Tātaitai demand horahanga papa

Tātaungia te demand pakihi mai i te horahanga papa me te whakamahinga.

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Ngā wāhanga
Wāhanga toru
Voltage wāhanga
230 V
Tauira mai i te ripanga
Te toharite tā
Rohe
2 rārangi
Taputapu motuhake
0 kVA

Whakahiato nui rawa mō ia wae

217.39A

Whakahiato katoa
150kVA
Offices · Light and power
75kVA
Offices · Airconditioning, zonal reheat
75kVA

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Tau i tangohia i Table C3Toharite i tāngia

    AS/NZS 3000:2018 Table C3

  2. Offices · Light and power, whakahiato pūngao50VA/m²

    AS/NZS 3000:2018 Table C3

  3. Offices · Light and power, 1500 m²75kVA

    AS/NZS 3000:2018 Table C3

  4. Offices · Airconditioning, zonal reheat, whakahiato pūngao50VA/m²

    AS/NZS 3000:2018 Table C3

  5. Offices · Airconditioning, zonal reheat, 1500 m²75kVA

    AS/NZS 3000:2018 Table C3

  6. Tono katoa150kVA

    AS/NZS 3000:2018 App C Para C2.4.3

  7. Au mō ia wae, kVA ÷ (3 × voltage wae)Hua217.39A

    AS/NZS 3000:2018 App C Para C2.4.3

Mō tēnei tātaitai

How this is calculated

The tool estimates the maximum demand of a commercial or light-industrial building from its floor area. It uses the energy demand method in AS/NZS 3000:2018 App C Para C2.4.3. It reads the VA per square metre from Table C3.

  1. Pick the figure. For each area, choose an occupancy and a use. The tool takes the printed average, or the low or high end of the printed range (Table C3). You can type your own figure instead.
  2. Work out each area. The tool multiplies the area by the VA per square metre and divides by 1000. The result is kVA.
  3. Add EV charging. The NOTE to Table C3 puts EV charging on top of all other energy demands. The tool adds the carpark EV rows to the total.
  4. Add special equipment. Table C3 prints no figure for it. You enter its kVA from the load details, and the tool adds it.
  5. Total demand. The tool adds every area and the special equipment (Para C2.4.3).
  6. Current. On one phase, the tool divides the kVA by the phase voltage. On three phases, it divides by 3 times the phase voltage. That gives the current in each phase.
StepTable or clauseWhat it decides
Figure per areaTable C3The VA per square metre for each use
EV chargingNOTE to Table C3The charging load added on top
Total demandApp C Para C2.4.3The sum of the areas and special equipment
CurrentApp C Para C2.4.3The demand in amps on each phase

Worked example

  • Small retail and office building with basement EV charging. Shops of 600 m² at 70 VA/m² for light and power and 30 VA/m² for air conditioning. Offices of 400 m² at 50 and 25 VA/m². A basement carpark of 300 m² at 15 VA/m², plus its EV charging at 20 VA/m². The total demand is 100.5 kVA. The current is 145.65 A per phase at 230 V.
  • The Paragraph C2.4.3.2 case. 1500 m² of office at 50 + 50 VA/m². The total demand is 150 kVA. The current is 217.39 A per phase.

Limits

  • Table C3 is for commercial and light-industrial buildings. It is not for homes. Use Table C1 for a home.
  • The figures depend on the climate, the hours of use, energy management and how evenly the load spreads.
  • The per phase figure assumes an even spread over three phases. Check the heaviest phase where the load is uneven.
  • The tool uses the phase voltage. On a 230/400 V supply, enter 230.
  • Special equipment has no printed figure. You must know its kVA. The tool does not guess it.
  • An own figure outside the printed range gives a warning. Check it before you rely on it.
  • To work from a list of loads, use the Table C2 method in the Maximum Demand tool.

See also: The energy demand method and Table C3, Shop and office maximum demand by floor area and the Maximum Demand tool.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

Āhea au e whakamahi ai i Table C3 hei utu mō Table C2?

He pai a Table C3 mō tētahi whare arumoni, ahumahi māmā rānei i te wāhanga hoahoa moata, ina mōhio koe ki te horahanga papa me te whakamahinga, engari kāore ngā uta. Me ngā rōpū uta e hiahia ana a Table C2. Ina mōhio ki ngā uta, tirohia te demand mā Table C2.

Ko tēhea uara me tango i te awhe?

Ka tuwhera te taputapu ki te toharite kua tā. Ko te paerewa e kī ana ka whakawhirinaki ngā tauāhua ki te āhuarangi, ngā hāora, te whakahaere pūngao, me te horapa ōrite o te uta. Tangohia te pae teitei mō te āhuarangi wera, mō ngā hāora roa, kōwhiria rānei tōu ake tauāhua.

Me pēhea te huri a te taputapu i te kVA ki ngā amps?

Ka wehea te VA katoa ki te voltage wāhanga. Ki ngā wāhanga toru ka wehea ki te toru ngā wā o te voltage wāhanga, nō reira he 150 kVA i te 230 V ka hoatu 217.39 A ia wāhanga. Ka rite tēnei ki te tauira i Paragraph C2.4.3.2.

Kei roto te EV charging i te tatauranga wāhi tūtaka?

Kāo. Kei Table C3 te EV charging hei rārangi motuhake i raro i ngā wāhi tūtaka o waho me ngā wāhi tūtaka o raro, ā, ko tāna NOTE e tāpiri ana ki te demand katoa atu. Tāpirihia he wāhi EV charging ki te taha o te wāhi tūtaka.

He aha mō ngā taputapu motuhake i tētahi whare penapena, i tētahi wāhi mahi rānei?

Kāore he tatauranga a Table C3 mō ngā taputapu motuhake. Tātaihia mai i ngā kōrero uta, ā, uruhia ki te kVA. Ka tāpirihia e te taputapu ki te katoa.

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.