Voltage rise for a 10 kW three‑phase inverter

Voltage Rise calculator

+3 references

Worked to AS/NZS 3000:2018, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 4777.1:2016. Tables checked 27 Sept 2026.

A three-phase solar inverter on a commercial plant room wall, with isolators beside it.

The question

A commercial roof array feeds a 10 kW inverter in a plant room. The switchboard sits 50 m away. The installer wants to know whether 6 mm² cable holds the voltage rise inside the design limit. The installer also wants to know how much further that cable could run.

Voltage rise is the mirror of voltage drop. The inverter pushes current towards the switchboard. The voltage at the inverter terminals then sits above the voltage at the board. The inverter trips on over-voltage when the rise is too large.

The inputs

  • Phases: 3
  • Voltage: 400 V
  • Inverter rating: 10 kW
  • Power factor: 1
  • Route length: 50 m
  • Cable size: 6 mm²
  • Limit: 2 %
A 14.43 A circuit over 50 m on 6 mm²Supply230 VDevice14.43 A50 m6 mm² CuLoad14.43 A
A 14.43 A circuit over 50 m on 6 mm²

The clause

AS/NZS 3000:2018 Cl 3.6.2 Note 3 points voltage rise at AS/NZS 4777.1. AmpSize does not hold AS/NZS 4777.1. The 2 % figure above is an input to the tool. It is not a value read from a standard. Check the current edition of AS/NZS 4777.1 for the limit and the clause that apply. The tool prints the same caution beside the result.

The conductor data comes from AS/NZS 3008.1.2:2017 Tables 30 to 35. Cl 4.5 of the same Standard sets how resistance and reactance combine at the power factor.

The steps

The tool converts the rating to a current first. A three‑phase inverter at unity power factor divides 10 kW by 400 V and by the square root of three.

  • Inverter output current: 14.43 A
  • Resistance of 6 mm² copper: 3.75 Ω/km
  • Combined figure at a power factor of 1: 6.495 mV/A·m

It multiplies that figure by the current and the route length.

  • Voltage rise: 4.69 V
  • Voltage rise as a percentage: 1.17 %
  • Maximum length at the limit: 85.33 m

The result

The rise is 1.17 % against the 2 % design limit, so 6 mm² passes at 50 m. The cable reaches the limit at 85.33 m, so a re-routed cable still has room.

The three‑phase connection does the heavy lifting here. A single‑phase inverter of the same rating at 230 V would carry a much larger current over the same route. The three‑phase current of 14.43 A is what keeps a 6 mm² cable viable over 50 m.

What to watch

The 2 % figure is a budget, not a hard number from a held standard. Some network companies publish a tighter allowance for the inverter cable. The rise on this cable adds to the rise already present on the network at the point of supply.

Power factor also moves the answer. An inverter set to absorb reactive power runs below unity and carries more current for the same kW. Re-run the case at the power factor the inverter is commissioned to, not at 1.

Check current capacity as a separate step. A cable that passes on rise must still carry the inverter current after derating. The protective device must match as well.

The same job on one phase

A 10 kW single‑phase inverter at 230 V is the usual alternative on a small commercial site. It carries far more current than the three‑phase case. Rise grows with current, so the single‑phase version needs a much larger conductor over the same 50 m.

The three‑phase connection also spreads the export across three phases at the point of supply. A network company often caps single‑phase export for that reason. Ask the network company for its export limit before the inverter is chosen. That limit can decide the phase count.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Voltage rise for a 5 kW solar inverter cable, Voltage drop with the mV/A·m method and PV and inverter basics.

Subukan gamit ang mga input na ito

Size ng Cable
6 mm²
Output ng inverter
10 kW
Haba ng run
50 m
Limitasyon ng voltage rise
2 %
Power factor
1
Mga phase
Three phase
Voltage
400 V
Buksan ang calculator gamit ang mga input na ito

Ano ang susunod

Ang mga ideyang nasa likod nito

Higit pang worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.