AmpSize

Voltage unbalance o tētahi puna hiko

Te unbalance o te voltage, o te iahiko rānei mai i ngā pānui rārangi e toru.

Kāore he paerewa

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Ngā ine
Ngā uara raina
Whakahiato A ki B
405 V
Whakahiato B ki C
398 V
Whakahiato C ki A
411 V

Te rerekē o te kore taurite

1.65%

Te kore taurite o te raupapa
1.86%
Te toharite o ngā tokotoru
404.67V
Te rerekētanga nui rawa mai i te toharite
6.67V
Te pikinga o te whakatipu pāmahana o te wiri, ā-ture matua
5.4%

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Te toharite o ngā tokotoru404.67V
  2. Te rerekētanga nui rawa mai i te toharite6.67V
  3. Whakamāramatanga whakamate: 100 × 6.67 ÷ 404.67Hua1.65%
  4. Whakamāramatanga raupapa: 100 × raupapa negative ÷ raupapa positive, mai i ngā rahi e toru1.86%
  5. Wera mōtā: 2 × 1.65²5.4%

Mō tēnei tātaitai

How this is calculated

A three‑phase supply is balanced when its three line voltages are equal and 120° apart. Long rural lines, single‑phase loads spread unevenly and a failing connection all pull the three apart. The tool puts a number on how far apart they are, in the two ways the trade uses.

The deviation definition is the simple one. The tool takes the mean of the three readings and finds the reading furthest from it. The unbalance is that deviation over the mean, as a percent. This is the definition NEMA uses for motors.

The sequence definition comes from symmetrical components. Any three phasors split into a positive sequence, which turns a motor forward, and a negative sequence, which turns against it. The unbalance is the negative sequence over the positive sequence, as a percent. This is the IEC definition. The tool works it from the three magnitudes alone, with a closed formula that holds for line-to-line voltages. For a small unbalance the two definitions are close.

For voltages the tool also gives a motor heating figure. A widely published rule of thumb puts the percent increase in the winding temperature rise at twice the square of the percent unbalance. It is an estimate, not a standard's curve. AmpSize holds no standard for unbalance, so the tool cites none.

The same sums work on three line currents. Current unbalance is often several times the voltage unbalance behind it.

StepTable or clauseWhat it decides
MeanThe sum of the three readings over threeThe reference the deviation is taken from
Deviation definitionLargest deviation over the meanThe NEMA style unbalance
Sequence definitionNegative over positive sequence, from the magnitudesThe IEC style unbalance
Motor heatingTwice the square of the unbalanceA rule of thumb for the increase in the winding temperature rise
A reading that cannot closeOne reading larger than the other two togetherNo sequence figure, check the readings

Worked examples

Limits

The tool takes three readings at one moment. A supply that swings through the day needs readings at its worst hour, or a logger.

It does not give a motor's rating at an unbalance. That curve is in NEMA MG 1 and in the maker's data, which AmpSize does not hold. Use the maker's figure for a motor that runs near its full load.

Phase-to-neutral readings can carry a zero sequence part that the sequence formula leaves out. Enter line-to-line voltages.

See also: Neutral current, Three phase power and Motor.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

Me pēhea te tātai i te Voltage Unbalance?

Tangohia te toharite o ngā voltage rārangi e toru. Kimihia te pānui e tawhiti rawa ana i te toharite. Ko te unbalance he rerekētanga tērā ki runga i te toharite, hei ōrau. Ko 405, 398 me 411 V he toharite 404.67 V, ā, he 1.65 % te rerekē.

He aha te rerekē i waenga i ngā whakamāramatanga rerekētanga me sequence?

Ka whakamahi te whakamāramatanga rerekētanga i te rerekētanga nui rawa mai i te toharite. Ka wehe te whakamāramatanga sequence i te voltage negative sequence ki te voltage positive sequence. Mō te unbalance iti, ka tata ngā mea e rua. Ka hoatu e te taputapu ngā mea e rua.

He aha te voltage unbalance e wera ai te mōtā?

Ka tuku te voltage negative sequence i tētahi iahiko e huri ana ki te rotor. Ka tāpiri ia i te ngaronga me te wera, engari kāore he mahi. He ture mahi kua whakaputaina e kī ana, ka piki te ōrau o te piki pāmahana o te winding ki te 2 × te pūtoru o te ōrau unbalance, tata ana.

Me ine koe i ngā voltage raina, wāhanga rānei?

Whakamahia ngā voltage line-to-line. Me toru ngā phasor e kati ana i tētahi tapatoru te tauritenga sequence, pērā i ngā voltage rārangi. Ka taea e ngā pānui wāhanga-ki-te-neutral te kawe i tētahi wāhanga zero sequence e waiho ana e te tauritenga.

Ka taea e ia te mahi i te kore taurite o te iahiko?

Āe. Kōwhiria ngā iahiko rārangi, ā, uruhia ngā pānui e toru. He maha ngā wā e nui ake ai te current unbalance i te voltage unbalance e puta ai, nō reira ka taea e tētahi voltage unbalance iti te whakaatu hei current unbalance nui ki tētahi mōtā.

He whai hua tēnei?