Lumaktaw sa nilalaman
AmpSize

MCB trip curve at cable limit

I-plot ang MCB trip band laban sa cable na pinoprotektahan nito.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 2 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Uri ng breaker
Curve C
Rating
20 A
Fault current sa malayong dulo
300 A
Fault current sa board
0 A
Standard
NZ · AS/NZS 3008.1.2
Cable size
2.5 mm²
Material
Tanso
Insulation
PVC 75 °C

Pinakahuling trip sa fault current

0.1s

Kakayahang tumagal ng cable sa fault current
0.86s
Instant trip, batayan ng Table 8.1
150A
Instant trip, karaniwang saklaw
100 hanggang 200A
Conventional operating current
29A
Pinakamalaking Zs para sa 0.4 s
1.53Ω

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Conventional operating current29A

    AS/NZS 3000:2018 Cl 2.5.3.1

  2. Mean tripping current, Type C150A

    AS/NZS 3000:2018 Table 8.1

  3. Instantaneous trip sa mean, hindi lalampas sa0.1s

    AS/NZS 3000:2018 Table 8.1

  4. Pinakamalaking Zs para sa 0.4 s1.53Ω

    AS/NZS 3000:2018 Table 8.1

  5. Karaniwang instantaneous band, mababang gilid100A
  6. Karaniwang instantaneous band, mataas na gilid200A
  7. k factor×111.00

    AS/NZS 3008.1.2:2017 Table 52 p.121

  8. Kakayahang tumagal ng cable sa fault current0.86s

    AS/NZS 3008.1.2:2017 Cl 5.3

  9. Pinakahuling trip sa fault currentResulta0.1s

Tungkol sa calculator na ito

How this is calculated

A miniature circuit-breaker does not trip at one exact time for a current. Two breakers of the same type and rating trip at different times, so a maker draws a band: the earliest and the latest each can trip. This tool draws that band for a Type B, C or D breaker, draws the cable's limit beside it, and reads the latest trip time at the fault current you enter.

Three figures come from AS/NZS 3000. A breaker operates within its conventional time at 1.45 times its rating. Table 8.1 takes it as tripping instantly, within 0.1 s, at its mean tripping current: 4 times the rating for Type B, 7.5 for Type C and 12.5 for Type D. The largest loop impedance for a 0.4 s disconnection follows from that current. The rest of the band, the edges of the instant region and the thermal part, is a typical band. AmpSize does not hold AS/NZS 60898, and the result says so.

The cable's line is its adiabatic limit: the time it can carry a fault current before its insulation is damaged, from the k factor of AS/NZS 3008.1, through the fault rating tool. The circuit passes when the breaker's latest time is no longer than the cable's time at that current. Check it at the far end, where the fault current is least and the trip slowest, and give the fault current at the board too: there the current is highest, the cable's time shortest, and the worse of the two ends decides.

StepTable or clauseWhat it decides
Conventional operating currentAS/NZS 3000 Cl 2.5.3.1Where the band starts
Instant trip at the mean currentAS/NZS 3000 Table 8.1 and Para B4.5The current that trips it instantly, and the largest Zs
Instant region and thermal edgesA typical band, not a standardThe earliest and latest trip at each current
The cable's limitAS/NZS 3008.1 Table 52 and Cl 5.3The time the cable withstands the fault
The checkThe latest trip against the cable's timeWhether the breaker clears the fault first

Worked examples

Limits

The band is typical, not a maker's curve. A real breaker clears a large fault in much less than 0.1 s, and limits the energy it lets through; the maker publishes that energy as I²t. Where the band fails a cable at a high current, compare the maker's I²t with k²S² before you change the cable.

gG fuses are not drawn yet. Their curves are in IEC 60269, which AmpSize does not hold.

See also: Loop impedance, Fault rating and IDMT protection.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang pagkakaiba ng B, C at D curve na MCB?

Gaano karaming current ang nagti-trip nito agad. Kinukuha ng AS/NZS 3000 Table 8.1 ang mean bilang 4 na beses ng rating para sa Type B, 7.5 para sa Type C, at 12.5 para sa Type D. Ang mas mataas na type ay nakakaraos sa motor at transformer start.

Bakit iginuguhit bilang band ang trip curve?

Dalawang breaker na magkapareho ang type at rating ay nagti-trip sa magkaibang oras. Ipinapakita ng maker ang pinakamaaga at pinakahuling oras na maaaring mag-trip ang bawat isa. Binabasa ng tool ang pinakahuling oras, kaya nananatiling totoo ang check para sa pinakamabagal na breaker.

Paano ko malalaman kung pinoprotektahan ng breaker ang cable sa fault?

Kayang dalhin ng cable ang fault current sa loob ng oras na itinatakda ng k factor at laki nito, (k × S ÷ I)². Dapat mag-trip ang breaker sa loob ng oras na iyon. Ikinukumpara ng tool ang dalawa sa fault current na ilalagay mo.

Curve ba ng maker ang band?

Hindi. Galing sa AS/NZS 3000 ang operating point, at karaniwan para sa type ang mga gilid ng band. Walang hawak na AS/NZS 60898 ang AmpSize. Tingnan sa curve ng maker ang malapit na resulta.

Paano kung mas maikli sa 0.1 s ang kayang itagal ng cable?

Malapit sa board, mataas ang fault current at ilang millisecond lang tumatagal ang maliit na cable. Naaalis ng breaker ang malaking fault nang mas mabilis sa 0.1 s. Ikumpara ang let-through energy ng maker, I²t, sa k²S².

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 2 Oct 2026.