AS/NZS 3000:2018

Table 5.2

Acceptable earth electrodes and their installation

The outbuilding earthing tool reads the electrode the installer picks, its least dimension and coating, and the depth or length and cover it is laid to.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 283 (PDF 287). I tirohia 1 Oct 2026.

Ngā unit: Treatment um um, Value M m

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

17 rārangi

Table 5.2, Acceptable earth electrodes and their installation
KindOrientationMaterialTreatmentTreatment umClausePageJurisdictionValue M (m)
electrodeverticalsteelcopper-clad250Table 5.2283
electrodeverticalsteelcopper-plated250Table 5.2283
electrodeverticalsteelstainless500Table 5.2283
electrodeverticalsteelhot-dipped-galvanized63Table 5.2283
electrodeverticalsteelhot-dipped-galvanized63Table 5.2283
electrodeverticalnon‑ferroussolid—Table 5.2283
electrodehorizontalcoppersolid—Table 5.2283
electrodehorizontalcoppersolid—Table 5.2283
electrodehorizontalcopperbare—Table 5.2283
electrodehorizontalcopperbare—Table 5.2283
electrodehorizontalsteelhot-dipped-galvanized63Table 5.2283
electrodehorizontalsteelhot-dipped-galvanized63Table 5.2283
install5.3.6.3(a)283au1.2
install5.3.6.3(b)283nz1.8
install5.3.6.3283both0.5
install5.3.6.3(i)283au3
install5.3.6.3(ii)283nz7.5

Ngā taputapu e pānui ana i tērā (1)

Ngā aratohu me ngā whārangi ako e whakahua ana i tēnei (2)