AS/NZS 3000:2018
Table 5.1, aluminium
Minimum copper earthing conductor size for aluminium active conductors
The earthing tool reads the smallest aluminium earthing conductor for the active conductor size. It is the aluminium companion to the copper table.
Na-verify: binasa laban sa naka-print na standard, mga pahina 278–279. Na-check noong 26 Sept 2026.
Mga unit: Active mm², Earth mm²
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
14 na row
| Active (mm²) | Earth (mm²) |
|---|---|
| 16 | 4 |
| 25 | 6 |
| 35 | 6 |
| 50 | 10 |
| 70 | 10 |
| 95 | 16 |
| 120 | 25 |
| 150 | 25 |
| 185 | 35 |
| 240 | 50 |
| 300 | 70 |
| 400 | 95 |
| 500 | 95 |
| 630 | 120 |