Whakawhiti ki te ihirangi
AmpSize

Arc flash me te karaehe pākahiko

DVC pākahiko, karaehe mōrearea, pūngao arc flash me te taumata PPE.

Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Matū
Lithium ion
Kua whakakōtuia ki te Best Practice Guide, ētahi kēhi rānei kua whakatauhia ki V0
Kāo
Hiko pātene, d.c. teitei rawa
51.2 V
Ia hapa whakatakai i te mahi
6 kA
Wā ūkui
2 s
Tawhiti mahi
45 cm
Whare
Takotoranga pātene, kabineti rānei (tauutu 3)
Wāhi
I roto, i te kāinga rānei

Incident energy arc flash

4.55cal/cm²

Taumata PPE
Taumata 2
Te taumahatanga o te pānga
Waenga
Rohe arc flash
876mm
Karaehe voltage whakatau
A
Te taumahatanga o te whakararu ahi
Taumata 1

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Te karaehe voltage whakatauA

    AS/NZS 5139:2019 Table 3.2

  2. Te taumahatanga o te whakararu ahiTaumata 1

    AS/NZS 5139:2019 Table 3.1

  3. Mōrearea kua ingoatiaHiko, pūngao, ngāwari, hau pahū me te paoa paitini

    AS/NZS 5139:2019 Table 3.1

  4. Ia ūkui, te haurua o te ia hapa whakatakai3kA

    AS/NZS 5139:2019 Eq 3.2.4(2)

  5. Tauwehe whakarea3

    AS/NZS 5139:2019 Cl 3.2.4.3

  6. Te kaha o te arc flashHua4.55cal/cm²

    AS/NZS 5139:2019 Eq 3.2.4(1)

  7. Rohe pāhū ūkui876mm

    AS/NZS 5139:2019 Eq F.4

  8. Te taumahatanga PPETaumata 2

    AS/NZS 5139:2019 Table 3.3

  9. Te taumahatanga o te pāngaWaenga

    AS/NZS 5139:2019 Table 6.1

Mō tēnei tātaitai

How this is calculated

AS/NZS 5139 asks for a battery system to be classed before it is installed: which hazards its chemistry carries, which voltage class it is in, and how much energy an arc at its terminals would release. This tool works all three from a few inputs and reads the tables that follow from them.

The hazards and the fire hazard level come from the chemistry. Lithium ion is fire hazard level 1, lead acid and nickel alkaline level 2. A note to the table lifts the level for pre-assembled lithium equipment that meets the industry Best Practice Guide, and for lead acid or nickel alkaline in cases rated V0. The decisive voltage class comes from the battery's highest d.c. voltage.

The arc flash energy uses the standard's equation. It multiplies the battery voltage, the arcing current, the arcing time divided by the working distance squared, and a factor for where the arc is: at least 3 in an enclosure and 1.5 in a room. The arcing current is half the bolted fault current. The working distance is 45 cm at most. The arcing time is 2 s where the protective device's time is not known, or where the work is on its battery side. The boundary is the distance where the energy falls to 1.2 cal/cm². The appendix tables are this equation at 45 cm and a factor of 3, and a test runs every printed row through it.

The energy then sets the PPE level, the consequence level for the risk assessment, and, in a home or outside one, the limits on where the system may go.

StepTable or clauseWhat it decides
Hazards and fire hazard levelAS/NZS 5139 Table 3.1What the chemistry carries
Decisive voltage classAS/NZS 5139 Table 3.2DVC-A, B or C from the d.c. voltage
Arcing current and energyAS/NZS 5139 Cl 3.2.4The incident energy at the working distance
Arc flash boundaryAS/NZS 5139 Equation F.4Where the energy falls to the boundary level
PPE levelAS/NZS 5139 Table 3.3The arc-rated clothing level
Consequence levelAS/NZS 5139 Table 6.1The consequence for the risk assessment
Home and outdoor limitsAS/NZS 5139 Cl 6.3.2.3Where the system may go at that energy

Worked examples

Limits

The tool works the energy at one point with one arcing time. It does not find the bolted fault current, which comes from the battery maker or the home battery tool, or a fuse's clearing time at that current, which comes from its curve. It does not grade the likelihood side of the risk matrix.

The tool reads the 2019 edition as published. Amendment 1 (2025) is not on hand, so check any change it makes before relying on a figure.

See also: Home battery, Arc flash and Battery.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

Me pēhea te tātai i te pūngao arc flash o te pākahiko?

Ka whakareatia e AS/NZS 5139 Cl 3.2.4 te voltage pākahiko, te iahiko arcing, te wā arcing ki runga i te tawhiti mahi tapawhā, me tētahi tauwehe mō te kōpaki. Ko te iahiko arcing te haurua o te iahiko hapa bolted.

He aha te wā arcing me whakamahia e au?

Whakamahia te 2 s ina kore e mōhiotia te wā mahi o te taputapu whakamaru, ina mahi rānei ki te taha pākahiko o taua taputapu. Ki tērā taha, whakamahia te wā o te taputapu i taua iahiko hapa. Ka whakaiti te fuse i waenga i ngā strings i te wā me te pūngao.

He aha te karaehe voltage whakatau o tētahi pākahiko?

Ka whakarōpū a AS/NZS 5139 Table 3.2 i tētahi pākahiko d.c. hei DVC-A tae atu ki te 60 V, DVC-B tae atu ki te 120 V, ā, DVC-C ki runga ake. Ko tētahi pūnaha DVC-B, DVC-C rānei he whakaurunga voltage iti i raro i AS/NZS 3000.

Ka taea e tētahi pākahiko kāinga te neke atu i te 4 cal/cm²?

Āe, i raro i te 40 cal/cm². Ina neke atu i te 4, me tuku ki tētahi rūma motuhake, ki tētahi enclosure rānei kāore i piri ki tētahi whare me ngā rūma noho, kua tutuki rānei te fire hazard level 1, ā, kāore i roto, kāore rānei i te taha o taua whare. Ka taea e te whakamaru inter-string te whakaiti i tērā.

Ko tēhea taumata PPE e hiahiatia ana e au?

Ka whakatau a AS/NZS 5139 Table 3.3 i te taumata PPE e ai ki te pūngao: taumata 1 tae atu ki te 4 cal/cm², taumata 2 tae atu ki te 8, taumata 3 tae atu ki te 25, me taumata 4 tae atu ki te 40. Ki runga ake i te 40 kāore he taumata PPE e pā ana.

Ngā tauira mahi

Kōrero o muri

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.