Solar أدلة
ارتفاع الجهد على كابلات العاكس والمصفوفة، وتحديد مقاس كابل البطارية لعمل شمسي.
- قراءة 5 دقيقةArc flash at a 48 V home batteryClass a 48 V lithium home battery with 6 kA at its terminals by AS/NZS 5139, find its arc flash energy and PPE level, then bring it down with fuses.

- قراءة 2 دقيقةA circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.

- قراءة 3 دقيقةDC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.

- قراءة 3 دقيقةSolar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at -5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.

- قراءة 3 دقيقةWhere can a home battery go? Garage wallsA garage wall that backs onto a bedroom, with a hot water cylinder nearby. See which AS/NZS 5139 location rules fail for a home battery, then fix each one.

- قراءة 5 دقيقة12 V caravan cable: d.c. voltage dropA 12 V caravan feed at 30 A over 6 m, checked on 4, 6 and 10 mm² twin against the 10 % ELV limit, then a 48 V battery-to-inverter run.

- قراءة 4 دقيقةSolar battery size for a family home: 25 kWh a daySize a solar battery for a home that uses 25 kWh a day with an 8 kW array. Usable and nominal kWh, the bank, the inverter, winter solar and where it can go.

- قراءة 3 دقيقة22 kW EV charger amps at 400 V three‑phaseA 22 kW three-phase EV charger draws 31.75 A at 400 V. See the inputs, the clause, the arithmetic and the current that feeds cable sizing and demand.

- قراءة 3 دقيقةOff-grid battery bank autonomy at 48 VA bach load list of 7600 Wh per day at 48 V needs 703.7 Ah of battery for two days of autonomy at 0.5 depth of discharge, worked step by step.

- قراءة 4 دقيقةAS/NZS 3000 Appendix C: conduit space factorWhat the conduit space factor in AS/NZS 3000 Appendix C governs, which tool reads it, and a worked 50 mm conduit that reaches 52.95 % fill against a 40 % limit.

- قراءة 3 دقيقةEV charger cable size for a 7 kW 32 A circuitA 7 kW EV charger on a 32 A dedicated circuit over 30 m needs 6 mm², with 38 A derated capacity, 2.85 percent voltage drop and 0.73 Ω loop impedance.

- قراءة 4 دقيقةAS/NZS 3008.1.2 Tables 22 to 29: deratingWhat the derating tables govern, how ambient and grouping combine into one factor, and a 63 A feeder whose capacity falls to 78.85 A on 35 mm² copper.

- قراءة 3 دقيقةAS/NZS 3008 Table 27 (now 3.44, 3.45): temperatureAS/NZS 3008 Table 27 corrects a cable rating for the air or soil temperature. The 2025 AU part splits it into Tables 3.44 and 3.45 and re-derives the factors.

- قراءة 5 دقيقةDC cable size: 48 V battery and 600 V PV arrayTwo d.c. circuits sized to AS/NZS 3008.1.1:2025, a 48 V battery-to-inverter run that current sizes and a 600 V array feed that voltage drop sizes.

- قراءة 3 دقيقةVoltage rise for a 5 kW solar inverter cableA 5 kW single-phase inverter 40 m from the switchboard on 10 mm² copper, with the rise in volts, the percent and the maximum length the tool returns.

الحاسبات التي تستخدمها هذه الأدلة
- وميض القوس للبطارية وفئتهاDVC للبطارية، وفئة الخطر، وطاقة وميض القوس، ومستوى PPE.
- جدول دوائر لوحة التوزيعأنشئ جدول دوائر للوحة والملصقات التي تحتاجها.
- حاسبة مفتاح عزل PV والتأريضقيّم كابلات مصفوفة PV ومفتاح العزل للتيار المستمر والتأريض.
- حاسبة سلسلة PVالوحدات في كل سلسلة وتيار السلسلة ومفتاح العزل لـ PV.
- أداة فحص موقع البطاريةتحقّق من مكان وضع البطارية المنزلية وفق AS/NZS 5139.
- حاسبة هبوط الجهداحسب هبوط الجهد على مسار الكابل وتحقّق من الحد.
- حاسبة البطارية الشمسيةحدّد مقاس البطارية المنزلية لحمل المساء على الطاقة الشمسية.
- حاسبة تيار الحمل الكاملاحسب تيار الحمل الكامل من القدرة والجهد والطور.
- حاسبة مجموعة البطارياتاحسب سعة مجموعة البطاريات والاستقلالية لحمل معين.
- حاسبة امتلاء الماسورةتحقّق من أن حزمة الكابلات تتسع في الماسورة.
- حاسبة مقاس الكابلاعثر على أصغر مقاس كابل يكون مطابقاً في كل فحص.
- حاسبة مقاس كابل DCحدّد مقاس كابل d.c. حتى 1500 V للتيار وهبوط الجهد.
- حاسبة ارتفاع الجهداحسب ارتفاع الجهد للتوليد الموزّع أو PV.