Circuit loading calculator

Bilangin ang mga point na kayang dalhin ng final subcircuit.

Reads AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Rating ng circuit-breaker
20 A
Cable size
2.5 mm²
Installation
Domestic
Mga lighting point
0
10 A socket-outlet
8
15 A socket-outlet
0
20 A socket-outlet
0
Fixed o stationary na load
0 A
Isama ang cooking appliance
Hindi
Ilapat ang upstream diversity
Hindi

Kabuuan ng mga kontribusyon

8A

Rating ng circuit-breaker
20A

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Mga lighting point0A

    AS/NZS 3000:2018 Table C9

  2. 10 A socket‑outlets8A

    AS/NZS 3000:2018 Table C9

  3. 15 A socket‑outlets0A

    AS/NZS 3000:2018 Table C9

  4. 20 A socket‑outlets0A

    AS/NZS 3000:2018 Table C9

  5. Nakapirming at hindi gumagalaw na load0A

    AS/NZS 3000:2018 Table C9

  6. Kabuuan ng mga kontribusyonResulta8A

    AS/NZS 3000:2018 Table C9

  7. Rating ng circuit-breaker20A

    AS/NZS 3000:2018 Table C9

Tungkol sa calculator na ito

How this is calculated

The tool counts the points a final subcircuit can carry. It reads AS/NZS 3000:2018 Table C9. You enter the breaker rating, the cable size and the points on the circuit.

  1. Lighting points. Each point adds the current that Table C9 gives for a lighting point.
  2. Socket‑outlets. The tool counts 10 A, 15 A and 20 A socket‑outlets. Each group has its own contribution in Table C9.
  3. Fixed and stationary load. You enter the rated current of fixed loads. The tool adds it in full.
  4. Cooking and diversity. If you turn them on, the tool adds the cooking demand and applies the diversity for upstream devices.
  5. Sum of contributions. The tool adds all contributions.
  6. Check. It compares the sum with the breaker rating. The pair of cable size and device rating must also be one that Table C9 lists.
StepTable or clauseWhat it decides
Point contributionsAS/NZS 3000:2018 Table C9The current each point counts for
SumTable C9The total counted load
PairTable C9Whether the cable and device are listed together

Worked example

Limits

The tool fails a circuit when the sum is over the rating. It warns when Table C9 does not pair the cable with the device. It also fails a cooking range that the table does not permit.

It counts points. It does not check the voltage drop or the loop impedance. Use the cable size calculator for those.

See also: Maximum demand with Table C1 and C2, What size breaker for 4 mm² cable and the maximum demand tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng circuit loading tool?

Dinadagdag ng tool ang contribution ng bawat point sa final subcircuit. Ang lighting point ay 0.5 A bawat isa. Ang 10 A socket ay 2 A kapag non‑domestic na installation na walang air conditioning, o 1 A kung hindi. Hindi dapat lumampas ang kabuuan sa rating ng circuit-breaker.

Aling mga table ang ginagamit nito?

Galing ang contribution sa AS/NZS 3000:2018 Table C9. Galing ang cooking demand sa Table C5. Galing ang upstream diversity factor sa Table C4. Galing ang cable at device pair sa parehong Table C9 row.

Ilang socket‑outlet ang puwede kong ilagay sa 20 amp circuit?

Sa domestic installation, ang bawat 10 A na socket ay binibilang na 1 A. Kaya 20 socket ang aabot sa rating ng 20 A device. Kapag ang non‑domestic installation ay walang permanent air conditioning, ang bawat socket ay binibilang na 2 A. Kaya 10 socket ang aabot sa parehong rating.

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.