %
معامل القدرة
1
الأطوار
طور واحد
الجهد
230 V