+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Rahi kaikawe

1.5mm²

Kaha kua whakaiti
16A
Heke voltage
4.3%
Kaikawe whenua
1.5mm²
Whakatuwhera te tātaitai me ēnei whakauru

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

A drawn result card from the Cable Size tool: conductor size 1.5 mm²; voltage drop checked.

A lighting circuit on a 10 A breaker in New Zealand takes 1.5 mm² copper cable on a typical route. For 30 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 16 A of derated capacity and a voltage drop of 4.3 %.

The case

The circuit is single‑phase at 230 V. The design current is the full 10 A of the curve C breaker. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 1.5 mm² earth, and the earth fault loop impedance is 1.34 Ω.

Voltage drop is the check closest to its limit. A longer run reaches the limit before the cable runs out of capacity.

What changes the answer

A 16 A lighting circuit on the same route takes 2.5 mm² with a drop of 3.76 %.

See also: How far can 1.5 mm² run on a 10 A circuit? and Voltage drop basics.

Whakamātau ki ēnei whakauru

Pāmahana taiao
30 °C
Ngā matua
Multicore
Kauwhata taputapu
Kauwhata C
Tirohia te taputapu tiaki
Āe
Ngā ara iahiko whakarōpū
1
Insulation
PVC 75 °C
Roa rerenga
30 m
Iahiko hoahoa
10 A
Rauemi
Parahi
Tikanga whakaurunga
Enclosed in air
Power factor
1
Ngā wāhanga
Wāhanga kotahi
Reiti taputapu
10 A
Rohe heke voltage
5 %
Voltage
230 V
Impedance waho Ze
0.35 Ω