فحص كابل محرك VSD
تحقّق من كابل محرك VSD: ذروة الجهد والطول والكابل.
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
جرّب مشروعاً 4
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a drive motor leadWhether a pump on a drive needs an output filter for its motor lead.
- Check a long fan lead on a VSDA fan motor far from its drive, against the drive maker limit.
- Size a conveyor drive lead with a filterA long conveyor lead on a sine filter and the current for its cable.
- Check an inverter-rated motor on a driveWhether an inverter-rated motor takes the reflected peak without a filter.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- قدرة المحرك
- 22 kW
- جهد التغذية
- 400 V
- معامل قدرة المحرك
- 0.85
- جهد الذروة المقنن للمحرك
- 1,000 V
- طول توصيل المحرك
- 60 m
- كابل
- محمي بدرع، متماثل
- مرشح الخرج
- لا شيء
- حد توصيل الشركة المصنعة، بدون مرشح
- 100 m
- زمن صعود النبضة
- 0.1 µs
- سرعة النبضة في الكابل
- 150 m/µs
خط توصيل المحرك
غير مطابق
- الذروة عند المحرك، حتى
- 1,131V
- حد الطول الذي يحدده المصنّع
- 100m
- طول الخط الحرج
- 7.5m
- التيار لمقاس الكابل
- 41.51A
- ناقل التيار المستمر للمحرك
- 565.7V
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- التيار لمقاس الكابل41.51A
- ناقل التيار المستمر للمحرك565.7V
- الطول الحرج للتوصيل عند زمن صعود 0.1 µs7.5m
- الذروة عند المحرك، حتى1,131V
- عزل المحرك، الذروة المقننة1,000V
- حد توصيل الشركة المصنعة، بدون مرشح100m
- خط توصيل المحركالنتيجةيفشل
حول هذه الحاسبة
How this is calculated
A variable speed drive does not send a smooth sine wave down the motor lead. It sends fast pulses at the voltage of its d.c. bus, and each pulse can reflect at the motor. On a long enough lead the reflection nearly doubles the voltage at the motor terminals, which can break down the insulation of a motor not rated for it. This tool works that peak, checks the lead against the drive maker's limit, and gives the current to size the cable for.
The bus voltage is the supply voltage times √2. The critical length is how far a pulse travels in half its rise time; on a lead longer than that the reflection is full and the peak at the motor reaches about twice the bus. On a shorter lead the tool scales it down. A dv/dt filter or an output reactor slows the edge but does not end the reflection, so the tool makes no estimate of its own: you enter the peak at the motor from the filter maker's data for your lead, and the result says it is the maker's figure. Only a sine filter brings the peak down to the bus voltage. The peak is compared with the motor maker's rating. The lead is compared with the drive maker's limit, with or without the filter.
The current is the motor tool's full load current. The rise time, the pulse speed, the limits and the motor's rating are makers' data, entered by you, so the result calls them assumptions. AS/NZS 3000 warns of high frequency current on the protective earth, and notes the cable tables are for 50 Hz.
| Step | Table or clause | What it decides |
|---|---|---|
| Cable current | The motor tool | The current for the cable size |
| Bus voltage | Supply voltage times √2 | The height of each pulse |
| Critical length | Pulse speed times half the rise time | Where the reflection becomes full |
| Peak at the motor | Up to twice the bus; the filter maker's figure with a dv/dt filter or reactor; the bus with a sine filter | The voltage the motor sees |
| Lead length | The drive maker's limit | Whether the lead needs a filter |
| Earthing and ratings | AS/NZS 3000 Cl 5.4.8 and Cl 4.12.8 Note 1 | The earth current and the 50 Hz basis |
Worked examples
- A 22 kW pump on a 60 m lead, standard motor fails: the peak can reach 1,131 V against the motor's 1000 V rating. The cable carries 41.51 A.
- The same pump with a dv/dt filter passes if the filter maker gives a peak of 900 V at the motor for 60 m. The tool prints that 900 V as the maker's figure; it is an example, not an estimate.
- The same pump with an inverter-rated motor passes with a peak of up to 1,131 V on a 1600 V rating.
- A 7.5 kW fan on a 150 m lead fails on length: the drive maker allows 100 m with no filter, though the peak of up to 1,131 V is within the motor's rating.
- A 55 kW conveyor on a 250 m lead with a sine filter passes with a peak near 566 V, inside the 300 m limit with the filter.
Limits
The peak is a first estimate from the lead length alone. The real peak depends on the cable's and motor's surge impedance, the switching pattern and the drive's own output stage, which the makers test. The tool does not size the cable for harmonics on the drive's supply side, the cable's capacitive charging current, or bearing currents.
See also: Motor, Motor starting and Cable size.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
لماذا يهم طول كابل المحرك الطويل على VSD؟
يرسل المشغّل نبضات جهد سريعة. على كابل طويل، تنعكس كل نبضة عند المحرك، وقد يكاد الجهد هناك يتضاعف. وقد يؤدي ذلك إلى تلف عزل محرك لم يُصمَّم عزله لتحمّل ذلك.
ما هو طول الكابل الحرج؟
هو المسافة التي تقطعها النبضة في نصف زمن صعودها. وبعدها يكون الانعكاس كاملاً. مع زمن صعود 0.1 µs وسرعة نبضة 150 m/µs تكون 7.5 m، لذلك تتجاوزها معظم كابلات المحرك.
هل أحتاج إلى مرشح dv/dt أو مرشح الجيب (sine)؟
عندما يتجاوز كابل المحرك حد الشركة الصانعة للمشغّل، أو تتجاوز الذروة القيمة الاسمية للمحرك. يبطّئ مرشّح dv/dt أو المفاعل الحافة لكنه يترك بعض التجاوز، لذلك تأخذ الأداة تلك الذروة من بيانات الشركة الصانعة للمرشّح. ويجعل مرشّح الجيب الخرج أقرب ما يكون إلى موجة جيبية.
أي كابل يجب أن يستخدم VSD؟
كابل ذو حجاب معدني ومتماثل، مع ربط الحجاب المعدني من كل الجهات عند طرفيه، كما يذكر صانع المشغّل. حدّد مقاسه وفق تيار المحرك، وتذكّر أن القيم الاسمية لـ AS/NZS 3008.1 مبنية على 50 Hz.
لماذا يمكن أن يسبب VSD صدمة من معدن مؤرض؟
يحذّر AS/NZS 3000 Cl 5.4.8 من أن المشغّل قد يضع تياراً عالي التردد على موصل التأريض الوقائي، مع جهود لمس تصل إلى 100 V. قد لا يُظهره جهاز اختبار 50 Hz. أرضِّ المشغّل كما يذكر صانعه.
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 4.12.8Equipment on a converter output
- AS/NZS 3000:2018 Cl 5.4.8Variable frequency devices
- AS/NZS 3000:2018 Cl 5.4.8 and Cl 4.12.8Variable frequency drives
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 2 Oct 2026.
أدوات ذات صلة
هل كان هذا مفيداً؟
سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.