مدقق مناطق الأماكن الرطبة
حدّد المنطقة وفق Section 6 وتصنيف IP وRCD بالقرب من الماء.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
جرّب مشروعاً 12
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a downlight over a showerWhether an IP20 downlight 0.5 m from a 2.4 m ceiling rose passes.
- Put a socket‑outlet by a basinThe zone and the conditions for a socket‑outlet 0.1 m from a basin.
- Light a spa poolThe zone and IP rating for a light 1 m from a 1500 L spa.
- Put a socket‑outlet beside a bathThe zone and the conditions 0.4 m from a bath.
- Put a switch in a bathroomThe zone for a light switch 0.7 m from a shower.
- Put a socket‑outlet by a kitchen sinkThe zone and the conditions 0.2 m from a sink.
- Light a swimming pool surroundThe zone and IP rating for a light 2 m from a pool.
- Put a socket‑outlet near a poolWhether a socket‑outlet 3 m from a pool passes.
- Fit a light in a saunaThe zone for a luminaire above a sauna heater.
- Light a fountainThe zone and IP rating for a light in a fountain.
- Check a communal shower roomThe IP rating a communal shower asks for.
- Check a bathroom in AustraliaThe zone and IP rating for a light near an open shower, to the Australian rules.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- الحالة
- حوض الاستحمام
- الدولة
- نيوزيلندا
- طول التجهيزة
- 1.6 m
- عرض التجهيزة
- 0.7 m
- ارتفاع نقطة التوصيل أو الوردة
- 0 m
- حمام أو دش مشترك
- لا
- المعدات
- وحدة الإضاءة
- المسافة من وصلة الدُش
- 0 m
- في الماء أو القاعدة (المنطقة 0)
- لا
- المسافة الخارجة
- 0.8 m
- الارتفاع فوق الأرضية
- 2.4 m
- تصنيف IP
- IPX4
- على RCD بتيار 30 mA
- نعم
- الطباعة
- A1 إلى A3 (الحالي)
المنطقة
خارج كل المناطق
- أدنى تصنيف IP
- لا شيء
- مسموح به هنا
- Outside the zones
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- الوضعحوض استحمام
AS/NZS 3000:2018 Cl 6.2.2.1
- المسافة المقاسة منالحافة الداخلية
AS/NZS 3000:2018 Cl 6.2.2.1
- المنطقة 10 m out, up to 2.25 m (Cl 6.2.2.1(b))
AS/NZS 3000:2018 Cl 6.2.2.1
- المنطقة 20.6 m out, up to 2.25 m (Cl 6.2.2.1(d))
AS/NZS 3000:2018 Cl 6.2.2.1
- المنطقة 33 m out, up to 2.25 m (Cl 6.2.2.1(e))
AS/NZS 3000:2018 Cl 6.2.2.1
- موضع الجهاز0.8 m out, 2.4 m up
AS/NZS 3000:2018 Cl 6.2.2.1
- منطقةالنتيجةخارج كل منطقة
AS/NZS 3000:2018 Cl 6.2.2.1
حول هذه الحاسبة
How this is calculated
The tool places a light, switch or socket‑outlet in a zone. It then reads the least IP rating and the RCD rule for that zone. It follows Section 6 of AS/NZS 3000:2018.
- Situation. You pick the fitting: a bath, a shower, a basin, a spa, a pool or a sauna. Each one has its own table of zones.
- Reference point. Each situation measures from its own point. A bath measures from the internal rim. A shower measures from the fixed plumbing connection or the rose.
- Zone limits. The tool lists Zone 1, Zone 2 and Zone 3 (Cl 6.2.2.1). Each has a distance out and a height up.
- Device position. You enter the horizontal distance and the height of the device. The tool finds the first zone that holds that point.
- IP rating. The zone sets the least IP rating (Cl 6.2.4). The tool compares your rating with it.
- RCD and position. The tool adds the RCD rule for a home (Cl 2.6.3.3.1). It also gives the lowest height for a socket‑outlet or switch.
| Step | Table or clause | What it decides |
|---|---|---|
| Zone limits | Cl 6.2.2.1 | The distance and height of each zone |
| IP rating | Cl 6.2.4 | The least IP rating for the zone |
| Walls and fixed barriers | Cl 6.2.1 | Where a zone stops |
| RCD | Cl 2.6.3.3.1 | The 30 mA rule for a home |
| Bonding | Cl 5.6.2.5 | The earth bond of conductive reinforcing |
Worked example
Each link opens the tool with its inputs.
- Luminaire at an open shower. The luminaire sits 0.3 m from the plumbing connection and 1.8 m up. It has an IPX2 rating. The tool puts it in Zone 1 and asks for IPX4 at least. The check fails on the IP rating.
Limits
- The tool does not model a barrier that shrinks a zone. Walls, doors, floors and ceilings also limit the zones. Check the room.
- A shower over a bath adds a radius from the shower connection. You must type that distance.
- Equipment behind a fixed IPX4 panel that needs a tool to open is not in a zone. The tool does not decide this for you.
- A recessed fitting with all live parts above the ceiling is outside the zones below it.
- Protection by obstacles or by placing out of reach is not allowed in these zones.
- The tool points at the clause. It is not a ruling on a design.
See also: Wire a bathroom: zones, IP and the RCD, Damp situations and the Section 6 zones and RCD selection.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
إلى أي ارتفاع تمتد المنطقة 1 في NZ وفي أستراليا؟
تمتد المنطقة 1 فوق الحوض أو الدش إلى 2.25 m فوق الأرضية في نيوزيلندا و2.5 m في أستراليا. وترتفع حتى وصلة الدش حيث تكون أعلى. تنتهي المنطقة 2 عند 2.25 m في البلدين. وتأخذ المنطقة 3 الأسترالية أيضًا المساحة فوق المنطقة 2، حتى 2.5 m.
هل يمكن وضع مقبس في الحمام؟
ليس في المنطقة 0 أو المنطقة 1. في المنطقة 2 يجب أن يكون وحدة تغذية للحلاقة، أو مقبسًا على RCD بقيمة 30 mA داخل خزانة. في المنطقة 3 يحتاج إلى RCD بقيمة 30 mA أو دائرة معزولة أو SELV. أبقِ كل مقبس وكل مفتاح على ارتفاع 0.3 m أو أكثر فوق الأرضية.
ما تصنيف IP الذي تحتاجه إضاءة غاطسة فوق الدش؟
IPX4 في المنطقة 1 أو المنطقة 2. يعطي مركّب السقف منطقة 1 بطول 1.2 m في NZ و0.6 m في أستراليا، حتى ارتفاع المركّب. وتقع الإضاءة الغاطسة التي تكون كل أجزائها الحية فوق السقف خارج المنطقة الواقعة تحتها.
هل يغطي IPX7 منطقة تشترط IPX5؟
لا. الرقم الثاني حتى 6 يشمل كل رقم أدنى منه، لكن 7 أو 8 وحدهما لا يشملان نفاثات الماء (AS 60529 Cl 6). تطلب المنطقة 1 للمسبح IPX5، لذلك ابحث عن ترميز مزدوج مثل IPX5/IPX7.
لماذا يتغير حوض السبا عند 680 L و5000 L؟
تُطبَّق على السبا حتى 680 L مناطق الحمام والدش. من 680 L إلى 5000 L، تمتد المنطقة 1 مسافة 1.25 m من الحافة، حتى 2.5 m. فوق 5000 L، أو عند ربطه بحوض سباحة، تُطبَّق على السبا مناطق المسبح.
في المخطط
أمثلة محلولة
- IP ratings for an outdoor point and a hosed shedWhich IP code an outdoor power point, a milking shed light and a hosed switchboard need, and why an IP67 light can fail where IP65 passes.
- Kitchen power points and the cooktop zonePlace power points and switches near a cooktop, an outdoor gas bottle and a gas vent. Check each distance to AS/NZS 3000 and hand the sink to the wet area tool.
- Wire a bathroom: zones, IP ratings and the RCDA New Zealand bathroom with a 1.6 m bath and an open shower, worked through the AS/NZS 3000 Section 6 zones, the IP each item needs, the RCD and bonding.
الخلفية
- IP ratings explained: each digit and letterWhat the two numerals of an IP code mean, what X, the letters A to D and H, M, S, W add, why IP67 is not better than IP65 for jets, and where 3000 sets a code.
- Power points near a cooktop, gas bottle and sinkThe AS/NZS 3000 zones that keep power points, switches and lights away from cooktops, gas cylinders, gas vents and regulators, and where sinks are checked.
- Damp situations: the Section 6 zonesHow AS/NZS 3000 Section 6 zones the space around baths, showers, basins, spas, pools, fountains and saunas, how to read an IP code, and what A2 changed.
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 2.6.3.2.2AU domestic RCD circuits
- AS/NZS 3000:2018 Cl 2.6.3.3.1NZ residential RCD circuits
- AS/NZS 3000:2018 Cl 5.6.2.5Bonding in showers and bathrooms
- AS/NZS 3000:2018 Cl 5.6.2.6Bonding at swimming and spa pools
- AS/NZS 3000:2018 Cl 5.6.3.2Size of the wet area bonding conductor
- AS/NZS 3000:2018 Cl 6.2.1Limits of the bath and shower zones
- AS/NZS 3000:2018 Cl 6.2.2.1Zones for baths and showers
- AS/NZS 3000:2018 Cl 6.2.2.2Zones for basins, sinks and tubs
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.