AS/NZS 3000:2018
Table 5.1, konumohe
Minimum copper earthing conductor size for aluminium active conductors
The earthing tool reads the smallest aluminium earthing conductor for the active conductor size. It is the aluminium companion to the copper table.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 278–279. I tirohia 26 Sept 2026.
Ngā unit: Active mm², Earth mm²
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
14 rārangi
| Active (mm²) | Earth (mm²) |
|---|---|
| 16 | 4 |
| 25 | 6 |
| 35 | 6 |
| 50 | 10 |
| 70 | 10 |
| 95 | 16 |
| 120 | 25 |
| 150 | 25 |
| 185 | 35 |
| 240 | 50 |
| 300 | 70 |
| 400 | 95 |
| 500 | 95 |
| 630 | 120 |