Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3000:2018

Table C3

Maximum demand, energy demand method for non‑domestic installations

The floor area demand tool reads the VA/m² range and average for each use. It takes no figure from the special equipment rows, which print none.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 473–474 (PDF 477–478). I tirohia 1 Oct 2026.

Ngā unit: Min va VA/m², Max va VA/m², Avg va VA/m²

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

20 rārangi

Table C3, Maximum demand, energy demand method for non-domestic installations
OccupancyUseMin va (VA/m²)Max va (VA/m²)Avg va (VA/m²)EvTotal
OfficesLight and power406050
OfficesAirconditioning, cooling304035
OfficesAirconditioning, reverse cycle203025
OfficesAirconditioning, zonal reheat406050
OfficesAirconditioning, variable volume202020
CarparksOpen air0105
CarparksOpen air, EV charging51510yes
CarparksBasement102015
CarparksBasement, EV charging103020yes
Retail shopsLight and power4010070
Retail shopsAirconditioning204030
WarehousesLight and power51510
WarehousesVentilation555
WarehousesSpecial equipment———
Light industrialLight and power102015
Light industrialVentilation102015
Light industrialAirconditioning305040
Light industrialSpecial equipment———
Taverns, licensed clubsTotal6010080yes
TheatresTotal80120100yes