Tātaitai demand horahanga papa
Tātaungia te demand pakihi mai i te horahanga papa me te whakamahinga.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Estimate demand for a shop by floor areaThe demand of a 600 m² shop with airconditioning, from Table C3.
- Estimate demand for a warehouseA 3000 m² warehouse with ventilation and 40 kVA of special equipment.
- Estimate demand for a basement carparkA 4000 m² basement carpark with EV charging on a quarter of it.
- Estimate demand for an office floorAn 800 m² office with reverse cycle air, at the top of the range.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Ngā wāhanga
- Wāhanga toru
- Voltage wāhanga
- 230 V
- Tauira mai i te ripanga
- Te toharite tā
- Rohe
- 2 rārangi
- Taputapu motuhake
- 0 kVA
Whakahiato nui rawa mō ia wae
217.39A
- Whakahiato katoa
- 150kVA
- Offices · Light and power
- 75kVA
- Offices · Airconditioning, zonal reheat
- 75kVA
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Tau i tangohia i Table C3Toharite i tāngia
AS/NZS 3000:2018 Table C3
- Offices · Light and power, whakahiato pūngao50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Light and power, 1500 m²75kVA
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat, whakahiato pūngao50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat, 1500 m²75kVA
AS/NZS 3000:2018 Table C3
- Tono katoa150kVA
AS/NZS 3000:2018 App C Para C2.4.3
- Au mō ia wae, kVA ÷ (3 × voltage wae)Hua217.39A
AS/NZS 3000:2018 App C Para C2.4.3
Mō tēnei tātaitai
How this is calculated
The tool estimates the maximum demand of a commercial or light-industrial building from its floor area. It uses the energy demand method in AS/NZS 3000:2018 App C Para C2.4.3. It reads the VA per square metre from Table C3.
- Pick the figure. For each area, choose an occupancy and a use. The tool takes the printed average, or the low or high end of the printed range (Table C3). You can type your own figure instead.
- Work out each area. The tool multiplies the area by the VA per square metre and divides by 1000. The result is kVA.
- Add EV charging. The NOTE to Table C3 puts EV charging on top of all other energy demands. The tool adds the carpark EV rows to the total.
- Add special equipment. Table C3 prints no figure for it. You enter its kVA from the load details, and the tool adds it.
- Total demand. The tool adds every area and the special equipment (Para C2.4.3).
- Current. On one phase, the tool divides the kVA by the phase voltage. On three phases, it divides by 3 times the phase voltage. That gives the current in each phase.
| Step | Table or clause | What it decides |
|---|---|---|
| Figure per area | Table C3 | The VA per square metre for each use |
| EV charging | NOTE to Table C3 | The charging load added on top |
| Total demand | App C Para C2.4.3 | The sum of the areas and special equipment |
| Current | App C Para C2.4.3 | The demand in amps on each phase |
Worked example
- Small retail and office building with basement EV charging. Shops of 600 m² at 70 VA/m² for light and power and 30 VA/m² for air conditioning. Offices of 400 m² at 50 and 25 VA/m². A basement carpark of 300 m² at 15 VA/m², plus its EV charging at 20 VA/m². The total demand is 100.5 kVA. The current is 145.65 A per phase at 230 V.
- The Paragraph C2.4.3.2 case. 1500 m² of office at 50 + 50 VA/m². The total demand is 150 kVA. The current is 217.39 A per phase.
Limits
- Table C3 is for commercial and light-industrial buildings. It is not for homes. Use Table C1 for a home.
- The figures depend on the climate, the hours of use, energy management and how evenly the load spreads.
- The per phase figure assumes an even spread over three phases. Check the heaviest phase where the load is uneven.
- The tool uses the phase voltage. On a 230/400 V supply, enter 230.
- Special equipment has no printed figure. You must know its kVA. The tool does not guess it.
- An own figure outside the printed range gives a warning. Check it before you rely on it.
- To work from a list of loads, use the Table C2 method in the Maximum Demand tool.
See also: The energy demand method and Table C3, Shop and office maximum demand by floor area and the Maximum Demand tool.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
Āhea au e whakamahi ai i Table C3 hei utu mō Table C2?
He pai a Table C3 mō tētahi whare arumoni, ahumahi māmā rānei i te wāhanga hoahoa moata, ina mōhio koe ki te horahanga papa me te whakamahinga, engari kāore ngā uta. Me ngā rōpū uta e hiahia ana a Table C2. Ina mōhio ki ngā uta, tirohia te demand mā Table C2.
Ko tēhea uara me tango i te awhe?
Ka tuwhera te taputapu ki te toharite kua tā. Ko te paerewa e kī ana ka whakawhirinaki ngā tauāhua ki te āhuarangi, ngā hāora, te whakahaere pūngao, me te horapa ōrite o te uta. Tangohia te pae teitei mō te āhuarangi wera, mō ngā hāora roa, kōwhiria rānei tōu ake tauāhua.
Me pēhea te huri a te taputapu i te kVA ki ngā amps?
Ka wehea te VA katoa ki te voltage wāhanga. Ki ngā wāhanga toru ka wehea ki te toru ngā wā o te voltage wāhanga, nō reira he 150 kVA i te 230 V ka hoatu 217.39 A ia wāhanga. Ka rite tēnei ki te tauira i Paragraph C2.4.3.2.
Kei roto te EV charging i te tatauranga wāhi tūtaka?
Kāo. Kei Table C3 te EV charging hei rārangi motuhake i raro i ngā wāhi tūtaka o waho me ngā wāhi tūtaka o raro, ā, ko tāna NOTE e tāpiri ana ki te demand katoa atu. Tāpirihia he wāhi EV charging ki te taha o te wāhi tūtaka.
He aha mō ngā taputapu motuhake i tētahi whare penapena, i tētahi wāhi mahi rānei?
Kāore he tatauranga a Table C3 mō ngā taputapu motuhake. Tātaihia mai i ngā kōrero uta, ā, uruhia ki te kVA. Ka tāpirihia e te taputapu ki te katoa.
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 App C Para C2.4.3Energy demand method for commercial installations
- AS/NZS 3000:2018 Table C3Maximum demand, energy demand method for non‑domestic installations
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 1 Oct 2026.
Ngā taputapu hononga
- Tātaitai Maximum DemandEstimate maximum demand for domestic or non‑domestic loads.AS/NZS 3000 Table C1/C2
- Tātaitai maximum demand ia wāhangaSpread the load over three phases and see the imbalance.AS/NZS 3000
- Tātaitai kaha e toe anaSee if a new load fits the main switch of a supply.AS/NZS 3000 Cl 2.2.2